© Danfoss | 2017.01 | 9
VI.HX.K4.02
Alarm description DECS 2.0
Event Text Priority Source Trigger condition
ERROR Heatmeter 1 1 ECL, OPR10,
OPR20
Alarm status goes On if heat meter 1 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 2 1 ECL, OPR10,
OPR20
Alarm status goes On if heat meter 2 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 3 1 ECL, OPR10,
OPR20
Alarm status goes On if heat meter 3 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 4 1 ECL, OPR10,
OPR20
Alarm status goes On if heat meter 4 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 5 1 ECL, OPR10,
OPR20
Alarm status goes On if heat meter 5 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 6 1 OPR10
OPR20
Alarm status goes On if heat meter 6 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 7 1 OPR10
OPR20
Alarm status goes On if heat meter 7 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 8 1 OPR10
OPR20
Alarm status goes On if heat meter 8 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 9 1 OPR10
OPR20
Alarm status goes On if heat meter 9 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatmeter 10 1 OPR10
OPR20
Alarm status goes On if heat meter 10 reports a non-zero error code to DECS 2.0. The m-bus
meter alarm is monitored by DECS 2.0.
ERROR Heatquantity 1 2 ECL, OPR10,
OPR20
Alarm status goes On if the consumption value read from energy meter 1 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 2 2 ECL, OPR10,
OPR20
Alarm status goes On if the consumption value read from energy meter 2 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 3 2 ECL, OPR10,
OPR20
Alarm status goes On if the consumption value read from energy meter 3 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 4 2 ECL, OPR10,
OPR20
Alarm status goes On if the consumption value read from energy meter 4 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 5 2 ECL, OPR10,
OPR20
Alarm status goes On if the consumption value read from energy meter 5 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 6 2 OPR10
OPR20
Alarm status goes On if the consumption value read from energy meter 6 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 7 2 OPR10
OPR20
Alarm status goes On if the consumption value read from energy meter 7 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 8 2 OPR10
OPR20
Alarm status goes On if the consumption value read from energy meter 8 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 9 2 OPR10
OPR20
Alarm status goes On if the consumption value read from energy meter 9 is lower than previ-
ous readout. The consumption alarm is monitored by DECS 2.0.
ERROR Heatquantity 10 2 OPR10
OPR20
Alarm status goes On if the consumption value read from energy meter 10 is lower than
previous readout. The consumption alarm is monitored by DECS 2.0.