Panduit CNLTD142A3 Installation guide

Category
Rack accessories
Type
Installation guide

Panduit CNLTD142A3 helps manage airflow in switch cabinets and is compatible with Net Access Legacy or Net-Access N-Type Switch Cabinets. The duct system includes a top seal plate, 4 adjustment brackets, an upper LH bracket, upper RH bracket, upper inlet duct box, side ducting, lower LH bracket, lower RH bracket, lower inlet duct box, and a bottom seal plate. The system requires some assembly and can be installed in two days, with the first day being dedicated to installing side ducts and the second day being dedicated to installing the rest of the components.

Panduit CNLTD142A3 helps manage airflow in switch cabinets and is compatible with Net Access Legacy or Net-Access N-Type Switch Cabinets. The duct system includes a top seal plate, 4 adjustment brackets, an upper LH bracket, upper RH bracket, upper inlet duct box, side ducting, lower LH bracket, lower RH bracket, lower inlet duct box, and a bottom seal plate. The system requires some assembly and can be installed in two days, with the first day being dedicated to installing side ducts and the second day being dedicated to installing the rest of the components.

For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Upper LH
Bracket
(4) Adjustment Brackets
Lower Inlet Duct Box
7009 Duct
Duct System for a Switch Cabinet Mounted
CNLTD142A3 (Cisco 7009)
Component Guide
Front of Cabinet
(Cold Aisle)
Rear of Cabinet
(Hot Aisle)
Upper Inlet Duct Box
Side Ducting
Upper RH
Bracket
Lower LH
Bracket
Lower RH
Bracket
For a Net Access Legacy
or Net-Access N-Type
Switch Cabinet
(N*** or CN***)
Note: Upper RH Bracket
Has Notches On Top.
Note: Lower RH Bracket
Has Notches On Bottom.
Top Seal Plate
Bottom Seal Plate
Page 1 of 14
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
INDEX
Preparing Cabinet for 7009 Duct Installation....................................................................................................................
Device Placement..............................................................................................................................................................
Top / Bottom Left Hand Bracket Installation......................................................................................................................
Top / Bottom Right Hand Bracket Installation....................................................................................................................
Installing Side Duct Day 1: Without Switch or Side Panel Installed...................................................................................
Installing Side Duct Day 2: With Switch and Side Panel Installed
Separate Side Duct Sections..........................................................................................................................................
Section A of Side Duct Installation..................................................................................................................................
Section B of Side Duct Installation..................................................................................................................................
Side Duct Seal Plate Installation........................................................................................................................................
Upper / Lower Duct Box Installation...................................................................................................................................
Securing Vertical Blanking Panel.......................................................................................................................................
PAGE
3
4
5
6
7
8
9
10
11
12
13
Tools Needed:
-Phillips Head Screwdriver
-Socket Wrench
-3/8” Socket
-5/16” Socket
# 12 Star
Washer
# 12-24
Screw
# 10-32
Nut
Hardware Supplied:
Page 2 of 14
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Preparing Cabinet for 7009 Duct Installation
For Legacy Net-Access (CN***) Cabinets Only
If present, remove side panel bumper by unscrewing (4) # 12-24 screws and (4) # 12 washers. (As shown in View A)
Remove (1) # 12-24 bolt from the front of the vertical blanking panel. Save bolt to be reinstalled later. (As shown in View B)
(1) 12-24 Bolt
Bumper
(4) 12-24
Screws
(4) # 12 Star
Washers
View B
View A
Front of Cabinet
(Cold Aisle)
Rear of Cabinet
(Hot Aisle)
Page 3 of 14
Vertical Blanking Panel
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Device Placement for Net-Access Legacy Cabinets (CN***)
Due to physical constraints posed by the front-to-back beams on the Net-Access Legacy cabinet, there are
certain areas of the cabinet that the device cannot be mounted when used in conjunction with this inlet duct.
For Net-Access Legacy cabinets, front equipment rails need to be in full forward position and rear equipment
rails need to be 24.25” - 26.1” back.
NOTES:
Numbers-up RU numbering (#1 at bottom) assumed.
45 RU Net-Access CN*** Cabinet (Legacy)
42 RU Net-Access CN*** Cabinet (Legacy)
Device KEEP-OUT
area - RU 41 - 45
Device KEEP-OUT
area - RU 20 - 26
Device KEEP-OUT
area - RU 1 - 5
Device can be installed
in RU 6 -19
Device can be installed
in RU 27 - 40
Device KEEP-OUT
area - RU 1 - 5
Device can be installed
in RU 6 - 19
Device KEEP-OUT
area - RU 20 - 42
Page 4 of 14
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Device Placement for Net-Access N-Type Cabinets (N***)
For Net-Access N-Type switch cabinets, there are no device keep-out areas. The only restriction on device is
that 3 RU must be left open above and below the switch.
For Net-Access N-Type cabinets front and rear equipment rails need to be 24.25”-24.50” apart.
NOTES:
Numbers-up RU numbering (#1 at bottom) assumed.
Device KEEP-OUT
area - RU 1 - 3
Device KEEP-OUT
area - RU 1 - 3
Device KEEP-OUT
area - RU 42 - 45
Device KEEP-OUT
area - RU 40 - 42
Device can be installed
in RU 4 - 41
Device can be installed
in RU 4 - 39
Page 5 of 14
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Top / Bottom Left Hand Bracket Installation
Measure distance between front and rear equipment rails.
Attach (1) adjustable bracket to each side bracket. (As shown)
Adjust bracket to fit equipment rail spacing.
Tighten adjustment bracket nuts.
Install (1) upper left hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Install (1) lower left hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Upper
Left Hand
Bracket
Front of Cabinet
(Cold Aisle)
(8) #12-24
screws
(8) #12 Star
Washers
Rear of Cabinet
(Hot Aisle)
Lower
Left Hand
Bracket
Vertical Blanking Panels
Adjustment Nuts
Adjustment Bracket
Adjustment Nuts
Adjustment Bracket
Page 6 of 14
Equipment Rail Spacing
Equipment Rail Spacing
Lower
Left Hand Bracket
Upper
Left Hand Bracket
NOTE: If cabinet equipment mounting rails have square holes, one grounding cage nut should be used in each mounting rail.
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Upper
Right Hand
Bracket
Front of Cabinet
(Cold Aisle)
(8) #12-24
screws
(8) #12 Star
Washers
Rear of Cabinet
(Hot Aisle)
Lower
Right Hand Bracket
Top / Bottom Right Hand Bracket Installation
Measure distance between front and rear equipment rails.
Attach (1) adjustable bracket to each side bracket. (As shown)
Adjust bracket to fit equipment rail spacing.
Tighten adjustment bracket nuts.
Install (1) upper right hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Install (1) lower right hand bracket with (4) #12-24 screws and (4) #12 star washers. (Leave screws loose until Inlet Box is installed.)
Adjustment Bracket
Adjustment Nuts
Upper
Right Hand Bracket
Adjustment Nuts
Adjustment Bracket
Lower
Right Hand Bracket
Vertical Blanking Panels
Page 7 of 14
Equipment Rail Spacing
Equipment Rail Spacing
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Side Duct Installation
Install Side Duct by sliding threaded studs on side duct into slots in upper and lower right hand brackets and secure with (4) #10-32
nuts.
NOTE: For Net-Access N-Type cabinets only, attach 1” thick foam seal along edge of side duct. (See Detail Below)
Side Duct
(4) #10-32 Nuts
Vertical Blanking Panels Removed for Clarity.
Rear of Cabinet
(Hot Aisle)
Front of Cabinet
(Cold Aisle)
Installing Side Duct Day 1:
Without Switch or Side Panel in Place.
Page 8 of 14
(4) Threaded
Studs
(4) Bracket
Slots
NOTE:
For Net-
Access N-Type
Cabinets Only,
attach
provided strip
of foam seal
along edge of
side duct.
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Installing Side Duct Day 2:
With Switch and Side Panel in Place.
(4) #10-32 Nuts
Section A
of Side Duct
Section B
of Side Duct
Separate Side Duct Sections
Remove (4) #10-32 nuts.
Separate Section A from Section B.
Page 9 of 14
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Section A of Side Duct Installation
From the rear of the cabinet slide section A of the side duct into cabinet. (Exactly as shown)
Slide the threaded studs on the side duct into the slots in the upper and lower right hand brackets as shown.
Secure side duct to brackets with (4) #10-32 nuts.
(4) #10-32 Nuts
Note:
Shaded area
represents
side panel.
Section A
of Side Duct
Rear of Cabinet
(Hot Aisle)
Front of Cabinet
(Cold Aisle)
Threaded
Stud
Slot in Bracket
7009 Switch
Page 10 of 14
Front to Back Support Brackets Removed for Clarity.
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Section B of Side Duct Installation
From the rear of the cabinet slide section B of the side duct into the cabinet. (Exactly as shown)
Through opening in top right bracket lift side duct into place and slide slots on section B of side duct onto threaded studs on section
A of side duct.
Secure section B to section A with (4) #10-32 nuts,
(4) #10-32 Nuts
Section A
of Side Duct
Note:
Shaded area
represents
side panel.
Front to Back Support Brackets Removed for Clarity.
Section B
of Side Duct
Rear of Cabinet
(Hot Aisle)
Front of Cabinet
(Cold Aisle)
7009 Switch
Slot in Section B
Threaded
Stud
Use Opening in Top Right
Side Bracket to Slide
Section B onto Section A.
Page 11 of 14
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Side Duct Seal Plate Installation
Install top and bottom seal plates to side duct by inserting threaded studs into the holes in the duct and side bracket. Secure the seal
plates in place with (4) #10-32 nuts.
Side Duct
(4) #10-32 Nuts
Rear of Cabinet
(Hot Aisle)
Front of Cabinet
(Cold Aisle)
Top Seal Plate
Bottom Seal Plate
Side Duct
Page 12 of 14
(4) Threaded
Studs
(4) Holes in side
brackets and
duct.
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
Upper / Lower Duct Box Installation
Install (1) upper inlet duct box by sliding box into upper brackets, along built in guide flanges and securing with (2) #10-32 nuts.
Install (1) lower inlet duct box by sliding box into lower brackets, along built in guide flanges and securing with (2) #10-32 nuts.
Tighten all bracket screws that were intentionally left loose earlier.
(2) #10-32 Nuts
Upper Inlet
Duct Box
Lower Inlet
Duct Box
Front of Cabinet
(Cold Aisle)
Rear of Cabinet
(Hot Aisle)
Upper Brackets
Lower Brackets
Page 13 of 14
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2012
CM584A
E-mail:
Phone:
866-405-6654
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
www.panduit.com
Page 14 of 14
Securing Vertical Blanking Panel (For Legacy Net-Access (CN***) Cabinets Only)
Replace the (1) # 12-24 bolt that was removed on page 1.
(1) # 12-24 Bolt
Vertical Blanking Panel
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Panduit CNLTD142A3 Installation guide

Category
Rack accessories
Type
Installation guide

Panduit CNLTD142A3 helps manage airflow in switch cabinets and is compatible with Net Access Legacy or Net-Access N-Type Switch Cabinets. The duct system includes a top seal plate, 4 adjustment brackets, an upper LH bracket, upper RH bracket, upper inlet duct box, side ducting, lower LH bracket, lower RH bracket, lower inlet duct box, and a bottom seal plate. The system requires some assembly and can be installed in two days, with the first day being dedicated to installing side ducts and the second day being dedicated to installing the rest of the components.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI