FAULT FINDING
0740 800 218
- 18 -
© ESAB AB 2014
7. Check the air sensor. Measure the continuity over the connectors on the air sensor. If the
air sensor is open (no continuity), replace the air sensor, see instructions in section
“Replace the air sensor” in chapter “Service instructions”. If the air sensor is closed
(continuity), it is working.
8. Check the solenoid valve. Measure the voltage over the connectors on the solenoid
valve. The value should be 24 V AC.
If not, measure over pin 2 and 8 on the connector J2 on the display board. If there is
voltage on the display board, replace the solenoid valve, see instructions in section
“Replace the solenoid valve” in chapter “Service instructions”.
If there is no voltage, replace the display board, see instructions in section “Replace the
display board” in chapter “Service instructions”.
PIP LED blinking, air pressure LED lit, low air pressure
The green LED is lit, the PIP LED is blinking, the air pressure LED lit and the air pressure is
low. The torch is not working.
1. Check the external air supply.
2. Check external air hoses and connections for leakage, dirt or damage.
3. Check the pressure gauge on the air regulator. At least 70 psi (4.8 bar) is required for
cutting.
If there is external air supply of at least 70 psi (4.8 bar) and 23.8 gallon/m (90 l/m) but not
possible to adjust the pressure on the air regulator, replace the air regulator.
4. Check the air hoses inside the power source for loose connections, damage and
leakage.
5. Check the air regulator for leakage, dirt or damage.
6. Check the set air regulator for leakage, dirt or damage.
7. Check the air sensor. Measure the continuity over the connectors on the air sensor. If the
air sensor is open (no continuity), replace the air sensor, see instructions in section
“Replace the air sensor” in chapter “Service instructions”. If the air sensor is closed
(continuity), it is working.
8. Check the solenoid valve. Measure the voltage over the connectors on the solenoid
valve. The value should be 15 V DC.
If not, measure over pin 2 and 8 on the connector J2 on the display board. If there is
voltage on the display board, replace the solenoid valve, see instructions in section
“Replace the solenoid valve” in chapter “Service instructions”.
If there is no voltage, replace the display board, see instructions in section “Replace the
display board” in chapter “Service instructions”.
Over temperature LED blinking
The green LED is lit the over temperature LED is blinking. The torch is not working.
1. The duty cycle is too high. Wait for a while to let the fans cool down the equipment.
2. Does the over temperature indication appear frequently? Check the fan, is it running
without problems? If not, replace the fan.
3. Check the thermal switches at normal temperature. Measure the continuity. If any of
them are open replace the damaged thermal switch.
4. Does the over temperature indication appear frequently together with transfer problems
between the pilot arch and cutting arc? Replace the pilot arc board.