Where field wiring and control panel wiring must be joined at a terminal block, a connector is used to facilitate
770MAX instrument-to-sensor wiring, as described below.
Install a 25320 connector near the terminal block for each 770MAX Smart Sensor. Connect a 1005-87 5 ft. (1.5
m) or 1015-87 15 ft. (4.5 m) extension cable from the 770MAX to the connector. Connect a patch cord from
the connector to the sensor. All connections are plug-in. (Screw terminal wiring is not recommended because
each patch cord has ten #28 AWG conductors.)
Although not recommended because of difficulty in assembly, shortened patch cords or extension cables can be
made by cutting off the modular connector (instrument end) and installing AMP plug 5-557963-3 using AMP
hand crimp tool 58560-1 on the shortened cord.
Technical Note
770MAX Control Panel to Sensor Wiring
THORNTON
Leading Pure Water Analytics
25320 Connector for
patch cord extension
0.88 x 1.5 x 0.63"
(22 x 38 x 16 mm)
10XX-87 Extension Cable
5 or 15 ft.
(1.5 or 4.6 m)
Smart Sensor with Connector
1XXX-79 Patch Cord
1-300 ft. (0.3-91 m)
770MAX
www.thorntoninc.com
For the most current product information visit:
www.thorntoninc.com
Created 10/00
Updated logo & address 09/03
Mettler-Toledo Thornton, Inc.
36 Middlesex Turnpike
Bedford, MA 01730 USA
Telephone: +1-781-301-8600
Toll-Free: 1-800-510-PURE
Customer/Technical Service
Telephone: +1-781-301-8690
Toll-Free: 1-800-642-4418
Cust Service Fax: +1-781-271-0214
Tech Service Fax: +1-781-271-0675
Mettler-Toledo Thornton, Inc. – Subject to Technical Changes
  • Page 1 1

Mettler Toledo 770MAX Control Panel to Sensor Wiring Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI