Viessmann Vitodens 200-W System Datasheet

Category
Space heaters
Type
Datasheet

This manual is also suitable for

VITODENS
200-W
Gas-fired wall-mounted condensing boiler
31 to 370 MBH / 9 to 105 kW
Multi-boiler installation 320 to 1480 MBH/
Vitodens 200-W
WB2B Series
Gas-Fired Wall-Mounted Condensing Boiler
with modulating MatriX cylinder burner
for room air independent operation
(using a direct vent system) or room air
dependent operation
For Natural Gas and Liquid Propane Gas
Heating input 31 to 370 MBH
for NG and LPG 9 to 105 kW
Technical Data Manual
Model Nos. and pricing: see Price List
This trademark is registered with the U.S. Patent and Trademark Office.
5369 295 v1.5 09/2012
Product Information
2
VITODENS 200-W
Equipped with the industry’s first intelligent
combustion management system and
powerful control technology, the new
generation Vitodens 200-W gas-fired
wall-mount condensing boiler delivers
unparalleled performance, reliability and
comfort.
The benefits at a glance:
HBest value in its class with new
industry-leading technology and the most
standard features.
HHighest Efficiency up to 98% at full
modulation and up to 96.1% A.F.U.E.
CSA thermal efficiency rating to ANSI
Z.21.13/CSA 4.9 of 94.5% (for model
WB2B 105 only). Energy Star and the
CSA Energy Performance are not
applicable for model WB2B 105.
HLasting performance with industry-leading
Viessmann made SA240 316 Ti stainless
steel Inox-Radial heat exchanger
constructed to CSA B51 and ASME
Section IV.
HLow Emission Combustion with Viessmann
made stainless steel MatriX cylinder
burner. Factory calibrated.
HFast Installation and Reduced Maintenance
with Lambda Pro, industry-first intelligent
combustion management system: Adjusts
automatically to gas type and quality. No
fuel conversion kit required.
HPowerful and User-friendly
Viessmann Vitotronic on-board
multi-function outdoor reset boiler and
system control for multi-temperature
space and DHW heating.
HExpanded Application Range with
increased capacity up to 370 MBH.
Multi-boiler installation up to 1480 MBH
with up to 4 boilers (models WB2B 45,
60, 80, 105).
HGreater Venting Flexibility with increased
vent length (up to 180 ft. / 55 m) and
multiple venting options.
- Horizontal or vertical sealed combustion
coaxial venting (factory supplied).
- Horizontal, vertical or hybrid sealed
combustion double-pipe venting (field
supplied).
- Horizontal or vertical single-wall venting
(field supplied).
HCompact, Esthetic Product Design
and zero clearance to combustibles.
HExtremely Quiet Operation; quieter than
most refrigerators.
HTrue High-Altitude Operation up to
10,000 ft. / 3,000 m with simple
electronic adjustment.
HEfficiency up to 98% through intensive
condensation. The flue gas temperature is
only approximately 9-27º F (5-15º C)
above boiler return temperature (see chart
below).
5
3
6
9
2
9
5
v
1
.
5
Inox-Radial
heat exchanger
Modulating MatriX
cylinder burner
Vitotronic 200, HO1
on-board outdoor
reset control
Boiler may not look exactly as illustrated.
Cross-Section
3
5
3
6
9
2
9
5
v
1
.
5
Technical Data
4
Table 1.
Boiler Model Model No. WB2B- 19 26 35 45 60 80 105*
A
Natural gas / Liquid propane gas
CSA input
CSA output/DOE
*1
heating capacity
MBH
kW
MBH
kW
31-67
9-20
28-61
8-18
31-93
9-27
28-85
8-25
31-125
9-37
28-114
8-33
60-160
17-47
55-146
16-43
60-212
17-62
55-194
16-57
104-285
30-83
95-260
28-76
104-370
30-108
98-350
29-103
Net I=B=R rating
*2
MBH 53 74 99 127 169 226 304
Heat exchanger surface area ft.
2
m
2
10.23
0.95
10.23
0.95
10.23
0.95
15.76
1.46
15.76
1.46
28.88
2.68
28.88
2.68
Min. gas supply pressure
Natural gas
Liquid propane gas
“w.c.
“w.c.
4
10
4
10
4
10
4
10
4
10
4
10
4
10
Max. gas supply pressure
*3
Natural gas
Liquid propane gas
“w.c.
“w.c.
14
14
14
14
14
14
14
14
14
14
14
14
14
14
A.F.U.E. % 96.1 96.1 96.1 96.1 96.1 96.1
CSA thermal efficiency
ANSI Z21.13/CSA 4.9 % 94.5
Weight lbs
kg
102
46
102
46
102
46
155
70
155
70
225
102
225
102
Boiler water content USG
L
0.87
3.3
0.87
3.30
0.87
3.3
1.9
7.2
1.9
7.2
3.4
12.8
3.4
12.8
Boiler max. flow rate
*4
GPM
L/h
6.2
1400
6.2
1400
6.2
1400
15.4
3500
15.4
3500
35.2
8000
35.2
8000
Max. operating pressure
at 210ºF / 99ºC
psig
bar
45
3
45
3
45
3
60
4
60
4
60
4
60
4
Boiler water temperature
– Adjustable high limit (AHL)
range
space heating
(steady state)
DHW production
Fixed high limit (FHL)
ºF/
ºC
ºF/
ºC
ºF/ºC
68 to 165 /
20 to 74
165 /
74
210/99
68 to 176 /
20 to 80
176 /
80
210/99
Boiler connections
Boiler heating supply and return NPTM “
Pressure relief valve NPTF “
Drain valve (male
thread)
Boiler supply/return for
indirect-fired DHW storage tank NPT”
(field supplied)
Gas valve connection NPTF
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
¾
1
¾
¾
1
¾
¾
1
¾
¾
1
*
A
For high altitude installations (5,000 - 10,000 ft.), the input for model WB2B 105 will have an altitude de-ration of 14% for 5,000 ft.
and 28% for 10,000 ft. (average of 2.8% / 1,000 ft.).
*1
Output based on 140ºF / 60ºC, 120ºF / 49ºC system supply/return temperature.
*2
Net I=B=R rating based on piping and pick-up allowance of 1.15.
*3
If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed upstream of the
heating system.
*4
See “Typical System Flow Rates” on page 11 in this manual.
5
3
6
9
2
9
5
v
1
.
5
Technical Data
5
Table 1 (continued)
Boiler Model Model No. WB2B- 19 26 35 45 60 80 105*
A
Dimensions
Overall depth
Overall width
Overall height
Height with flue gas elbow
(accessory)
inches
mm
inches
mm
inches
mm
inches
mm
14
360
17¾
450
33½
850
44
1116
14
360
17¾
450
33½
850
44
1116
14
360
17¾
450
33½
850
44
1116
15
380
19
480
33½
850
47¼
1200
15
380
19
480
33½
850
47¼
1200
21
530
19
480
33½
850
47¼
*9
1200
21
530
19
480
33½
850
47¼
*9
1200
Flue gas
*5
Temperature (at boiler return
temperature of 86ºF / 30ºC)
– at rated full load
– at rated partial load
Temperature (at boiler return
temperature of 140ºF / 60ºC)
ºF/ºC
ºF/ºC
ºF/ºC
113/45
95/35
154/68
113/45
95/35
158/70
113/45
95/35
158/70
95/35
91/33
149/65
104/40
95/35
158/70
95/35
91/33
149/65
104/40
95/35
158/70
Average condensate
flow rate
*6
with natural gas and
T
S
/T
R
=104/86ºF / 40/30ºC USG/day
L/day
2.6-3.4
10-12
2.9-3.4
11-13
4-4.5
15-17
3.7-5
14-19
6-7.4
23-28
6.6-7.9
25-30
9.5-10.5
35-40
Condensate connection
*7
hose
nozzle
in 1 1 1 1 1 1 1
Boiler flue gas connection
*8
in/mm 2
3
/
8
/60 2
3
/
8
/60 2
3
/
8
/60 3¼/80 3¼/80 4
3
/
8
/110 4
3
/
8
/110
Combustion air supply
connection (coaxial)
*8
outer
in/mm 4/100 4/100 4/100 5/125 5/125 6/150 6/150
*
A
For high altitude installations (5,000 - 10,000 ft.), the input for model WB2B 105 will have an altitude de-ration of 14% for 5,000 ft.
and 28% for 10,000 ft. (average of 2.8% / 1,000 ft.).
*5
Measured flue gas temperature with a combustion air temperature of 68°F / 20°C.
*6
Based on typical boiler cycles, including partial load conditions.
*7
Requires 1” / 25 mm tubing. See the Installation Instructions of the Vitodens 200-W, WB2B for details.
*8
For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, WB2B Venting System.
Amaximum of 5elbows may be installed in the vent system.
Do not attempt to common-vent Vitodens 200-W with any other appliance.
Venting material to be supplied by Viessmann only; side wall vent installation must include Viessmann protective screen!
For details refer to the Installation Instructions for the Vitodens 200-W, WB2B Venting System.
*9
Add 2½” / 65 mm for coaxial vent pipe transition adaptor.
"For information regarding other Viessmann System Technology componentry, please reference documentation of respective product.
5
3
6
9
2
9
5
v
1
.
5
Dimensional Information
6¼” / 158 mm
5
5
/
8
” /
143 mm
1¾” /
44 mm
14
1
/
8
” /
360 mm
2¾” /
70 mm
2½” /
65 mm
7” / 177 mm
13¾” /
348 mm
8
7
/
8
” / 225 mm
4” / 102 mm
4” / 102 mm
33½” /
850 mm
12” /
300 mm
2¾” /
70 mm
17¾” /
450 mm
BS BR
PRV
BD
DS
GC
DR
BF
*
1
DHW Connections
(Field Supplied)
EXTEXT
Floor line
78” / 1975 mm
for single boiler
installation
Fig. 1
Fig. 2
Fig. 3
6
*1
Models WB2B 19, 26, 35
Legend
BD Boiler Drain
BR Boiler Return
BS Boiler Supply
AV Air Vent (not shown)
GC Gas Connection, ¾” NPT
PRV Pressure Relief Valve
BF Boiler Fill
PG Pressure Gage
EXT Extension Adaptors, ¾” NPT
DR Boiler heating return for domestic hot
water production ¾” (field supplied)
DS Boiler heating supply for domestic
hot water production ¾” (field
supplied)
*
1
See page 38 for alternate DHW
connection.
5
3
6
9
2
9
5
v
1
.
5
Dimensional Information
19” / 480 mm
9½” / 240 mm
35½” /
902 mm
39” /
996 mm
41¾” /
1061 mm
51” /
1301 mm
78” / 1975 mm
for single boiler
installation
9½” /
240 mm
6½” /
165 mm
9½” / 240 mm
3” / 80 mm
15¾” /
400 mm
6½” /165 mm
5½” / 146 mm
4” / 100 mm
15” /
380 mm
Ø 5” /
125 mm
33½ “/
850 mm
12” /
305 mm
PRV
BD
GC
BF
PG
Floor line
BS BR
DS DR
*
1
DHW Connections
(Field Supplied)
Fig. 4
Fig. 5
Fig. 6
7
Models WB2B 45, 60
Legend
BD Boiler Drain
BR Boiler Return
BS Boiler Supply
AV Air Vent (not shown)
GC Gas Connection, 1” NPT
PRV Pressure Relief Valve
BF Boiler Fill
PG Pressure Gage
DR Boiler heating return for domestic hot
water production 1¼” NPT (field supplied)
DS Boiler heating supply for domestic hot
water production 1¼” NPT (field supplied)
*
1
See page 38 for alternate DHW
connection.
5
3
6
9
2
9
5
v
1
.
5
Dimensional Information
19” /
480mm
9½” /
240mm
4¼” /
108mm
33½” /
850mm
43” /
1090mm
3” / 80mm
9½” / 240mm
15¾” /
400mm
6½” /
165mm
9½” /
240mm
9½” /
236mm
4” / 102mm
21” /
530mm
15¾” /
400mm
Floor line PRV
BD
GC
BF
PG
78” / 1975 mm
for single boiler
installation
BS BR
DS
*
1
DHW Connections
(Field Supplied)
DR
Fig. 7
Fig. 8
11
5
/
8
“ / 295mm
for WB2B 80-105
using the coaxial
vent system
Fig. 9
8
Models WB2B 80, 105
Legend
BD Boiler Drain
BR Boiler Return
BS Boiler Supply
GC Gas Connection, 1” NPT
PRV Pressure Relief Valve
BF Boiler Fill
PG Pressure Gage
DR Boiler heating return for domestic hot water production 1¼”
DS Boiler heating supply for domestic hot water production 1¼”
*
1
See page 38 for alternate DHW connection.
5
3
6
9
2
9
5
v
1
.
5
Minimum Clearances
9
Recommended Minimum Service Clearances
Minimum Clearances to Combustibles
Top Front Rear Left Right Vent pipe
*1
0 0 AL, CL 0 0 0 0
AL= Alcove
CL= Closet
*1
Refer to the Installation Instructions of the Vitodens 200-W, WB2B Venting System for details.
Please note:
The Vitodens boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the Harmonized Standard
ANSI Z21.13. CSA 4.9.2000 and therefore is listed for zero clearance to combustibles when vented with a single wall special venting
system (AL-29-4C material). The zero inches vent clearance to combustibles for the Vitodens boiler supercedes the clearance to
combustibles listing that appears on the special venting system label.
5
3
6
9
2
9
5
v
1
.
5
Front
12” / 305 mm
Top
12”/305 mm
0”/mm
Side
0”/mm
Back
Side
28” / 700 mm
Fig. 10
Waterside Flow
10
Waterside Flow (primary circuit)
The Vitodens 200-W, WB2B is designed for closed loop, forced circulation hot water heating systems only.
Pressure drop (primary circuit) for Vitodens
200-W, WB2B 19, 26, 35
For sizing an on-site circulation system.
Max. flow rate: 1400 L/h / 6.2 GPM
Pressure drop (primary circuit) for Vitodens
200-W, WB2B 45, 60
For sizing an on-site circulation system.
Max. flow rate 3500 L/h / 15.4 USGPM
Pressure drop (primary circuit) for Vitodens
200-W, WB2B 80, 105
For sizing an on-site circulation system.
Max. flow rate 8000 L/h / 35.2 USGPM
Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds
boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly
recommends the installation of a low-loss header. An alternative method may be used, such as primary secondary piping using closely
spaced tees. A low-loss header offers additional benefits not provided by a pair of closely spaced tees. Viessmann therefore strongly
recommends and prefers the use of a low-loss header over closely spaced tees. See page 13 for low-loss header information.
5
3
6
9
2
9
5
v
1
.
5
0 500 1000 1500
0
1
2
3
4
5
6
0
3.3
6.6
9.8
13.1
16.4
19.7
2000 l/h
7
8
23
26
Supply head pressure (water)
0 2.2 4.4 6.6 8.8 GPM
H(ft.) H(m)
Fig. 11
H(ft.) H(m)
20.1 6.1
16.7 5.1
13.4 4.1
10.0 3.1
6.7 2.0
3.4 1.0
0 0
0
0500 1000 1500 2000 2500 3000 3500 l/h
2.2 4.4 6.6 8.8 11 13.2 15.4 GPM
Supply head pressure (water)
Fig. 12
H(ft.) H(m)
33.5 10.2
30.1 9.2
8.226.8
7.123.4
6.120.1
5.116.7
4.113.4
3.110.0
2.0
6.7
1.03.4
00 0
0
1000 2000 3000 4000 5000 6000 7000 8000 l/h
4.4 8.8 13.2 17.6 22.0 26.4 30.8 35.2 GPM
Supply head pressure (water)
Fig. 13
System Flow Rates
11
Typical System Flow Rates
Table 2.
Model WB2B 19 26 35
t for NG/LPG
Output (NG/LPG)
Btu/h
61 000 85 000 114 000
20ºF rise (GPM) 6.1 8.5 11.4
25ºF rise (GPM) 4.9 6.8 9.1
30ºF rise (GPM) 4.1 5.7 7.6
35ºF rise (GPM) 3.5 4.9 6.5
40ºF rise (GPM) 3.1 4.3 5.7
Table 3.
Model WB2B 45 60
t for NG/LPG
Output (NG/LPG)
Btu/h
146 000 194 000
20ºF rise (GPM) 14.6 19.4
25ºF rise (GPM) 11.7 15.5
30ºF rise (GPM) 9.7 12.9
35ºF rise (GPM) 8.3 11.1
40ºF rise (GPM) 7.3 9.7
Table 4.
Model WB2B 80 105
t for NG/LPG
Output (NG/LPG)
Btu/h
260 000 350 000
20ºF rise (GPM) 26.0 35.0
25ºF rise (GPM) 20.8 28.0
30ºF rise (GPM) 17.3 23.3
35ºF rise (GPM) 14.9 20.0
40ºF rise (GPM) 13.0 17.5
Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds
boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly
recommends the installation of a low-loss header. Once the low-loss header is connected, the built-in low-loss header logic of the Vitodens
200-W boiler ensures the required
T across the system through the sensory communication between the low-loss header and the boiler.
See page 13 for low-loss header information.
5
3
6
9
2
9
5
v
1
.
5
Boiler max. flow rate 1400 L/h (6.2 GPM)
Boiler max. flow rate 3500 L/h (15.4 GPM)
Boiler max. flow rate 8000 L/h (35.2 GPM)
Pump Information
12
Heating Circuit / Boiler Pumps
Viessmann offers a variety of Grundfos heating circuit / boiler pumps which meet typical Vitodens system installation requirements (see
“Heating circuit pump (field supplied)“ or “Boiler pump (field supplied)” in the Installation Examples starting on page 29). See tables below
for recommended pumps. Refer to the graphs on page 10 for the proper waterside boiler friction loss calculations.
Pump selection must be based on accurate
system flow and pressure drop calculations
(incl. DHW sizing).
The following pumps have been selected based on boiler heat exchanger head loss and boiler piping to a low-loss header. Before
using the following pumps for a DHW tank application, find out the proper pressure drop through the tank, the required
temperature difference through the coil and system piping head loss of the domestic hot water.
Table 5.
Model WB2B 19 26 35
Flow rate
20 ºF
t
6.1 8.5 11.4
25 ºF
t
4.9 6.8 9.1
30 ºF
t
4.1 5.7 7.6
35 ºF
t
3.5 4.9 6.5
40 ºF
t
3.1 4.3 5.7
Flow limitation L/h / GPM 1400 / 6.2
Recommended boiler pumps Grundfos 15-58 (3-speed)
Taco 00R
Wilo Star S 21 FX
Table 6.
Model WB2B 45
Flow rate Boiler pressure
drop (ft.)
Recommended pump option 1
Grundfos
Recommended pump option 2
Grundfos
20 ºF
t
14.6 15.8 UPS 26-99FC, 115V, Speed3
25 ºF
t
11.7 10.0 UPS 26-99FC, 115V, Speed2 UP 26-64F, 115V
30 ºF
t
9.7 7.5 UPS 26-99FC, 115V, Speed2
35 ºF
t
8.3 5.8 UPS 26-99FC, 115V, Speed1
40 ºF
t
7.3 4.2 UPS 26-99FC, 115V, Speed1
Flow limitation L/h / GPM 3500 / 15.4
Table 7.
Model WB2B 60
Flow rate Boiler pressure
drop (ft.)
Recommended pump option 1
Grundfos
Recommended pump option 2
Grundfos
20 ºF
t
19.4 Not Recommended Not Recommended
25 ºF
t
15.5 16.7 UPS 26-99FC, 115V, Speed3
30 ºF
t
12.9 12.6 UPS 26-99FC, 115V, Speed3 UP 26-64F, 115V
35 ºF
t
11.1 9.2 UPS 26-99FC, 115V, Speed2 UP 26-64F, 115V
40 ºF
t
9.7 7.5 UPS 26-99FC, 115V, Speed2
Flow limitation L/h / GPM 3500 / 15.4
5
3
6
9
2
9
5
v
1
.
5
IMPORTANT
Pump and Low-Loss Header Information
13
Heating Circuit / Boiler Pumps (continued)
Table 8.
Model WB2B 80
Flow rate Boiler pressure
drop (ft.)
Recommended pump
Grundfos
20 ºF
t
26.0 16.7 UPS 32-160/2, 115V, Speed1 / UPS 26-150F, 115V, Speed 3
25 ºF
t
20.8 9.2 UPS 26-99FC, 115V, Speed3
30 ºF
t
17.3 6.5 UPS 26-99FC, 115V, Speed2
35 ºF
t
14.9 4.8 UPS 26-99FC, 115V, Speed2
40 ºF
t
13.0 3.4 UPS 26-99FC, 115V, Speed2
Flow limitation L/h / GPM 8000 / 35.2
Table 9.
Model WB2B 105
Flow rate Boiler pressure
drop (ft.)
Recommended pump
Grundfos
20 ºF
t
35.0 30.0 UPS 32-160/2, 115V, Speed3
25 ºF
t
28.0 20.0 UPS 32-160/2, 115V, Speed2 / UPS 26-150F, 115V, Speed 3
30 ºF
t
23.3 12.5 UPS 32-160/2, 115V, Speed1
35 ºF
t
20.0 9.0 UPS 26-99FC, 115V, Speed3
40 ºF
t
17.5 6.4 UPS 26-99FC, 115V, Speed2
Flow limitation L/h / GPM 8000 / 35.2
Table 10. Sizing of Low-Loss Header in a Residential Single-Boiler Application
Boiler
Model
No. of
Boilers
Boiler
Max.
Flow Rate
Typical System Flow Rates Viessmann
Temp. Sensor
Required
System
t*1
20
11.0
25
13.9
30
16.8
35
16.1
40
13.4
°F
°C
WB2B 19 1 6.1
1385
System Flow Rate
LLH Required
LLH Model
6.1
1385
Yes
80/60
4.9
1108
Optional
80/60
4.1
924
Optional
80/60
3.5
792
Optional
80/60
3.1
693
Optional
80/60
GPM
L/h
Yes
WB2B 26 1 6.1
1385
System Flow Rate
LLH Required
LLH Model
8.5
1931
Yes
80/60
6.8
1544
Yes
80/60
5.7
1287
Optional
80/60
4.9
1103
Optional
80/60
4.3
965
Optional
80/60
GPM
L/h
Yes
WB2B 35 1 6.1
1385
System Flow Rate
LLH Required
LLH Model
11.4
2589
Yes
80/60
9.1
2071
Yes
80/60
7.6
1726
Yes
80/60
6.5
1480
Yes
80/60
5.7
1295
Optional
80/60
GPM
L/h
Yes
WB2B 45 1 15.4
3498
System Flow Rate
LLH Required
LLH Model
14.6
3316
Yes
80/60
11.7
2653
Optional
80/60
9.7
2211
Optional
80/60
8.3
1895
Optional
80/60
7.3
1658
Optional
80/60
GPM
L/h
Yes
WB2B 60 1 15.4
3498
System Flow Rate
LLH Required
LLH Model
19.4
4406
Yes
80/60
15.5
3525
Yes
80/60
12.9
2937
Optional
80/60
11.1
2518
Optional
80/60
9.7
2203
Optional
80/60
GPM
L/h
Yes
WB2B 80 1 35
7949
System Flow Rate
LLH Required
LLH Model
26.0
5905
Yes
120/80
20.8
4724
Yes
120/80
17.3
3937
Optional
120/80
14.9
3374
Optional
120/80
13.0
2953
Optional
120/80
GPM
L/h
Yes
WB2B 105 1 35
7949
System Flow Rate
LLH Required
LLH Model
35.2
7949
Yes
120/80
28.0
6359
Yes
120/80
23.3
5300
Yes
120/80
20.0
4542
Optional
120/80
17.5
3975
Optional
120/80
GPM
L/h
Yes
*1
For system t<20°F use low-loss header sizes for t 20°F.
5
3
6
9
2
9
5
v
1
.
5
Low-Loss Header Information
14
Low-Loss Header Application (continued)
Table 11. Sizing of Low-Loss Header in a Commercial Multiple-Boiler Application
Boiler
Model
No. of
Boilers
Boiler
Max.
Flow
Rate
Total
Flow
Rate
Typical System Flow Rates Viessmann
Temp.Sensor
Required
*2
System
t*1
20
11.0
25
13.9
30
16.8
35
16.1
40
13.4
°F
°C
WB2B 45 2 15.4
3498
30.8
6995
System Flow Rate
LLH Required
LLH Model
29.2
6632
Yes
120/80
23.4
5306
Yes
120/80
19.5
4421
Yes
120/80
16.7
3790
Yes
120/80
14.6
3316
Yes
120/80
GPM
L/h
Yes
WB2B 45 3 15.4
3498
46.2
10493
System Flow Rate
LLH Required
LLH Model
43.8
9948
Yes
160/80
35.0
7958
Yes
120/80
29.2
6632
Yes
120/80
25.0
5685
Yes
120/80
21.9
4974
Yes
120/80
GPM
L/h
Yes
WB2B 45 4 15.4
3498
61.6
13991
System Flow Rate
LLH Required
LLH Model
58.4
13264
Yes
200/120
46.7
10611
Yes
200/120
38.9
8843
Yes
160/80
33.4
7579
Yes
120/80
29.2
6632
Yes
120/80
GPM
L/h
Yes
WB2B 60 2 15.4
3498
30.8
6995
System Flow Rate
LLH Required
LLH Model
38.8
8812
Yes
160/80
31.0
7050
Yes
120/80
25.9
5875
Yes
120/80
22.2
5036
Yes
120/80
19.4
4406
Yes
120/80
GPM
L/h
Yes
WB2B 60 3 15.4
3498
46.2
10493
System Flow Rate
LLH Required
LLH Model
58.2
13219
Yes
200/120
46.6
10575
Yes
200/120
38.8
8812
Yes
160/80
33.3
7554
Yes
120/80
29.1
6609
Yes
120/80
GPM
L/h
Yes
WB2B 60 4 15.4
3498
61.6
13991
System Flow Rate
LLH Required
LLH Model
77.6
17625
Yes
200/120
62.1
14100
Yes
200/120
51.7
11750
Yes
200/120
44.3
10071
Yes
160/80
38.8
8812
Yes
160/80
GPM
L/h
Yes
WB2B 80 2 35
7949
70
15899
System Flow Rate
LLH Required
LLH Model
52.0
11810
Yes
200/120
41.6
9448
Yes
160/80
34.7
7874
Yes
160/80
29.7
6749
Yes
160/80
26.0
5905
Yes
160/80
GPM
L/h
Yes
WB2B 80 3 35
7949
105
23848
System Flow Rate
LLH Required
LLH Model
78.0
17716
Yes
200/120
62.4
14173
Yes
200/120
52.0
11810
Yes
200/120
44.6
10123
Yes
200/120
39.0
8858
Yes
160/80
GPM
L/h
Yes
WB2B 80 4 35
7949
140
31797
System Flow Rate
LLH Required
LLH Model
104.0
23621
Yes
250/150
83.2
18897
Yes
250/150
69.3
15747
Yes
200/120
59.4
13498
Yes
200/120
52.0
11810
Yes
200/120
GPM
L/h
Yes
WB2B 105 2 35
7949
70
15899
System Flow Rate
LLH Required
LLH Model
70
15899
Yes
200/120
56
12719
Yes
200/120
47
10599
Yes
200/120
40
9085
Yes
160/80
35
7949
Yes
160/80
GPM
L/h
Yes
WB2B 105 3 35
7949
105
23848
System Flow Rate
LLH Required
LLH Model
105
23848
Yes
250/150
84
19078
Yes
250/150
70
15899
Yes
200/120
60
13627
Yes
200/120
53
11924
Yes
200/120
GPM
L/h
Yes
WB2B 105 4 35
7949
140
31797
System Flow Rate
LLH Required
LLH Model
140
31797
Yes
300/200
112
25438
Yes
250/150
93
21198
Yes
250/150
80
18170
Yes
200/120
70
15899
Yes
200/120
GPM
L/h
Yes
NOTE: for multiple boiler applications when using the the Vitodens 200-W, WB2B boilers, refer to the multiple boiler low-loss distribution
manifold installation instructions.
*1
For system
t<20°F use low-loss header sizes for
t 20°F.
*
2
Low-Loss sensor - standard equipment of the Vitocontrol-S WB2B: for use in multiple boiler applications.
5
3
6
9
2
9
5
v
1
.
5
DHW Production
15
Domestic Hot Water Production
Vitodens 200-W boilers can be used in conjunction with the stand-alone DHW storage tanks offered by Viessmann.
All Viessmann DHW storage tanks sold in North America are available in “Vitosilver” finish only.
Size and select the DHW storage tank based on the forecasted DHW consumption of the building in question.
For further technical information on DHW storage tanks, see the Vitocell-V Technical Data Manuals.
For the connection of a stand-alone DHW tank, installation fittings (field supplied), an external circulating pump for DHW production (field
supplied) and a DHW temperature sensor (optional equipment, see Viessmann Price List for order information) are required.
Legend
DR Boiler heating return for domestic
hot water production
DS Boiler heating supply for domestic
hot water production
HR Heating Return
HS Heating Supply
BD Boiler Drain
BR Boiler Return
BS Boiler Supply
GC Gas Connection
PRV Pressure Relief Valve
BF Boiler Fill
PG Pressure Gage (not shown)
*
1
See page 38 for alternate DHW connection.
An adequately sized precharged expansion
tank must be used. See Installation
Examples for details.
5
3
6
9
2
9
5
v
1
.
5
DR
HR
HS
DS
Fig. 14
PRV
BD
GC
BF
BS BR
DS
*
1
DHW Connections
(Field Supplied)
DR
Fig. 15
IMPORTANT
DHW Recirculation
16
Domestic Hot Water Recirculation
DHW recirculation lines increase the level of comfort and convenience of the domestic hot water supply and reduce water consumption.
These advantages directly derive from the immediate availability of domestic hot water at all draw points.
Poor insulation of the DHW recirculation line, however, can result in considerable heat loss. Viessmann therefore recommends that
effective insulation be provided and used for DHW recirculation lines of 23 ft. / 7 m in length or longer.
Legend
DCW Domestic Cold Water
DHW Domestic Hot Water
TPV Temperature and Pressure Relief
Valve (on tank - not shown)
R DHW Recirculation Line
RP DHW Recirculation Pump
5
3
6
9
2
9
5
v
1
.
5
Vitocell-V stand-alone DHW storage tank
DCW
DCW
DHW
R
RP
Fig. 16
Wall Mounting
17
Models WB2B 19, 26, 35
The Vitodens 200-W, models WB2B 19 to 35 comes with a template, which allows you to easily mark the location of the screws for the
mounting bracket and the location of the flue gas pipe on the wall.
1. Loosen the screws at the bottom of the
boiler.
2. Remove front enclosure panel.
3. Mount boiler onto the mounting bracket
and connect boiler to the installation
fittings.
5
3
6
9
2
9
5
v
1
.
5
A
C
B
Fig. 17
AReference point top edge Vitodens 200-W
BMounting bracket
CVitodens 200-W mounting template
Legend
3.
2.
2x
1.
Fig. 18
Wall Mounting
18
Models WB2B 45, 60, 80, 105
The Vitodens 200-W, models WB2B 45 to105 comes with a template, which allows you to easily mark the location of the screws for the
mounting bracket and the location of the flue gas pipe on the wall.
1. Loosen the screws at the bottom of the
boiler.
2. Remove front enclosure panel.
3. Mount boiler onto the mounting bracket
and connect boiler to the installation
fittings.
5
3
6
9
2
9
5
v
1
.
5
A
C
B
AReference point top edge Vitodens 200-W
BMounting bracket
CVitodens 200-W mounting template
Fig. 19
Legend
2x
1.
3.
2.
Fig. 20
Condensate Connection/Neutralization Unit
19
Condensate Connection
Install the condensate drain pipe with a suitable gradient.
Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (accessory).
Pipe ventilation must take place between
the siphon trap and the neutralization unit (if
applicable).
Condensate Connection for
Vitodens 200-W, models WB2B 19, 26, 35
Condensate Connection for
Vitodens 200-W, models WB2B 45, 60
Condensate Connection for
Vitodens 200-W, models WB2B 80, 105
Condensate Drainage and Neutralization
The condensate formed both in the
condensing boiler and in the flue gas pipe
must be discharged into the public sewage
system in accordance with all applicable
local regulations. The condensate produced
by a gas-fired heating system has a pH
value between 3 and 4.
Some local codes may require the use of a
separate neutralization unit to treat the
aggressive and corrosive nature of the
condensate. With a neutralization unit
installed, all condensate from the boiler and
the flue gas pipe enters into the
neutralization unit where it is treated and
released into the public sewage system with
a safe pH value of above 6.5.
The use of neutralization granulate
(performing the neutralizing process) is
dependent on the operation of the heating
system. To determine the required refill
amount, check granulate level several times
during the first year of operation. In some
cases one granulate fill may last an entire
year.
Contact Viessmann to order a neutralization
unit for the Vitodens 200-W boiler.
See Viessmann Price List for order
information.
The condensate discharge outlet to the
drainage system connection must be clearly
visible. It must be installed with a suitable
gradient and provided with a stench trap.
If the condensate outlet of the Vitodens
200-W boiler is lower than the drain, a
condensate pump must be used.
Only corrosion-resistant materials must be
used for condensate drainage purposes (e.g.
braided hose). Do not use galvanized
materials or materials containing copper for
piping, couplings etc.
The condensate drain must have a trap to
prevent flue gas leakage.
Please note that other requirements might
apply depending on local regulations and/or
project-specific details.
It is advisable to contact your local
waterworks office (authority responsible for
waste water regulations) well before
commencing with the installation of the
neutralization unit in order to establish
details of local regulations that apply.
The following table shows the concentration
of (effluent) substances (e.g. heavy metals)
contained in the waste water from the
Vitodens 200-W condensing boiler.
Table 12.
Condensate
(effluent)
s
u
b
s
t
a
n
c
e
s
Values measured
in mg/L
(
e
f
f
l
u
e
n
t
)
substances Vitodens 200-W
Lead
Cadmium
Chromium
Copper
Nickel
Zinc
Tin
< 0.01
< 0.005
< 0.01
< 0.01
< 0.01
< 0.05
< 0.05
5
3
6
9
2
9
5
v
1
.
5
IMPORTANT
Fig. 21
Fig. 22
Fig. 23
Venting Options / Electrical Connection / Boiler Control
Fig. 26
4
+
?
OK
0
1
2
3
0
+
RESET
s
?F
A
140
M o
Boiler temp.
20
Venting Options
For an overview of venting options refer to the appendix starting on page NO TAG. For detailed information refer to the Installation
Instructions for the Vitodens 200-W, WB2B Venting System.
Electrical Connection
For an overview of the required wiring refer to pages 39 (for WB2B 19 to 60) and 40 (for WB2B 80 and 105).
Power Supply
The Vitodens 200-W is shipped with a
Power / Pump Module. The module requires
a 120 VAC power supply from a wall
receptacle. The module contains a 120/230
VAC step-up transformer to power the
Vitodens 200-W with 230 VAC. Refer to
the Installation Instructions shipped with the
module for wiring details, or reference the
“Overview of Electrical Connections” on
pages 39 and 40 of this manual.
Power Supply Connection of Accessories
The power supply connection of accessories
can be made directly at the boiler control.
The connection is activated and deactivated
with the system on/off switch.
The mixing valve accessory kit and the
Vitosolic control (if used) will require a
separate 120 VAC power supply from the
wall receptacle.
Wire cabling required for:
Houtdoor temperature sensor
HVitotronic 200-H, HK1M mixing valve
control
Haccessory kit for heating circuit with
mixing valve
HVitotrol 200 remote control
HVitotrol 300 remote control
Hremote switching of operating mode
Hremote disable
Halarm output
On-Board Vitotronic 200, HO1 Outdoor Reset Control
The on-board Vitodens menu-driven Vitotronic 200, HO1 control provides the following:
5
3
6
9
2
9
5
v
1
.
5
Vent Connection, models WB2B 19, 26, 35
(with optional air intake openings on sides)
Vent Connection, models WB2B 45, 60, 80,105
Fig. 24 Fig. 25
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Viessmann Vitodens 200-W System Datasheet

Category
Space heaters
Type
Datasheet
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI