FandF LE-03MQ is a static, calibrated single-phase or three-phase AC electricity meter designed for precise measurement and registration of electrical energy consumption. It features two-way measurement (4-quadrant), a backlit multifunctional LCD, and password-protected configuration. With its RS-485 port and Modbus RTU protocol, it enables remote reading and communication for advanced energy management systems. The meter complies with MID standards and offers indications of kWh/kvar (imported/exported) and various network parameters.

FandF LE-03MQ is a static, calibrated single-phase or three-phase AC electricity meter designed for precise measurement and registration of electrical energy consumption. It features two-way measurement (4-quadrant), a backlit multifunctional LCD, and password-protected configuration. With its RS-485 port and Modbus RTU protocol, it enables remote reading and communication for advanced energy management systems. The meter complies with MID standards and offers indications of kWh/kvar (imported/exported) and various network parameters.

ELECTRICITY CONSUMPTION METER
3-phase LE-03MQ CT
- 1 - - 2 - - 3 - - 4 -
Number of the meter
The meter is marked with an individual serial number, which
makes it possible to identify it unambiguously.
The marking is indelible (laser engraving).
Sealing
The meter has the option of sealing the input and output termi-
nals, preventing the meter from being bypassed.
Compliance
Directive: 2014/32/EU
Certificate number: 0120/SGS 0216
The LE-03MQ CT is a static (electronic) calibrated single-phase or
three-phase alternating current electricity meter in a semi-indirect
system. It is used for indication and registration of electric energy
consumption and parameters of the power supply network with
the option for remote reading through a wired RS-485 network.
The meter works with current transformers (CT) with a secondary
current of 1 A or 5 A.
The meter is configured via the configuration menu accessible
from the front panel and via the communication port according to
Modbus RTU software functions.
Purpose
User manual and programming instructions
Detailed PDF manual available for download from the following
website: www.le.fif.com.pl
Features
Active energy imported/exported AE+/AE- [kWh]
Reactive energy imported/exported RE+/RE- [kvarh]
Phase voltage U1, U2, U3 [V]
Phase currents I1, I2, I3 [A]
Frequency F [Hz]
Active power P [W]
Reactive power Q [var]
Apparent power S [VA]
Power factor cosϕ
Total Harmonic Distortion THD %
Power and current demand kW, kvar, kVA, I
* 1-phase or 3-phase system (3- and 4-wire)
* two-way measurement (4-quadrant)
* 1 A or 5 A transformers
* current ratio 1÷9999
* indications of kWh/kvar (imported/exported)
* indications of network parameters
* MID compliance
* RS-485 port
* Modbus RTU protocol
* SO (×2) pulse output
* backlit, multifunctional LCD
* password-protected meter configuration
Measured values
5 908312 599821
Connection diagram
1-phase 2-wire installation
covers
of the terminals
place of
sealing the cover
1÷4 voltage inputs 13, 14 RS-485 (B, A)
5, 6 power supply (POW) 15÷20 current inputs
9÷12 pulse outputs
F&F Filipowski sp. j.
Konstantynowska 79/81 95-200 Pabianice
phone/fax: (+48 42) 215 23 83 / 227 09 71 POLAND
http://www.fif.com.pl e-mail: [email protected]
WARRANTY. The F&F products are
covered by a warranty of the 24 months
from the date of purchase. Effective only
with proof of purchase.
Do not dispose of this device in the trash along with other waste! According
to the Law on Waste, electro coming from households free of charge and can
give any amount to up to that end point of collection, as well as to store the
occasion of the purchase of new equipment (in accordance with the principle
of old-for-new, regardless of brand). Electro thrown in the trash or abandoned
in nature, pose a threat to the environment and human health.
L
N
POW
3200imp/kWh 3K6 50Hz 2017
3×230/400V 0.25-5(6)A SW:V1.3
LE-03MQ-CT
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 56 7 8
0120/SGS0216
0120
M17
B
B A
P2
S2
P1
S1
RS-485
12
D211102
- 5 - - 7 - - 8 -
Configuration software
A program for PCs (with Windows) that allows you to check the
status of the meter and configure all of its settings is available
for download on the fif.com.pl website (on the LE-03MQ CT
meter subpage).
CE and MID declarations
Copy of the CE and MID declarations available for download
from the website: from the product subpage.
Technical data
reference voltage 3×230/400 V
base current 0.25÷5 A
maximum current 6 A
minimum measured current 0.02 A
measured voltage
L-N 100÷289 V AC
L-L 173÷500 V AC
accuracy of measurement class 1
overload capacity 30×Imax/10 ms
insulation 4 kV/1 min; 6 kV/1 µs
own energy consumption of the meter 10 VA; 2 W
power of current inputs <1 VA
power supply voltage of the meter
85÷275 V AC /120÷380 V DC
counter display range 0÷9999999.9 kWh
meter constant kWh 3200 imp/kWh
meter constant kvarh/kWh 0,01, 0,1, 10, 100 imp/kvar
reading signalling 1×LED
pulse outputs kWh/kvarh
OC (open collector) 27 V DC/50 mA
pulse time kWh/kvarh 60, 100, 200 ms
port RS-485
communication protocol Modbus RTU
working temperature -25÷55°C
terminal 4.0 mm² screw terminals
tightening torque 0.5 Nm
dimensions 4 modules (72 mm)
mounting on TH-35 rail
ingreess protection IP51
3-phase 4-wire installation3-phase 3-wire installation
1÷4 voltage inputs 13, 14 RS-485 (B, A)
5, 6 power supply (POW) 15÷20 current inputs
9÷12 pulse outputs
1÷4 voltage inputs 13, 14 RS-485 (B, A)
5, 6 power supply (POW) 15÷20 current inputs
9÷12 pulse outputs
L1
L2
L3
N
POW
3200imp/kWh 3K6 50Hz 2017
3×230/400V 0.25-5(6)A SW:V1.3
LE-03MQ-CT
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8
0120/SGS0216
0120
M17
B
B A
P2
S2
P1
S1
P2
S2
P1
S1
P2
S2
P1
S1
12RS-485
L1
L2
L3
POW
3200imp/kWh 3K6 50Hz 2017
3×230/400V 0.25-5(6)A SW:V1.3
LE-03MQ-CT
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 56 7 8
0120/SGS0216
0120
M17
B
B A
P2
S2
P1
S1
P2
S2
P1
S1
RS-485
12
  • Page 1 1
  • Page 2 2

FandF LE-03MQ User manual

Category
Measuring, testing & control
Type
User manual

FandF LE-03MQ is a static, calibrated single-phase or three-phase AC electricity meter designed for precise measurement and registration of electrical energy consumption. It features two-way measurement (4-quadrant), a backlit multifunctional LCD, and password-protected configuration. With its RS-485 port and Modbus RTU protocol, it enables remote reading and communication for advanced energy management systems. The meter complies with MID standards and offers indications of kWh/kvar (imported/exported) and various network parameters.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI