Danfoss AFT 06/26/17/27 Operating instructions

Type
Operating instructions

Danfoss AFT 06/26/17/27 actuators are designed for temperature control of water, water-glycol mixtures, and steam for heating, district heating, and cooling systems. They offer precise temperature control, easy installation, and reliable operation. With a wide range of compatible valves, these actuators provide flexible solutions for various applications.

Danfoss AFT 06/26/17/27 actuators are designed for temperature control of water, water-glycol mixtures, and steam for heating, district heating, and cooling systems. They offer precise temperature control, easy installation, and reliable operation. With a wide range of compatible valves, these actuators provide flexible solutions for various applications.

1












12
11
10
9
8
7
6
5
=10C
Installation Guide
AFT 06/26/17/27
District Energy VI.GA.N3.81 DHS-SMT/SI
ENGLISH
Actuator for Temperature Control
AFT 06, 26, 17, 27
www.danfoss.com Page 4
DEUTSCH
Antrieb für Temperaturregelung
AFT 06, 26, 17, 27
www.danfoss.com
Seite 5
FRANCAIS
Tête thermostatique pour régulation de température
AFT 06, 26, 17, 27
www.danfoss.com Page 6
POLSKI
Napкd do regulacji temperatury
AFT 06, 26, 17, 27
www.danfoss.com
Strona 7
РУССКИЙ
Привод для регуляторов температуры
AFT 06, 26, 17, 27
www.danfoss.com
Страница 8
HRVATSKI
Pogon za regulaciju temperature
AFT 06, 26, 17, 27
www.danfoss.com
Stranica 9
AFT 06 AFT 26 AFT 17 AFT 27 VFG 2(1), VFGS2 VFU 2 VFG 33
2








Type
VFG 21, 33
VFU 2
VFG 2 VFGS 2
-
ZF 6
-
ZF 6
-
ZF 4
T
max medium
(°C) 150 150 200 200 200 300
Max. operating pressure
1)
(bar) 14 PN 14 PN 14 PN
PN
16, 25, 40 16, 25, 40 16, 25, 40
VFG 33
B
ABA
Installation Guide AFT 06/26/17/27
DHS-SMT/SI VI.GA.N3.81 District Energy
46 mm








VFG .., VFU 2
< 120 °C












VFG .., VFU 2, VFGS 2
> 120°C
33
Installation Guide AFT 06/26/17/27
District Energy VI.GA.N3.81 DHS-SMT/SI
401




AFT 06 AFT 26
AFT 17
AFT 27
VFG 33
VFU 2
VFG 2
VFG 21
VFGS 2
5 x 10 = 50 °C
4
Safety Notes
Prior to assembly and commissioning to
avoid injury of persons and damages of
the devices, it is absolutely necessary to
carefully read and observe these instructions.
Necessary assembly, start-up, and maintenance
work must be performed only by qualied,
trained and authorized personnel.
Prior to assembly and maintenance work on the
controller, the system must be:
- depressurized,
- cooled down,
- emptied and
- cleaned.
Please comply with the instructions of the
system manufacturer or system operator.
Disposal instruction
This product should be
dismantled and its components
sorted, if possible, in various
groups before recycling or
disposal.
Always follow the local disposal regulations.
Denition of Application
The actuator AFT.. is used in combination with
Danfoss valves for temperature control of water,
water-glycol mixtures, and steam for heating,
district heating, and cooling systems.
The technical data on the rating plates
determine the use.
Permissible Pressures and
Temperatures
Mounting
Permissible Installation Positions
For valves VFG 2., VFG 3., VFU 2
DN 15-80
medium temperatures up to 120°C
For valves VFG 2., VFG 3., VFU 2
DN 100-125 and for DN 15-80,
medium temperatu res > 120°C
and
Valves VFGS 2
Installation Scheme
Valves VFG 2(1), VFGS 2, VFU
Can be installed in both ow or the return pipe.
Mixing valve VFG 33
Mixing valve in the supply ow - heating
Mixing valve in the supply ow - cooling
Valve Installation
1. Install strainer in front of valve.
2. Rinse system before installing valve.
3. Observe ow direction on the valve body.
Flanges in the pipeline system must
be in parallel direction, the sealing
surfaces must be clean and undamaged.
4. Install valve.
5. Tighten screws crosswise in 3 steps up to the
maximum torque.
Actuator and Valve Mounting
1. Place actuator at the valve and align.
2. Tighten union nut , torque 100 Nm
Temperature Sensor Installation
- The temperature sensor may be installed in
any position
- The capillary tube may not be twisted or
buckled. The minimum bending radius is
50 mm.
- The temperature of the medium has to be
taken directly without any delay.
- Care for sucient cross section of ow .
Filling the system and
First Start-up
When lling the system, the temperature
control valve must be open. Alternatively, the
lling can be carried out from all sides.
To ensure that the temperature control valve is
open, the following must be observed:
The stem of the actuator:
is extended
if the temperature at the sensor is higher
than the setpoint .
is retracted
if the temperature at the sensor is lower than
the setpoint .
In order to open the temperature control valve,
the setpoint at the setpoint adjuster is to be
increased or reduced, depending on the valve
designs - .
The pressure behind the valve may exceed
the pressure in front of the valve only
insignicantly.
Non-compliance may cause damages at the
valve.
Pressure test
Carry out pressure tests only with the
actuator mounted.
Without actuator, the valve is open , the seal
is in the actuator.
It is absolutely necessary to constantly
increase pressure from all sides.
Non-compliance may cause damages at the
controller.
Observe nominal pressure of the valve.
Max. test pressure is 1,5 × PN
Setpoint Adjustment
The setpoint range is indicated on the rating
plate.
The system must be in operation.
Adjustment
1. Observe temperature indicator .
2. Adjust setpoint by turning the setpoint
adjuster .
increases the setpoint
reduces the setpoint
If the temperature at the sensor is noticeably
higher than the setpoint temperature, then:
- return setpoint adjuster only in increments of
max. 10 °C and
- wait until the temperature at the sensor
dropped.
After having adjusted the setpoint, wait until
the temperature indication shows its nal
value.
Dismounting of Valve
and Actuator
Danger
Danger of injury by steam or hot water!
Valve without actuator is open , sealing is
in the actuator.
It is absolutely necessary to depressurize system
prior to dismounting.
Dimensions
Installation Guide AFT 06/26/17/27
DHS-SMT/SI VI.GA.N3.81 District Energy
LANGUAGEENGLISH
10
Installation Guide AFT 06/26/17/27
DHS-SMT/SI VI.GA.N3.81 District Energy
LANGUAGE
1111
Installation Guide AFT 06/26/17/27
District Energy VI.GA.N3.81 DHS-SMT/SI
LANGUAGE
Installation Guide AFT 06/26/17/27
73696090/VI.GA.N3.81
Produced by Danfoss A/S © 10/2015
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Danfoss AFT 06/26/17/27 Operating instructions

Type
Operating instructions

Danfoss AFT 06/26/17/27 actuators are designed for temperature control of water, water-glycol mixtures, and steam for heating, district heating, and cooling systems. They offer precise temperature control, easy installation, and reliable operation. With a wide range of compatible valves, these actuators provide flexible solutions for various applications.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI