MGE GALAXY 5000

APC MGE GALAXY 5000, MGE Galaxy 5000 40 kVA Specification

  • Hello! I am an AI chatbot trained to assist you with the APC MGE GALAXY 5000 Specification. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MGEGalaxy5000
40–130kVA480V
Installation
TableofContents
IMPORTANTSAFETYINSTRUCTIONS-SAVETHESE
INSTRUCTIONS...............................................................................................................1
SymbolsUsed...................................................................................................................1
Specications...................................................................................................................2
ACInput...........................................................................................................................2
ACOutput.........................................................................................................................2
Batteries............................................................................................................................2
ACBypass........................................................................................................................2
RecommendedFuses........................................................................................................3
ConnectInputandGroundCablesinSingleSystems..............................4
SingleUtility/MainsSystems....................................................................................4
DualUtility/MainsSystems........................................................................................4
ConnectACInputandPowerCablesinParallelSystems......................5
SingleUtility/Mains......................................................................................................5
DualUtility/MainsSystems........................................................................................6
ConnectCommunicationCables...........................................................................7
OverviewofCommunicationCablesinSingleSystems..................................................7
OverviewofCommunicationCablesinParallelSystems................................................8
ConnectRelayCommunicationCard.....................................................................9
CommunicationCardConnectionExample...............................................................10
ConnectGeneralShutdownorRemoteEmergencyPowerOff......................10
ConnectParallelCommunicationCablesinRedundantParallel
Systems..........................................................................................................................11
ConnectParallelCommunicationCablesinCapacityParallel
Systems..........................................................................................................................12
InstallanExternalBatteryCabinet.......................................................................15
InstallATIZPCAandGNDBusbar...........................................................................15
TheBatteryCircuitBreaker.......................................................................................16
ConnectPowerandControlCables........................................................................17
MounttheBatteryCells..............................................................................................19
InstallPanelsandLabelson26”BatteryCabinet(StandAloneOnly)...........20
InstallPanels,LabelsandPalleton26”BatteryCabinet..................................21
990–5217
MGEGalaxy500040–130kV A480V
i
InstallPanelsandLabelson48”BatteryCabinet(StandAloneOnly)...........21
InstallPanelsandLabelson48”BatteryCabinet...............................................22
ii
MGEGalaxy500040–130kV A480V
990–5217
IMPORTANTSAFETYINSTRUCTIONS-
SAVETHESEINSTRUCTIONS
SymbolsUsed
WARNING:Indicatesanelectricalhazard,which,ifnotavoided,couldresultininjury
ordeath.
Caution:Indicatesahazard,which,ifnotavoided,couldresultininjuryordeath.
Note:Indicatesimportantinformation.
See:Indicatesthatmoreinformationisavailableonthesubject.
990–5217
MGEGalaxy500040–130kV A480V
1
Specications
ACInput
ACinput40kV A50kV A60kV A80kV A100kV A130kV A
Nominalinputvoltage(V)
480480480480480480
Inputfrequency(Hz)
60Hz60Hz60Hz60Hz60Hz60Hz
Nominalinputcurrent(A)
1
48597194117151
Maxinputcurrent(A)
2
597088111150182
Inputcurrentlimit(A)
3
57
7085111148182
InputphaserotationA,B,Cclockwise
Inputpowerfactor
>0.98
1
Inputcurrentbasedonratedloadandbatteriesfullycharged.
2
Inputcurrentbasedonfullybatteryrecharge,nominalvoltageandratedload.
3
Currentlimitationthroughelectroniccurrentlimitingisbasedonfullbatteryrechargeand-10%
inputvoltage.
ACOutput
40kV A50kV A60kV A80kV A100kV A130kV A
Nominalinputvoltage(V)
480480480480480480
Nominaloutputcurrent(A)
48597194117151
Batteries
Batteryinput40kV A50kV A60kV A80kV A100kV A130kV A
Nominalvoltage(VDC)
432
Endvoltage(VDC)
356
Max.oatingvoltage
(VDC)
490
I
Nom
discharge
1
(A)
90113135180225293
I
Max
discharge
2
(A)
109137164219273355
1
Nominalbatterydischargecurrentbasedonratedloadandnominalbatteryvoltage.
2
Maximumbatterydischargecurrentbasedonratedloadattheendofthedischarge.
ACBypass
40kV A50kV A60kV A80kV A100kV A130kV A
Inputfrequency(Hz)
606060606060
Nominalinputcurrent(A)
48597194117151
2
MGEGalaxy500040–130kV A480V
990–5217
RecommendedFuses
40kV A50kV A60kV A80kV A100kV A130kV A
Inputandoutputfuserating
(A)
160160160160315315
990–5217
MGEGalaxy500040–130kV A480V
3
ConnectInputandGroundCablesin
SingleSystems
SingleUtility/MainsSystems
1.Removetheprotectioncoverinthebottomof
theenclosure.
2.ConnecttheACinputcablestotheACinput
terminalsandtotheUPSgroundingplate.
3.ConnecttheACoutputcablestotheACoutput
terminalsandtotheUPSgroundingplate.
4.Connectthebatterycablestothebattery
terminals.
5.Securethecablestothecabinet.
6.Reinstallthecoverprotectionforpower
terminals.
DualUtility/MainsSystems
1.Removetheprotectioncoverinthebottomof
theenclosure.
2.ConnecttheACinputcablestotheACinput
terminalsandtotheUPSgroundingplate.
3.ConnecttheACbypasscablestotheACbypass
terminalsandtotheUPSgroundingplate.
4.ConnecttheACoutputcablestotheACoutput
terminalsandtotheUPSgroundingplate.
5.Connectthebatterycablestothebattery
terminals.
6.Securethecablestothecabinet.
7.Reinstallthecoverprotectionforpower
terminals.
4
MGEGalaxy500040–130kV A480V
990–5217
ConnectACInputandPowerCablesin
ParallelSystems
SingleUtility/Mains
Note:AmaximumoftwoUPSunitscanbeinstalledforPn.
1.Removetheprotectioncoverinthebottomoftheenclosure.
2.ConnecttheACinputcablestotheACinputterminalsandtotheUPSgroundingplateforboth
UPSunitsinbothUPSunits.
3.ConnecttheACoutputcablestotheACoutputterminalsandtotheUPSgroundingplateinUPS1.
4.ConnectthethreeloadconnectorsfromACoutputterminalsinUPS1toACoutputterminals
inUPS2.
5.Connectthebatterycablestothebatteryterminals.
6.Securethecablestothecabinet.
7.Reinstallthecoverprotectionforpowerterminals.
990–5217
MGEGalaxy500040–130kV A480V
5
DualUtility/MainsSystems
Caution:IfthetwoUPSunitsareplacedsidebyside,connectasindicatedbelow.Inother
congurations,alwaysmakesurethatthecablesbetweentheUPSunitsandthebypass
sourcehavethesamecross-sectionandthesamelength.Thesameistrueforthecables
betweentheUPSunitsandtheload.
Note:ThedrawingsbelowshowcongurationswithoutanexternalSystemBypassCabinet.
1.Removetheprotectioncoverinthebottomoftheenclosure.
2.ConnecttheACinputcablestotheACinputterminalsandtotheUPSgroundingplateinboth
UPSunits.
3.ConnecttheACbypasscablestotheACbypassterminalsandtotheUPSgroundingplatein
bothUPSunits.
4.ConnecttheACoutputcablestotheACoutputterminalsandtotheUPSgroundingplateinUPS1.
5.ConnectthethreeloadconnectorsfromACoutputterminalsinUPS1toACoutputterminals
inUPS2.
6.Connectthebatterycablestothebatteryterminals.
7.Securethecablestothecabinet.
8.Reinstallthecoverprotectionforpowerterminals.
6
MGEGalaxy500040–130kV A480V
990–5217
ConnectCommunicationCables
OverviewofCommunicationCablesinSingleSystems
Caution:Toensuresufcientisolationofcontrolandcommunicationcables,theymust
berunseparatelyfromthepowercables.Reinforcetheinsulationofthesecontroland
communicationcablesifanyriskofcontactwiththepowercablesexists.
A.Relaycommunicationcard(SELV)
B.Optionalcommunicationcards(SELVor
LV)
C.Externalbatterycircuitbreakercables
(SELV)
D.Generalshutdowncable(SELV)
990–5217
MGEGalaxy500040–130kV A480V
7
OverviewofCommunicationCablesinParallel
Systems
Caution:Toensuresufcientisolationofcontrolandcommunicationcables,theymust
berunseparatelyfromthepowercables.Reinforcetheinsulationofthesecontroland
communicationcablesifanyriskofcontactwiththepowercablesexists.
A.Relaycommunicationcard(SELV)
B.Optionalcommunicationcards(SELVor
LV)
C.Externalbatterycircuitbreakercables
(SELV)
D.Generalshutdowncable(SELV)
E.PCAINTNforconnectionofexternalbypass
cabinetcable(ELV),CANcables(SELV),
andexchange-currentcables(SELV).
8
MGEGalaxy500040–130kV A480V
990–5217
ConnectRelayCommunicationCard
Caution:Isolateandlock-outallpowersourcesforthiscardbeforemakingconnections.
NeverconnectSELV(safetyextralowvoltage)andnon-SELVcircuitstothedifferent
outputsofthesamecard.
Characteristicsofoutputcontacts:
Permissiblevoltage:250VAC,30VDC
Permissiblecurrent:2A
Cable:4x0.93mm²,Ø6.6+/-0.3mm
Characteristicsofinputcontacts:
Switchedvoltage:5VDC
Consumption:10mA
Cable:4x0.34mm²,Ø5+/-0.5mm
1.Removethecoversecuredbythescrews.
2.Runthecommunicationcablesthroughthe
cableentryholes.
3.Connectconductorstotheinputterminals.
A.UPSON
B.UPSOFF
990–5217
MGEGalaxy500040–130kV A480V
9
4.Connectconductorstotheoutputterminals.
A.Generalalarm
B.Batteryfault
C.LoadonUPS
D.Loadonautomaticbypass
E.Loadonbatterypower
F.Lowbatterywarning
5.Putthecoverbackinplaceandsecureitwith
thescrews.
6.Tightenthescrewstolockthecables.
7.Indicatethelocationsofthepowersourceson
thelabels.
8.Insertthecardsinitsslot.
9.Securethecardwithtwoscrews.
CommunicationCardConnectionExample
IfaSELVsourceisused,itmustalwaysbepossibletoisolatethecommunicationcardfromtheupstream
sourcetoensurethesafetyofpersonnelworkingontheinstallation.
ConnectGeneralShutdownorRemoteEmergency
PowerOff
PressingthegeneralshutdownbuttoncausesUPSshutdownandopeningofthebatterycircuitbreaker
(withopeningofthebypassstaticswitchdependingonpersonalizationsettings).TheRemoteEmergency
PowerOff(REPO)notionisapplicabletoinstallationswherepressingthebuttonalsocausestheupstream
NormalACsourceandACbypasssourcecircuitbreakerstoopen.Inparallelsystems,theremustbea
singlegeneralshutdownbuttonwithaseparatecontactforeachUPSunit.
10
MGEGalaxy500040–130kV A480V
990–5217
1.Removethewirejumperfromtheterminal
block.
2.ConnectthegeneralshutdownNCcontactto
terminals1and2(SELV).
3.Securethecable.
ConnectParallelCommunicationCablesinRedundant
ParallelSystems
Note:Thesuppliedcables(33ft)limitthedistancebetweentwoUPSunitstoapproximately
20ft.
1.ConnectacommunicationcablefromXMS02inUPS1toXMS02inUPS2.
2.ConnectacommunicationcablefromXMS03inUPS1toXMS03inUPS2.
3.InstallabluepluginconnectorXMS06inUPS1.
4.ConnectacommunicationcablefromXMS07inUPS1toXMS06inUPS2.
5.InstallaredpluginconnectorXMS07inUPS2.
6.Fittheprotectioncoversuppliedwiththeparallelsystemovertheauxiliaryinterconnectioncables.
990–5217
MGEGalaxy500040–130kV A480V
11
ConnectParallelCommunicationCablesinCapacity
ParallelSystems
Note:Thesuppliedcables(33ft)limitthedistancebetweenthetwoUPSunitsto
approximately20ft.
1.UsetheXMS02andXMS03terminalstocreatealoopbetweenallUPSunitsasshownonthe
illustration(alltheXMS02andXMS03terminalsmustbeused).
12
MGEGalaxy500040–130kV A480V
990–5217
2.Daisy-chaintheUPSunitsusingtheXMS06andXMS07terminals.Fitablueconnectoron
therstUPSunitsandaredplugonthelastUPSunit(alltheXMS06andXMS07connectors
mustbeused).
3.Connectterminals7,8,9,and10ontheauxiliaryterminalblockTB2inthesystembypass
cabinettoUPSterminalblocksXMS04/XMS05pins1,2,3,and4respectivelyandcreatealoop
connectionbetweenthesystembypasscabinetandtheUPSasshown.
4.Fittheprotectioncoversuppliedwiththeparallelsystemovertheauxiliaryinterconnectioncables.
990–5217
MGEGalaxy500040–130kV A480V
13
14
MGEGalaxy500040–130kV A480V
990–5217
InstallanExternalBatteryCabinet
InstallATIZPCAandGNDBusbar
26”and32”BatteryCabinet48”BatteryCabinet
1.IftheA TIZPCAoptionhasbeenpurchased,installtheA TIZPCAintherstbatterycabinet.
2.InstalltheGround(GND)busbar.
990–5217
MGEGalaxy500040–130kV A480V
15
TheBatteryCircuitBreaker
Note:Onlyonecircuitbreakerisnecessaryevenifseveralbatterycabinetsareconnected.
1.Thebatterycircuitbreakerispre-installedinthebatterycabinetfromfactory.
2.Securethebaseplatetothebatterycabinettosupportthecircuitbreaker.
3.SecuretheXR1connectorboxtothebatterycabinetframe.
4.Securethetemperaturesensortothebatterycabinetframe.
5.Whenthebatterieshavebeenconnectedtothecircuitbreaker,installthefrontplateinfront
ofthecircuitbreaker.
BatteryCircuitBreakerControlWiring
TB5
QF1WireColor
1
Brown
2
Brown
3
Yellow
4
Blue/Yellow
5
Jumper2to4
16
MGEGalaxy500040–130kV A480V
990–5217
/