D+H RZN 43xx-E Operating instructions

Category
Fire protection
Type
Operating instructions

D+H RZN 43xx-E is a modular smoke vent control panel designed for complex control requirements. Below you will find brief product information for D+H RZN 43xx-E:

  • It can be used to control lines and groups in any combination.
  • The control panel has comfort functions for daily ventilation.
  • It is suitable only for inside mounting.

D+H RZN 43xx-E is a modular smoke vent control panel designed for complex control requirements. Below you will find brief product information for D+H RZN 43xx-E:

  • It can be used to control lines and groups in any combination.
  • The control panel has comfort functions for daily ventilation.
  • It is suitable only for inside mounting.
en Original instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . Page . . . . . . . 2
99.826.07 4.1/08/18
approval no.
G 500002 0786 - CPD - 50664
EN 12101-10 : 2005/AC:2007
conform
Smoke Vent Control Panel RZN 43xx-E
Installation
Gebrauchsanleitung
Housing
transformer
rail
cable ducts
motherboard with rectifier card
and power supply plug-in unit
keys
instruction for use and
SHEV operational book
Fig. RZN 43xx-E6
Content
Assembly scheme
GE
F8,0A
min
15
2
45 30
sec
20
2
60 40
Air Indicat o r
12345678910
Bft.
LE
Weather plug-in unit
Group plug-in unit for ventilationGroup plug-in unit
Line plug-in unit
Servo plug-in unit
Line Group
BMS
External control
Window drive
SHEV button
Ventilation button
Fire detector Wind / rain transmitter
Room temp. control
Air-Indicator
panel
GE
F8,0A
min
15
2
45 30
sec
20
2
60 40
OK
Intended use
- SHEV control panel in modular plug-in card design for complex
control requirements
- Lines / groups in any combination
- Comfort functions for daily ventilation
- Only for inside mounting
Operating voltage 230 V AC!
Risk of injury from electric shock!
- Connection has to be carried out only by an authorized electrical
specialist
- Only for inside mounting
- Just use unchanged original D+H parts
Safety notes
Inspection and maintenance has to be carried out according to D+H
maintenance notes. Only original D+H spare parts may be used. Repair
is to be carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft cloth.
Do not use cleaning agents or solvents.
Repair and cleaning
We declare under our sole responsibility that the product described under
“Technical Data” is in conformity with the following directives:
2014/30/EU, 2014/35/EU, EU 305/2011
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder Maik Schmees
Member of the Board Authorized signatory,
Technical Director
20.03.2018
Declaration of Conformity
Observe regulations for danger warning systems VDE 0833, guidelines for
electrical systems VdS 2221, VDE 0100, DIN 18232 for smoke and heat
vent systems, regulations of the local fire-brigade and of EVU for
connection to mains supply.
Important Regulations
Smoke gases are to be carried off as unhindered as possible through
smoke and heat vent opening in case of fire. Size, kind and
arrangement of the opening is of decisive significance for an optimal
effect of the smoke and heat vent system.
These requirements are defined in the relevant regulations of the
respective country.
More informations, are also available under www.rwa-heute.de.
The SHEV opening should be coordinated with the responsible fire
protection authority.
SHEV opening
RZN 43xx-E RZN 43xx-E 3/202/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
English English
Electrical devices, accessories, batteries and packaging should be sorted
for environmental-friendly recycling.
Do not dispose electrical devices and batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for waste electrical and
electronic equipment and its implementation into national right, electrcal
devices that are no longer usable must be collected separately and dispo-
sed of in an environmentally correct manner.
Disposal
Overview
The components that are part of the VdS Approval are signed with an
VdS logo.
VdS Approval
Introduction / Assembly scheme ....................................................................................................................................................................................2
Intended use / Safety notes ...........................................................................................................................................................................................3
SHEV opening................................................................................................................................................................................................................3
Important Regulations / Repair and cleaning .................................................................................................................................................................3
Declaration of Conformity / Disposal..............................................................................................................................................................................3
Technical Data................................................................................................................................................................................................................4
Emergency Supply .........................................................................................................................................................................................................4
Pictograph Explanation ..................................................................................................................................................................................................4
Optional Functional Extensions......................................................................................................................................................................................4
Internal structure of standard control panels..................................................................................................................................................................5
Main board GP 509 / General plug-ins...........................................................................................................................................................................6
Supply plug-in card VE 520 / VE 530.............................................................................................................................................................................7
Servicetimer ...................................................................................................................................................................................................................7
Line plug-in card LE 513 ................................................................................................................................................................................................7
Group plug-in card GE 628 (-L) V2 ................................................................................................................................................................................8
Servo plug-in card SE 622 .............................................................................................................................................................................................9
Weather plug-in card WE 516 ......................................................................................................................................................................................10
Window-lock plug-in card AE 525-A / AE 526-DG........................................................................................................................................................10
Cables for D+H SHEV systems / Wiring plan / 230 V supply.......................................................................................................................................11
Connection assignment................................................................................................................................................................................................12
Connection – overview.................................................................................................................................................................................................13
Connection – Parallel connection of RT 45 on LE 513 ................................................................................................................................................13
Connection – Fire dectector or fire alarm system to LE 513 ........................................................................................................................................14
Connection – GE 628 V2 .............................................................................................................................................................................................14
Connection – SE 622 ...................................................................................................................................................................................................15
Connection – WE 516 ..................................................................................................................................................................................................16
Connection – AE 525-A................................................................................................................................................................................................16
Connection – AE 526-DG.............................................................................................................................................................................................17
Trouble shooting ..........................................................................................................................................................................................................18
Inspection / Maintenance .............................................................................................................................................................................................19
Introduction
Maintenance and repair
Every building operator is responsible for ensuring that its safety
equipment works reliably. Regular and professional maintenance ensures
that your system is always operational. As specialist SHEV businesses,
the D+H service and sales partners are best qualified to carry out
maintenance. By taking out a maintenance contract, operators can prove
at all times that they have fulfilled their obligations.
Quality with guarantee
For all D+H SHEV systems, which have been installed by a D+H service
and sales partner and are regularly serviced, you will receive extended
warranty services. Ask your local D+H service and sales partner about
this.
Always nearby
With the network of our own subsidiaries and exclusive partners, we are
represented nearly all over the world.
Are you looking for your local D+H partner?
Simply visit our website:
www.dh-partner.com
D+H service and sales partners
Safety in the building not only comes from the product. Above all, safety
results from competence. All D+H service and sales partners are certified
and regularly trained specialist SHEV businesses. Working closely with
D+H Mechatronic AG as the manufacturer, they develop comprehensive
system solutions for SHEVs and natural building ventilation. With integral
customer support and continuous quality assurance in all phases of the
project: from sales advice, planning and project management through to
installation, commissioning, repair and service. The highest national and
international quality standards are therefore reliably fulfilled.
Installation and operation
The comprehensive network of D+H service and sales partners is at your
disposal to professionally install your system and commission it. Our
partner system guarantees that D+H products are installed exclusively by
trained and experienced fitters, in compliance with the technical guidelines
and specifications. Personal handover and training for users is included.
Gebrauchsanleitung
Housing
transformer
rail
cable ducts
motherboard with rectifier card
and power supply plug-in unit
keys
instruction for use and
SHEV operational book
Fig. RZN 43xx-E6
Content
Assembly scheme
GE
F8,0A
min
15
2
45 30
sec
20
2
60 40
Air Indicat o r
12345678910
Bft.
LE
Weather plug-in unit
Group plug-in unit for ventilationGroup plug-in unit
Line plug-in unit
Servo plug-in unit
Line Group
BMS
External control
Window drive
SHEV button
Ventilation button
Fire detector Wind / rain transmitter
Room temp. control
Air-Indicator
panel
GE
F8,0A
min
15
2
45 30
sec
20
2
60 40
OK
Intended use
- SHEV control panel in modular plug-in card design for complex
control requirements
- Lines / groups in any combination
- Comfort functions for daily ventilation
- Only for inside mounting
Operating voltage 230 V AC!
Risk of injury from electric shock!
- Connection has to be carried out only by an authorized electrical
specialist
- Only for inside mounting
- Just use unchanged original D+H parts
Safety notes
Inspection and maintenance has to be carried out according to D+H
maintenance notes. Only original D+H spare parts may be used. Repair
is to be carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft cloth.
Do not use cleaning agents or solvents.
Repair and cleaning
We declare under our sole responsibility that the product described under
“Technical Data” is in conformity with the following directives:
2014/30/EU, 2014/35/EU, EU 305/2011
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder Maik Schmees
Member of the Board Authorized signatory,
Technical Director
20.03.2018
Declaration of Conformity
Observe regulations for danger warning systems VDE 0833, guidelines for
electrical systems VdS 2221, VDE 0100, DIN 18232 for smoke and heat
vent systems, regulations of the local fire-brigade and of EVU for
connection to mains supply.
Important Regulations
Smoke gases are to be carried off as unhindered as possible through
smoke and heat vent opening in case of fire. Size, kind and
arrangement of the opening is of decisive significance for an optimal
effect of the smoke and heat vent system.
These requirements are defined in the relevant regulations of the
respective country.
More informations, are also available under www.rwa-heute.de.
The SHEV opening should be coordinated with the responsible fire
protection authority.
SHEV opening
RZN 43xx-E RZN 43xx-E 3/202/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
English English
Electrical devices, accessories, batteries and packaging should be sorted
for environmental-friendly recycling.
Do not dispose electrical devices and batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for waste electrical and
electronic equipment and its implementation into national right, electrcal
devices that are no longer usable must be collected separately and dispo-
sed of in an environmentally correct manner.
Disposal
Overview
The components that are part of the VdS Approval are signed with an
VdS logo.
VdS Approval
Introduction / Assembly scheme ....................................................................................................................................................................................2
Intended use / Safety notes ...........................................................................................................................................................................................3
SHEV opening................................................................................................................................................................................................................3
Important Regulations / Repair and cleaning .................................................................................................................................................................3
Declaration of Conformity / Disposal..............................................................................................................................................................................3
Technical Data................................................................................................................................................................................................................4
Emergency Supply .........................................................................................................................................................................................................4
Pictograph Explanation ..................................................................................................................................................................................................4
Optional Functional Extensions......................................................................................................................................................................................4
Internal structure of standard control panels..................................................................................................................................................................5
Main board GP 509 / General plug-ins...........................................................................................................................................................................6
Supply plug-in card VE 520 / VE 530.............................................................................................................................................................................7
Servicetimer ...................................................................................................................................................................................................................7
Line plug-in card LE 513 ................................................................................................................................................................................................7
Group plug-in card GE 628 (-L) V2 ................................................................................................................................................................................8
Servo plug-in card SE 622 .............................................................................................................................................................................................9
Weather plug-in card WE 516 ......................................................................................................................................................................................10
Window-lock plug-in card AE 525-A / AE 526-DG........................................................................................................................................................10
Cables for D+H SHEV systems / Wiring plan / 230 V supply.......................................................................................................................................11
Connection assignment................................................................................................................................................................................................12
Connection – overview.................................................................................................................................................................................................13
Connection – Parallel connection of RT 45 on LE 513 ................................................................................................................................................13
Connection – Fire dectector or fire alarm system to LE 513 ........................................................................................................................................14
Connection – GE 628 V2 .............................................................................................................................................................................................14
Connection – SE 622 ...................................................................................................................................................................................................15
Connection – WE 516 ..................................................................................................................................................................................................16
Connection – AE 525-A................................................................................................................................................................................................16
Connection – AE 526-DG.............................................................................................................................................................................................17
Trouble shooting ..........................................................................................................................................................................................................18
Inspection / Maintenance .............................................................................................................................................................................................19
Introduction
Maintenance and repair
Every building operator is responsible for ensuring that its safety
equipment works reliably. Regular and professional maintenance ensures
that your system is always operational. As specialist SHEV businesses,
the D+H service and sales partners are best qualified to carry out
maintenance. By taking out a maintenance contract, operators can prove
at all times that they have fulfilled their obligations.
Quality with guarantee
For all D+H SHEV systems, which have been installed by a D+H service
and sales partner and are regularly serviced, you will receive extended
warranty services. Ask your local D+H service and sales partner about
this.
Always nearby
With the network of our own subsidiaries and exclusive partners, we are
represented nearly all over the world.
Are you looking for your local D+H partner?
Simply visit our website:
www.dh-partner.com
D+H service and sales partners
Safety in the building not only comes from the product. Above all, safety
results from competence. All D+H service and sales partners are certified
and regularly trained specialist SHEV businesses. Working closely with
D+H Mechatronic AG as the manufacturer, they develop comprehensive
system solutions for SHEVs and natural building ventilation. With integral
customer support and continuous quality assurance in all phases of the
project: from sales advice, planning and project management through to
installation, commissioning, repair and service. The highest national and
international quality standards are therefore reliably fulfilled.
Installation and operation
The comprehensive network of D+H service and sales partners is at your
disposal to professionally install your system and commission it. Our
partner system guarantees that D+H products are installed exclusively by
trained and experienced fitters, in compliance with the technical guidelines
and specifications. Personal handover and training for users is included.
Pictograph Explanation
Weather automatic switched on
Automatic temperature control
Signal "rain"
Signal "wind-force switchpoint"
Smoke and heat vent alarm
Control panel O.K.
Fuse drive
Power supply
Vent button function “OPEN”
Vent/ smoke vent function “CLOSE”
Fault
Battery fault
Charging voltage controller
Check pins ground fault
Regulator for wind-force switchpoint
Regulator for signal storage time
Ground fault
Smoke detector / fuse
Smoke-vent button / fuse
Window-lock group / fuse
Stroke-instantaneous value in per cent
Hysteresis
Regulator for Ventilation time
Regulator for OPEN running time
Automatic weather control activated
min
15
2
45 30
sec
20
2
60 40
OK
AUTO
M
Type RZN 4308-E RZN 4316-E RZN 4332-E RZN 4364-E
Power supply 230 V AC, 50Hz, +10% ... -15%
Rated power 240 VA 500 VA 1000 VA 2000 VA
Stand-by operating ca. 10,4 W ca. 11 W ca. 16,2 W ca. 26 W
Output voltage 24 V DC
Ripple ca. 48% (In conjunction with GKS 566/xx (page 6): < 2 Vss = < 3%)
Output rated current 8 A 16 A 32 A 64 A
Mode of operation
- Monitoring Continuous duty
- Alarm / ventilation Short-time duty (30 % DC)
Housing Steel sheet
Color RAL 7035; light grey
Ingress protection IP 54
Protection class I
Temperature range -5 ... +40 °C
RZN 43xx-E RZN 43xx-E 5/204/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Optional Functional Extensions
Internal structure of standard control panels
M8
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
Akku
Type 3
Akku
Type 3
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
E3
ESP1 ESP2 ESP3
+
-
M8
Akku
Type 3
Akku
Type 3
M16
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
Akku
Type 4
Akku
Type 4
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
E3
ESP1 ESP2 ESP3
+
-
Akku
Type 4
M16
Akku
Type 4
+
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6 ESP7 ESP8
E4 E3
+
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M16
Akku
Type 4
Akku
Type 4
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M32
2x Akku
Type 5
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
E3
ESP1 ESP2 ESP3
+
-
M32
2x Akku
Type 5
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M32
2x Akku
Type 5
+
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6 ESP7 ESP8
E4 E3
+
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M64
Akku
Type 6
Akku
Type 6
RZN 4308-E6
WxHxD: 500 × 500 × 210 mm
RZN 4316-E9
WxHxD: 600 × 600 × 210 mm
RZN 4332-E9
WxHxD: 600 × 600 × 210 mm
RZN 4308-E9
WxHxD: 600 × 600 × 210 mm
RZN 4316-E14
WxHxD: 600 × 600 × 210 mm
RZN 4332-E14
WxHxD: 600 × 800 × 250 mm
RZN 4316-E6
WxHxD: 500 × 500 × 210 mm
RZN 4332-E6
WxHxD: 600 × 600 × 210 mm
RZN 4364-E12
WxHxD: 800 × 1000 × 300 mm
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
+
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6 ESP7 ESP8
E4 E3
+
E3
ESP1 ESP2 ESP3
+
-
Transformer
(8, 16, 32 or 64 A)
Cable duct
35 mm top hat rail for
installation of modules
Main board GP 509
with 6 free plug-in slots
Extension board ZE 8
with 8 free plug-in slots
Extension board ZE 3
with 3 free plug-in slots
Emergency power supply for 72 hours.
Use only VdS approved accumulators.
RZN 4308-E : 2 x accumulator type 3 (12V, 7,0Ah ± 15%)
RZN 4316-E : 2 x accumulator type 4 (12V, 12Ah ± 15%)
RZN 4332-E : 2 x accumulator type 5 (12V, 18Ah ± 15%)
RZN 4364-E : 2 x accumulator type 6 (12V, 26Ah ± 15%)
24 V - Emergency Supply
Technical Data
+
+
-
+
2x 12 V
-
English English
Slot E1 / E2
AM 44-Z Alarm-cutoff module
for sirens, fire bells and flashing lights
TR 42 Cutoff relay module
for remote indication of fault or alarm
WFR 41 Weather-stepping-relay
for connecting of several D+H smoke vent control panels on a
wind/ rain detector
Slot LE
IM 44-E Impulse module
Triggering of alarm and reset fromFAS or
series connected smoke vent system
UM 41-Z Transmission module for RT 42-Z
Slot GE
AT 41 Drive starting time-lag module
in conjunction with shading systems
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
Pictograph Explanation
Weather automatic switched on
Automatic temperature control
Signal "rain"
Signal "wind-force switchpoint"
Smoke and heat vent alarm
Control panel O.K.
Fuse drive
Power supply
Vent button function “OPEN”
Vent/ smoke vent function “CLOSE”
Fault
Battery fault
Charging voltage controller
Check pins ground fault
Regulator for wind-force switchpoint
Regulator for signal storage time
Ground fault
Smoke detector / fuse
Smoke-vent button / fuse
Window-lock group / fuse
Stroke-instantaneous value in per cent
Hysteresis
Regulator for Ventilation time
Regulator for OPEN running time
Automatic weather control activated
min
15
2
45 30
sec
20
2
60 40
OK
AUTO
M
Type RZN 4308-E RZN 4316-E RZN 4332-E RZN 4364-E
Power supply 230 V AC, 50Hz, +10% ... -15%
Rated power 240 VA 500 VA 1000 VA 2000 VA
Stand-by operating ca. 10,4 W ca. 11 W ca. 16,2 W ca. 26 W
Output voltage 24 V DC
Ripple ca. 48% (In conjunction with GKS 566/xx (page 6): < 2 Vss = < 3%)
Output rated current 8 A 16 A 32 A 64 A
Mode of operation
- Monitoring Continuous duty
- Alarm / ventilation Short-time duty (30 % DC)
Housing Steel sheet
Color RAL 7035; light grey
Ingress protection IP 54
Protection class I
Temperature range -5 ... +40 °C
RZN 43xx-E RZN 43xx-E 5/204/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Optional Functional Extensions
Internal structure of standard control panels
M8
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
Akku
Type 3
Akku
Type 3
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
E3
ESP1 ESP2 ESP3
+
-
M8
Akku
Type 3
Akku
Type 3
M16
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
Akku
Type 4
Akku
Type 4
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
E3
ESP1 ESP2 ESP3
+
-
Akku
Type 4
M16
Akku
Type 4
+
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6 ESP7 ESP8
E4 E3
+
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M16
Akku
Type 4
Akku
Type 4
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M32
2x Akku
Type 5
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
E3
ESP1 ESP2 ESP3
+
-
M32
2x Akku
Type 5
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M32
2x Akku
Type 5
+
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6 ESP7 ESP8
E4 E3
+
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
M64
Akku
Type 6
Akku
Type 6
RZN 4308-E6
WxHxD: 500 × 500 × 210 mm
RZN 4316-E9
WxHxD: 600 × 600 × 210 mm
RZN 4332-E9
WxHxD: 600 × 600 × 210 mm
RZN 4308-E9
WxHxD: 600 × 600 × 210 mm
RZN 4316-E14
WxHxD: 600 × 600 × 210 mm
RZN 4332-E14
WxHxD: 600 × 800 × 250 mm
RZN 4316-E6
WxHxD: 500 × 500 × 210 mm
RZN 4332-E6
WxHxD: 600 × 600 × 210 mm
RZN 4364-E12
WxHxD: 800 × 1000 × 300 mm
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
VE
520
+
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6 ESP7 ESP8
E4 E3
+
E3
ESP1 ESP2 ESP3
+
-
Transformer
(8, 16, 32 or 64 A)
Cable duct
35 mm top hat rail for
installation of modules
Main board GP 509
with 6 free plug-in slots
Extension board ZE 8
with 8 free plug-in slots
Extension board ZE 3
with 3 free plug-in slots
Emergency power supply for 72 hours.
Use only VdS approved accumulators.
RZN 4308-E : 2 x accumulator type 3 (12V, 7,0Ah ± 15%)
RZN 4316-E : 2 x accumulator type 4 (12V, 12Ah ± 15%)
RZN 4332-E : 2 x accumulator type 5 (12V, 18Ah ± 15%)
RZN 4364-E : 2 x accumulator type 6 (12V, 26Ah ± 15%)
24 V - Emergency Supply
Technical Data
+
+
-
+
2x 12 V
-
English English
Slot E1 / E2
AM 44-Z Alarm-cutoff module
for sirens, fire bells and flashing lights
TR 42 Cutoff relay module
for remote indication of fault or alarm
WFR 41 Weather-stepping-relay
for connecting of several D+H smoke vent control panels on a
wind/ rain detector
Slot LE
IM 44-E Impulse module
Triggering of alarm and reset fromFAS or
series connected smoke vent system
UM 41-Z Transmission module for RT 42-Z
Slot GE
AT 41 Drive starting time-lag module
in conjunction with shading systems
GK VE
E1 E2
Trafo
Trafo
+
+B
-
ESP1 ESP2 ESP3 ESP4 ESP5 ESP6
E4 E3
General plug-ins
566
NBE
N+
24V=
VE
530
Service
USB/PC
F3,15A
F1,25A
F0,125A
* Third party drives typically require stable, load and independent of line voltage
stresses. For this stabilizer circuits are used.
Such circuits usually keep the voltage up to a certain maximum current constant.
Further stabilization with switching power supplies on request.
Rectifier card GK
1 x per control panel
up to an overall power of 32 A
or
2 x per control panel
up to an total current of 64 A
(2 motherboards).
Mains-battery-plug-in unit
NBE 566
Supply plug-in card
VE 520 / VE 530
1 x per control panel
Monitoring of
- grid
- battery voltage
- battery charging voltage
- earth leakage protection.
Stabilization GPS 566/32 *
to stabilize the output voltage when
connecting an external drive.
(Possibly housing extension is needed.)
Output current : 32 A
Output voltage : 24 V DC ±10%
Residual ripple : < 2 Vss = < 3%
Stabilization GPS 566/64 *
to stabilize the output voltage when
connecting an external drive.
(Possibly housing extension is needed.)
Output current : 64 A
Output voltage : 24 V DC ±10%
Residual ripple : < 2 Vss = < 3%
Line plug-in card LE 513
VE
530
Service
USB/PC
F3,15A
F1,25A
F0,125A
Supply plug-in card VE 520 / VE 530
RZN 43xx-E RZN 43xx-E 7/206/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Main board GP 509
free slots for LE/ GE/ WE/ AE/ SE 622
rectifier card GK power supply plug-in unit VE
optional functional extension by modules
optional functional extension by modules
slots E1 and E2
for extension of control panel
(ribbon cable required)
fire detection
element
(thermal maximum
detector) *
battery
connection
Earthing
* Monitoring the inner temperature of the controller. An emergency opening of the complete smoke and heat
ventilation system, under alarm conditions, will occur if the inner temperature exceeds 72°C, caused by the radiant
heat from a fire in the immediate vicinity of the installation location.
Note: There is only one fire detection element per control panel needed, otherwise from 2 × GP509 they are connected in parallel.
1 2 3 4 5 6 7
N
-N
+
S
S
t-
S
A
L+
KZ
Z
E1
1 2 3 4 5 6 7
N
-N
+
S
S
t-
S
A
L+
KZ
Z
E2
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7
8 9 10 11 8 9 10 11 8 9 10 11 8 9 10 11 8 9 10 11 8 9 10 11
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
GK VE
Trafo
Trafo
+
+B
-
ERDE
E3
E4
VE
530
Service
USB/PC
F3,15A
F1,25A
F0,125A
1 2 3 4 5 6
X5
Malfunction 1
Malfunction 2
LT Out 1
LT In 1
LT Out 2
LT In 2
513
LE
0
I
F1,25A
TEST
F0,125A
F0,125A
12345
ON
DIP-switch
factory setting
English English
Servicetimer:
An overdue maintenance of the system will be indicated by the control
panel after about ca. 14 to 16 months. If connected to "Malfunction 1" or
"Malfunction 2" the yellow LED in the RT 45 will start flashing.
A malfunction of the smoke vent system will be still indicated by the
extinction of the green LED in the RT 45.
The ventilation function OPEN can be interrupted for up to 2 groups via
the connections "LT In" and "LT Out" after the maintenance time is
expired. This function can be deactivated via the servicetool.
Attention: Reset of the service timer can be carried out by a
specialist company only, who has been authorized by the
appliance manufacturer.
1 x per control panel
VE 520 : Control panels up to 16 A
VE 530 : Control panels from 32 A
Functions:
Monitoring of
- Grid
- Battery voltage
- Battery charging voltage
- Earth leakage protection.
Integrated Servicetimer
- Programmable interval
- 2 Malfunction outputs (e.g. for RT 45)
- 2 floating outputs for disconnecting the ventilation function
- Reset via SCS software or BI-BT 2
- line plug-in card for connecting of maximum 14 fire detectors and 8 smoke vent buttons each
- Functions:
- line On/ Off
- alarm/ fault
Encoding LE 513
Following functions can be encoded on the plug-in board using the DIP-switch.
DIP-switch 1 on ON = In the case of a group fault (e.g. with broken motor line or missing end module) the control panel will be
switched to alarm i.e. the smoke vent opens.
DIP-switch 2 on ON = In the case of a line fault (e.g. with interrupted button line or missing terminal resistor) the control panel will be
switched to alarm, i.e. the smoke vent opens.
DIP-switch 3 on ON = Smoke detector alarm cannot be reset pressing the button in the smoke vent button once. DIP-switch 3 must be
switched to OFF if you want to carry out a remote reset of smoke detectors via the smoke vent button. Should only be
used if DIP-switch 4 and 5 = OFF.
DIP-switch 4 on ON = In case of alarm directly preceded groups, and the line will be triggered.
Important: Every previous plug-in slot for the triggering line and group must be occupied. Both the lines must be
switched OFF/ON for “Smoke Detector Reset” at the control panel.
Dip-switch 5 on ON = This line is released by a line connected in series.
Important: Every previous plug-in slot after the releasing line must be occupied! Both the lines must be
switched OFF/ON for “Smoke Detector Reset” at the control panel.
General plug-ins
566
NBE
N+
24V=
VE
530
Service
USB/PC
F3,15A
F1,25A
F0,125A
* Third party drives typically require stable, load and independent of line voltage
stresses. For this stabilizer circuits are used.
Such circuits usually keep the voltage up to a certain maximum current constant.
Further stabilization with switching power supplies on request.
Rectifier card GK
1 x per control panel
up to an overall power of 32 A
or
2 x per control panel
up to an total current of 64 A
(2 motherboards).
Mains-battery-plug-in unit
NBE 566
Supply plug-in card
VE 520 / VE 530
1 x per control panel
Monitoring of
- grid
- battery voltage
- battery charging voltage
- earth leakage protection.
Stabilization GPS 566/32 *
to stabilize the output voltage when
connecting an external drive.
(Possibly housing extension is needed.)
Output current : 32 A
Output voltage : 24 V DC ±10%
Residual ripple : < 2 Vss = < 3%
Stabilization GPS 566/64 *
to stabilize the output voltage when
connecting an external drive.
(Possibly housing extension is needed.)
Output current : 64 A
Output voltage : 24 V DC ±10%
Residual ripple : < 2 Vss = < 3%
Line plug-in card LE 513
VE
530
Service
USB/PC
F3,15A
F1,25A
F0,125A
Supply plug-in card VE 520 / VE 530
RZN 43xx-E RZN 43xx-E 7/206/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Main board GP 509
free slots for LE/ GE/ WE/ AE/ SE 622
rectifier card GK power supply plug-in unit VE
optional functional extension by modules
optional functional extension by modules
slots E1 and E2
for extension of control panel
(ribbon cable required)
fire detection
element
(thermal maximum
detector) *
battery
connection
Earthing
* Monitoring the inner temperature of the controller. An emergency opening of the complete smoke and heat
ventilation system, under alarm conditions, will occur if the inner temperature exceeds 72°C, caused by the radiant
heat from a fire in the immediate vicinity of the installation location.
Note: There is only one fire detection element per control panel needed, otherwise from 2 × GP509 they are connected in parallel.
1 2 3 4 5 6 7
N
-N
+
S
S
t-
S
A
L+
KZ
Z
E1
1 2 3 4 5 6 7
N
-N
+
S
S
t-
S
A
L+
KZ
Z
E2
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7
8 9 10 11 8 9 10 11 8 9 10 11 8 9 10 11 8 9 10 11 8 9 10 11
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
GK VE
Trafo
Trafo
+
+B
-
ERDE
E3
E4
VE
530
Service
USB/PC
F3,15A
F1,25A
F0,125A
1 2 3 4 5 6
X5
Malfunction 1
Malfunction 2
LT Out 1
LT In 1
LT Out 2
LT In 2
513
LE
0
I
F1,25A
TEST
F0,125A
F0,125A
12345
ON
DIP-switch
factory setting
English English
Servicetimer:
An overdue maintenance of the system will be indicated by the control
panel after about ca. 14 to 16 months. If connected to "Malfunction 1" or
"Malfunction 2" the yellow LED in the RT 45 will start flashing.
A malfunction of the smoke vent system will be still indicated by the
extinction of the green LED in the RT 45.
The ventilation function OPEN can be interrupted for up to 2 groups via
the connections "LT In" and "LT Out" after the maintenance time is
expired. This function can be deactivated via the servicetool.
Attention: Reset of the service timer can be carried out by a
specialist company only, who has been authorized by the
appliance manufacturer.
1 x per control panel
VE 520 : Control panels up to 16 A
VE 530 : Control panels from 32 A
Functions:
Monitoring of
- Grid
- Battery voltage
- Battery charging voltage
- Earth leakage protection.
Integrated Servicetimer
- Programmable interval
- 2 Malfunction outputs (e.g. for RT 45)
- 2 floating outputs for disconnecting the ventilation function
- Reset via SCS software or BI-BT 2
- line plug-in card for connecting of maximum 14 fire detectors and 8 smoke vent buttons each
- Functions:
- line On/ Off
- alarm/ fault
Encoding LE 513
Following functions can be encoded on the plug-in board using the DIP-switch.
DIP-switch 1 on ON = In the case of a group fault (e.g. with broken motor line or missing end module) the control panel will be
switched to alarm i.e. the smoke vent opens.
DIP-switch 2 on ON = In the case of a line fault (e.g. with interrupted button line or missing terminal resistor) the control panel will be
switched to alarm, i.e. the smoke vent opens.
DIP-switch 3 on ON = Smoke detector alarm cannot be reset pressing the button in the smoke vent button once. DIP-switch 3 must be
switched to OFF if you want to carry out a remote reset of smoke detectors via the smoke vent button. Should only be
used if DIP-switch 4 and 5 = OFF.
DIP-switch 4 on ON = In case of alarm directly preceded groups, and the line will be triggered.
Important: Every previous plug-in slot for the triggering line and group must be occupied. Both the lines must be
switched OFF/ON for “Smoke Detector Reset” at the control panel.
Dip-switch 5 on ON = This line is released by a line connected in series.
Important: Every previous plug-in slot after the releasing line must be occupied! Both the lines must be
switched OFF/ON for “Smoke Detector Reset” at the control panel.
Master CLOSE funct.
ZA...-SG
Drive with "-SGI"
Input 4-20 mA
Input 0-20 mA
Input 0-10 V
1
OFF
ON
ON
ON
ON
ON
2
ON
OFF
OFF
OFF
345678
Power failure sync.
OFF
OFF
ON
S2 S6
SGI
SG
no function
628 V2
GE
M
F8,0A
min
15
2
45 30
sec
20
2
60 40
12345678910
ON
DIP-switch
factory setting
Group plug-in card GE 628 (-L) V2
Attention:
When group-DIP-switch 8 is ON, the smoke vent is re-triggered during a period of 30 minutes at intervals of 2 minutes in accordance with VdS
2581, based on the set alarm direction (see DIP-switch 6). Therefor, the drive must be safeguarded against blockage in accordance with VdS
2580 Part 4.7. . All D+H drives meet this precondition. Otherwise DIP-switch 8 must be switched on OFF.
High-Speed function:
All D+H drives with SHEV high-speed function
are supported. In daily ventilation operation, a
considerable noise reduction is achieved
through the reduced drive speed. In case of
SHEV the drives run - triggered through the
orange monitoring line - with a very high speed
to reach the OPEN position defined within 60
seconds at the most.
622
Servo plug-in card SE 622
Functional description
Auto I/O
-N
SE 622
RZN 43xx-E / GVL 83xx-E
10
11 3 4 5 76 8 9
0
min. 7 sec.
RZN 43xx-E RZN 43xx-E 9/208/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
min
15
2
45 30
sec
20
2
60 40
12345678
ON
Factory settings
(0 - 10 V)
SG SGI
ON
1 2 3 4 5 6 7 8
S2
S6
S4
Attention!
Encode only, if unit is not plugged-in.
Encoding SE 622
English English
Functions GE 628 V2:
- For control of smoke and heat ventilation drives in conjunction with the line plug-in card LE 513
- Drives up to max. 10A can be connected to a group plug-in card
- Smoke and heat ventilation re-triggering function
- Group-fault display
- Power failure-CLOSE function
- Possibility of combination with further groups
- Adjustable ventilation time limitation and OPEN-running time limitation
Functions GE 628-L V2:
- For control of ventilation drives
- Drives up to max. 10A can be connected to a group plug-in card
- Possibility of combination with further groups
- Adjustable ventilation time limitation and OPEN-running time limitation
Encoding GE 628 (-L) V2
Following functions can be encoded on the plug-in board using the DIP-switch.
GE 628 V2 GE 628-L V2
DIP-switch 1 on ON OPEN-running time limitation in ventilation operation
Only possible if DIP-switch 5 = ON (Storage operation in OPEN-direction).
Running time in OPEN-direction can be limited by using the potentiometer.
If the vent button is actuated in OPEN-direction, the drives/ NSHEVs run for
the duration of the running time.
DIP-switch 2 on ON Ventilation time limitation
Only possible if DIP-switch 4 = ON (memory mode in CLOSED-direction). Ventilation time can be
set by using a potentiometer.
The drives / NSHEVs will automatically close again, after the set time has expired.
DIP-switch 3 on ON OPEN-retriggering
Only possible if DIP-switch 1 = ON (OPEN-running time limitation).
If DIP-switch 1 is switched to ON, the OPEN-running time limitation can be re-triggered again.
DIP-switch 4 on ON Storage operation in CLOSED-direction
Press vent button once briefly. > The drives / NSHEVs will close to their final position.
DIP-switch 4 on OFF Tip operation in CLOSED-direction
The drives / NSHEVs will close as long as the vent button is pressed.
DIP-switch 5 on ON Storage operation in OPEN-direction
Press vent button once briefly. > The drives / NSHEVs will open to their final position.
DIP-switch 5 on OFF Tip operation in OPEN-direction
The drives / NSHEVs will open as long as the vent button is pressed.
DIP-switch 6 on ON Group CLOSE in case of alarm - no function -
The drives/ NSHEVs will close in the case of alarm.
DIP-switch 7 on ON Power failure-CLOSE - only function, if control panel
Only possible if DIP-switch 4 = ON. has emergency
In the case of power failure, the drives/ NSHEVs. power supply -
will close.
DIP-switch 8 on ON Alarm re-triggering - no function -
During a period of 30 minutes, the smoke vent is triggered
at intervals of 2 minutes in accordance with VdS 2581.
DIP-switch 9 on ON The group plug-in card can be triggered in OPEN-direction via Az signals.
DIP-switch 10 on ON The group plug-in card can be triggered in CLOSED-direction via Zz signals. (If for example a rain detector is connected,
the switch must be ON, otherwise no closing will take place.)
The servo plug-in unit SE 622 is used as interface module between Building Management System
(BMS) or Central air conditioning plant (ZLT) and D+H Smoke extraction and vent system RZN 43xx-
E. The unit is to convert an analogue preset value from the BMS into a drive stroke between 0-100%
in conjunction with D+H drive with option "-SGI". Opening width can be steplessly controlled,
depending on the BMS input value.
For the function of the SE 622, two wires are additionally required to the drive with position
indicator for actual value feedback.
- Cable connection BMS - servo plug-in unit: provide 2 wires Ø 0,8 mm per servo plug-in unit.
- one group plug-in unit is required per servo plug-in unit.
- all connected drives must have the same stroke.
- Safe closing of all drives when the setpoint value from the BMS < 5 %.
Technical Data:
System requirements : RZN 43xx-E / GVL 83xx-E in conjunction with
D+H drive with option "-SGI" or ZA...-SG
Input (BMS) : selectable 0 -10V or 0 - 20 mA or 4 - 20 mA
Input impedance : voltage = 50 kΩ, current = 50 Ω
Hysteresis : adjustable 2-10%
Output :- 0 or 24VDC, only in conjunction with GE 628 (-L) V2
- 0-10 V current position
- max. 5 SE 622 per control panel
Function:
Triggering is effected as analogue setpoint value
via a 2-wire circuit. Either current-controlled with
values 0 - 20 mA, 4 - 20 mA or voltage-controlled
with values 0 - 10 V. This corresponds to an
opening width of 0 - 100%. BMS input is
electrically isolated from the D+H-system
voltage.
The servo plug-in unit compares the setpoint value
from BMS with the actual value of the drive and
operates the drive to the desired position, using
the group plug-in unit. The servo function can be
switched off at the plug-in unit or by remote
control. Then the drive group can be manually
opened or closed by built-in vent buttons or
external vent buttons LT. The actual value can
be checked on a digital display on the plug-in
unit. The feedback to the BMS is provided as
analogue signal with values 0 - 10 V.
The servo function is overridden in the case of an
alarm from the Smoke and heat vent system. The
function “Master CLOSE“, e.g. in the case of rain
or a timer, has a higher priority than the servo
function and can be activated by DIP-switch (5).
The drives are automatically closed in the case of
wire break or short circuit on the setpoint value wire.
Power failure-synchronisation
After a power failure with the DIP switch No. 6
switched to ON, the drive will go to its position
CLOSED in order to be able to open again up to
the given value (e.g. 50% from the BMS) in the
OPEN direction, after the power failure has been
resolved.
Ple a se n ote : Th e d r ive is co n tro l l ed
automatically, so there is a potential source of
danger of pinch or shear points in the area of the
drive. With the factory-setting “OFF“, the drive
must run to position „CLOSED“ after a power
failure, via a vent button with visual contact to
the drive. For this, the automatic operation of the
servo plug-in unit SE 622 must be switched OFF
beforehand.
D+H Drives with the option "-SGI" are
equipped with a digital pulse generator. The
servo plug-in unit must know the total pulse
number of the drive so that the setpoint value
from the BMS can be equally distributed over the
opening width. For this purpose, there is an
operating mode “Measure opening width“.
The clamps 8 + 9 (-N + Auto I/O) must be bridged
on the plug-in slot of the servo plug-in unit for the
activation of this operating mode.
This operating mode is activated with reset
button (S4). The button (S4) must be activated
for at least for 7 seconds.
Please note: In this mode, the drive will run over
the entire stroke length in the OPEN and in the
CLOSE direction. A stop is not possible at this
time.
The measured stroke will be saved in the
SE 622.
The drives of type ZA...-SG are equipped with
an analogue position indicator. The servo
plug-in unit compares the set value of BMS
with the actual value of the drive, and directs
the drive to the desired position using the
group plug-in unit.
Attention! The SE 622 is not compatible with
the SE 621! (Observe connection diagram!)
Master CLOSE funct.
ZA...-SG
Drive with "-SGI"
Input 4-20 mA
Input 0-20 mA
Input 0-10 V
1
OFF
ON
ON
ON
ON
ON
2
ON
OFF
OFF
OFF
345678
Power failure sync.
OFF
OFF
ON
S2 S6
SGI
SG
no function
628 V2
GE
M
F8,0A
min
15
2
45 30
sec
20
2
60 40
12345678910
ON
DIP-switch
factory setting
Group plug-in card GE 628 (-L) V2
Attention:
When group-DIP-switch 8 is ON, the smoke vent is re-triggered during a period of 30 minutes at intervals of 2 minutes in accordance with VdS
2581, based on the set alarm direction (see DIP-switch 6). Therefor, the drive must be safeguarded against blockage in accordance with VdS
2580 Part 4.7. . All D+H drives meet this precondition. Otherwise DIP-switch 8 must be switched on OFF.
High-Speed function:
All D+H drives with SHEV high-speed function
are supported. In daily ventilation operation, a
considerable noise reduction is achieved
through the reduced drive speed. In case of
SHEV the drives run - triggered through the
orange monitoring line - with a very high speed
to reach the OPEN position defined within 60
seconds at the most.
622
Servo plug-in card SE 622
Functional description
Auto I/O
-N
SE 622
RZN 43xx-E / GVL 83xx-E
10
11 3 4 5 76 8 9
0
min. 7 sec.
RZN 43xx-E RZN 43xx-E 9/208/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
min
15
2
45 30
sec
20
2
60 40
12345678
ON
Factory settings
(0 - 10 V)
SG SGI
ON
1 2 3 4 5 6 7 8
S2
S6
S4
Attention!
Encode only, if unit is not plugged-in.
Encoding SE 622
English English
Functions GE 628 V2:
- For control of smoke and heat ventilation drives in conjunction with the line plug-in card LE 513
- Drives up to max. 10A can be connected to a group plug-in card
- Smoke and heat ventilation re-triggering function
- Group-fault display
- Power failure-CLOSE function
- Possibility of combination with further groups
- Adjustable ventilation time limitation and OPEN-running time limitation
Functions GE 628-L V2:
- For control of ventilation drives
- Drives up to max. 10A can be connected to a group plug-in card
- Possibility of combination with further groups
- Adjustable ventilation time limitation and OPEN-running time limitation
Encoding GE 628 (-L) V2
Following functions can be encoded on the plug-in board using the DIP-switch.
GE 628 V2 GE 628-L V2
DIP-switch 1 on ON OPEN-running time limitation in ventilation operation
Only possible if DIP-switch 5 = ON (Storage operation in OPEN-direction).
Running time in OPEN-direction can be limited by using the potentiometer.
If the vent button is actuated in OPEN-direction, the drives/ NSHEVs run for
the duration of the running time.
DIP-switch 2 on ON Ventilation time limitation
Only possible if DIP-switch 4 = ON (memory mode in CLOSED-direction). Ventilation time can be
set by using a potentiometer.
The drives / NSHEVs will automatically close again, after the set time has expired.
DIP-switch 3 on ON OPEN-retriggering
Only possible if DIP-switch 1 = ON (OPEN-running time limitation).
If DIP-switch 1 is switched to ON, the OPEN-running time limitation can be re-triggered again.
DIP-switch 4 on ON Storage operation in CLOSED-direction
Press vent button once briefly. > The drives / NSHEVs will close to their final position.
DIP-switch 4 on OFF Tip operation in CLOSED-direction
The drives / NSHEVs will close as long as the vent button is pressed.
DIP-switch 5 on ON Storage operation in OPEN-direction
Press vent button once briefly. > The drives / NSHEVs will open to their final position.
DIP-switch 5 on OFF Tip operation in OPEN-direction
The drives / NSHEVs will open as long as the vent button is pressed.
DIP-switch 6 on ON Group CLOSE in case of alarm - no function -
The drives/ NSHEVs will close in the case of alarm.
DIP-switch 7 on ON Power failure-CLOSE - only function, if control panel
Only possible if DIP-switch 4 = ON. has emergency
In the case of power failure, the drives/ NSHEVs. power supply -
will close.
DIP-switch 8 on ON Alarm re-triggering - no function -
During a period of 30 minutes, the smoke vent is triggered
at intervals of 2 minutes in accordance with VdS 2581.
DIP-switch 9 on ON The group plug-in card can be triggered in OPEN-direction via Az signals.
DIP-switch 10 on ON The group plug-in card can be triggered in CLOSED-direction via Zz signals. (If for example a rain detector is connected,
the switch must be ON, otherwise no closing will take place.)
The servo plug-in unit SE 622 is used as interface module between Building Management System
(BMS) or Central air conditioning plant (ZLT) and D+H Smoke extraction and vent system RZN 43xx-
E. The unit is to convert an analogue preset value from the BMS into a drive stroke between 0-100%
in conjunction with D+H drive with option "-SGI". Opening width can be steplessly controlled,
depending on the BMS input value.
For the function of the SE 622, two wires are additionally required to the drive with position
indicator for actual value feedback.
- Cable connection BMS - servo plug-in unit: provide 2 wires Ø 0,8 mm per servo plug-in unit.
- one group plug-in unit is required per servo plug-in unit.
- all connected drives must have the same stroke.
- Safe closing of all drives when the setpoint value from the BMS < 5 %.
Technical Data:
System requirements : RZN 43xx-E / GVL 83xx-E in conjunction with
D+H drive with option "-SGI" or ZA...-SG
Input (BMS) : selectable 0 -10V or 0 - 20 mA or 4 - 20 mA
Input impedance : voltage = 50 kΩ, current = 50 Ω
Hysteresis : adjustable 2-10%
Output :- 0 or 24VDC, only in conjunction with GE 628 (-L) V2
- 0-10 V current position
- max. 5 SE 622 per control panel
Function:
Triggering is effected as analogue setpoint value
via a 2-wire circuit. Either current-controlled with
values 0 - 20 mA, 4 - 20 mA or voltage-controlled
with values 0 - 10 V. This corresponds to an
opening width of 0 - 100%. BMS input is
electrically isolated from the D+H-system
voltage.
The servo plug-in unit compares the setpoint value
from BMS with the actual value of the drive and
operates the drive to the desired position, using
the group plug-in unit. The servo function can be
switched off at the plug-in unit or by remote
control. Then the drive group can be manually
opened or closed by built-in vent buttons or
external vent buttons LT. The actual value can
be checked on a digital display on the plug-in
unit. The feedback to the BMS is provided as
analogue signal with values 0 - 10 V.
The servo function is overridden in the case of an
alarm from the Smoke and heat vent system. The
function “Master CLOSE“, e.g. in the case of rain
or a timer, has a higher priority than the servo
function and can be activated by DIP-switch (5).
The drives are automatically closed in the case of
wire break or short circuit on the setpoint value wire.
Power failure-synchronisation
After a power failure with the DIP switch No. 6
switched to ON, the drive will go to its position
CLOSED in order to be able to open again up to
the given value (e.g. 50% from the BMS) in the
OPEN direction, after the power failure has been
resolved.
Ple a se n ote : Th e d r ive is co n tro l l ed
automatically, so there is a potential source of
danger of pinch or shear points in the area of the
drive. With the factory-setting “OFF“, the drive
must run to position „CLOSED“ after a power
failure, via a vent button with visual contact to
the drive. For this, the automatic operation of the
servo plug-in unit SE 622 must be switched OFF
beforehand.
D+H Drives with the option "-SGI" are
equipped with a digital pulse generator. The
servo plug-in unit must know the total pulse
number of the drive so that the setpoint value
from the BMS can be equally distributed over the
opening width. For this purpose, there is an
operating mode “Measure opening width“.
The clamps 8 + 9 (-N + Auto I/O) must be bridged
on the plug-in slot of the servo plug-in unit for the
activation of this operating mode.
This operating mode is activated with reset
button (S4). The button (S4) must be activated
for at least for 7 seconds.
Please note: In this mode, the drive will run over
the entire stroke length in the OPEN and in the
CLOSE direction. A stop is not possible at this
time.
The measured stroke will be saved in the
SE 622.
The drives of type ZA...-SG are equipped with
an analogue position indicator. The servo
plug-in unit compares the set value of BMS
with the actual value of the drive, and directs
the drive to the desired position using the
group plug-in unit.
Attention! The SE 622 is not compatible with
the SE 621! (Observe connection diagram!)
Releases 1 2 4 8 16 24 30
cable 4 x 0,6 100 50 25 / / / / m
cable 4 x 1, 600 300 150 75 30 / / m
cable 4 x 2, 1000 500 250 125 60 45 30 m
cross section (mm²) = simple cable lenght (m) x no. of releases
400
Tripping devices:
230 V AC, 50 Hz
Seperate electric circuit.
Mark fuses.
to further ones
see line lenghts and cross sections
Drive at smoke
vent opening SHEV control panel
vent button
ca. 1,2 m above
upper edge
firm flooring
smoke vent button
ca. 1,5 m above
upper edge
firm flooring
external control
4x 0,8 Ø
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
2x 0,8 Ø
2x 0,8 Ø
OK
OK
Wind / rain transmitter
4x 0,8 Ø
fire detector
SD-O 371 or FD-T 271
F0.125A
F0.125A
F1.25A
F6.3A
TEST
AE
526-DG
- window-lock plug-in card for triggering of
max. 8 pressure-gas generators
- release via smoke vent buttons and/ or fire
detectors
- LE 513 is not required
Window-lock plug-in card AE 526-DG
12
ON
DIP-switch
factory setting
AE
525-A
0
I
F6,3A
F1,25A
TEST
F0,125A
- window-lock plug-in card for triggering of
window-lock units
- release via smoke vent buttons and/ or fire
detectors
- LE 513 is not required
Window-lock plug-in card AE 525-A
12
ON
DIP-switch
factory setting
Functional description
516
Functions:
- Weather plug-in card for wind-/ rain transmitter, central vent button and temperature control
- Weather automatic On/ Off
- Operational control central Open/ Close
- Wind force sensitivity adjustable
- Signal retention time adjustable
- Wind/ rain indication Closed
Encoding WE 516
You can select an infinitely variable wind-force setting between 2 and 8
on the Beaufort scale using the regulator on the plug-in unit.
As soon as the wind force reaches the set value (time lag of a few seconds), the signal is
displayed on the plug-in card and, if available, on the control panel.
If the automatic weather control is ON, the system closes automatically. This is given priority, even
over an attempted opening by temperature control. The wind signal remains active for an adjustable
length of time to prevent continuous actuator operation during gusty wind conditions.
The regulator on the plug-in unit can be used to select the infinitely
adjustable signal storage time between 1 and 15 minutes.
Weather plug-in card WE 516 Wiring plan (Paragon)
System voltage 24 V!
Do not run cables with together power lines!
In case of a cable with ground wire (green / yellow)
this must not be used!
Cable and terminal boxes have to be labeled.
Cables for D+H SHEV systems
When selecting and installing the cables, the
regional electrical installation regulations
concerning wiring systems and the necessary
safety equipment, or guidelines on integrity
maintenance of electric lines are observed
(e.g. MLAR).
Notice:
No type designation is given for these cables,
because of a large variety on the market.
Please consult your D+H partner.
Group cable (control panel - drive)
At least three wire design:
- 2 wires for the supply of the drive
- 1 wire for line monitoring, on which also the
SHEV high speed (HS) signal is transmitted to
the drive. If line DIP switch 1 is ON, the group
will in case of a fault automatically triggered
and opens.
Line cable (control panel - detector)
The cables are monitored for short circuit and
for interruption. If line DIP switch 2 is ON, the
group will in case of a fault automatically
triggered and opens.
RZN 43xx-E RZN 43xx-E 11/2010/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Line lenghts and cross sections
GE 628 (-L) V2
1
120
200
2
60
100
3
40
65
4
30
50
5
24
40
6
20
33
7
17
28
8
15
25
m
m
Type
Total current
3 x 1,5 mm²
3 x 2,5 mm²
9
13
22
10
12
20
230 V AC, 50 Hz
Seperate electric circuit.
Mark fuses.
* RZN 4308-E = T 2 A
RZN 4316-E = T 2,5 A
RZN 4332-E = T 6,3 A
RZN 4364-E = T 10 A
*
230 V supply
GP 509
(RZN 4364-E = 2x GP 509)
English English
Function of DIP- switches:
S1-1 on ON failure = alarm
S1-2 -no function-
Function of DIP- switches:
S1-1 on ON failure = alarm
S1-2 -no function-
Releases 1 2 4 6 8
cable 2 x 0,8 (2 x 2 x 0,6) 150 130 90 50 10 m
cable 2 x 1,5² 450 400 270 140 20 m
cable 2 x 2,5² 750 650 450 240 35 m
Pressure gas generators:
Cross section (mm²) = Cable lenght (m) x Total current
80
Automatic rain control:
If the automatic weather control is on, the system will close automatically when it starts to rain. A signal, if available, will be indicated on module/ plug-in unit
and on the control panel.
To test, place a moist finger on the surface. Clean rain detector electrodes and insulator with mild soap water in the case of dirt accumulation and rinse off
thoroughly.
Automatic temperature control:
Ventilation control is carried out by a room temperature controller, if available, and if the Automatic temperature control is switched on and if no wind / or rain
signal is indicated.
If a wind / or rain signal is present, this has priority and it will close the system.
Manual Control:
The system fully opens or closes fully by pressing the or button once briefly .
Pressing both buttons at the same time / or pressing the “Stop” button on the operator panel stops the system at any intermediate position.
Manual control is only enabled if no wind, rain or temperature signal is being processed or if the automatic control has been deactivated.
Releases 1 2 4 8 16 24 30
cable 4 x 0,6 100 50 25 / / / / m
cable 4 x 1, 600 300 150 75 30 / / m
cable 4 x 2, 1000 500 250 125 60 45 30 m
cross section (mm²) = simple cable lenght (m) x no. of releases
400
Tripping devices:
230 V AC, 50 Hz
Seperate electric circuit.
Mark fuses.
to further ones
see line lenghts and cross sections
Drive at smoke
vent opening SHEV control panel
vent button
ca. 1,2 m above
upper edge
firm flooring
smoke vent button
ca. 1,5 m above
upper edge
firm flooring
external control
4x 0,8 Ø
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
2x 0,8 Ø
2x 0,8 Ø
OK
OK
Wind / rain transmitter
4x 0,8 Ø
fire detector
SD-O 371 or FD-T 271
F0.125A
F0.125A
F1.25A
F6.3A
TEST
AE
526-DG
- window-lock plug-in card for triggering of
max. 8 pressure-gas generators
- release via smoke vent buttons and/ or fire
detectors
- LE 513 is not required
Window-lock plug-in card AE 526-DG
12
ON
DIP-switch
factory setting
AE
525-A
0
I
F6,3A
F1,25A
TEST
F0,125A
- window-lock plug-in card for triggering of
window-lock units
- release via smoke vent buttons and/ or fire
detectors
- LE 513 is not required
Window-lock plug-in card AE 525-A
12
ON
DIP-switch
factory setting
Functional description
516
Functions:
- Weather plug-in card for wind-/ rain transmitter, central vent button and temperature control
- Weather automatic On/ Off
- Operational control central Open/ Close
- Wind force sensitivity adjustable
- Signal retention time adjustable
- Wind/ rain indication Closed
Encoding WE 516
You can select an infinitely variable wind-force setting between 2 and 8
on the Beaufort scale using the regulator on the plug-in unit.
As soon as the wind force reaches the set value (time lag of a few seconds), the signal is
displayed on the plug-in card and, if available, on the control panel.
If the automatic weather control is ON, the system closes automatically. This is given priority, even
over an attempted opening by temperature control. The wind signal remains active for an adjustable
length of time to prevent continuous actuator operation during gusty wind conditions.
The regulator on the plug-in unit can be used to select the infinitely
adjustable signal storage time between 1 and 15 minutes.
Weather plug-in card WE 516 Wiring plan (Paragon)
System voltage 24 V!
Do not run cables with together power lines!
In case of a cable with ground wire (green / yellow)
this must not be used!
Cable and terminal boxes have to be labeled.
Cables for D+H SHEV systems
When selecting and installing the cables, the
regional electrical installation regulations
concerning wiring systems and the necessary
safety equipment, or guidelines on integrity
maintenance of electric lines are observed
(e.g. MLAR).
Notice:
No type designation is given for these cables,
because of a large variety on the market.
Please consult your D+H partner.
Group cable (control panel - drive)
At least three wire design:
- 2 wires for the supply of the drive
- 1 wire for line monitoring, on which also the
SHEV high speed (HS) signal is transmitted to
the drive. If line DIP switch 1 is ON, the group
will in case of a fault automatically triggered
and opens.
Line cable (control panel - detector)
The cables are monitored for short circuit and
for interruption. If line DIP switch 2 is ON, the
group will in case of a fault automatically
triggered and opens.
RZN 43xx-E RZN 43xx-E 11/2010/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Line lenghts and cross sections
GE 628 (-L) V2
1
120
200
2
60
100
3
40
65
4
30
50
5
24
40
6
20
33
7
17
28
8
15
25
m
m
Type
Total current
3 x 1,5 mm²
3 x 2,5 mm²
9
13
22
10
12
20
230 V AC, 50 Hz
Seperate electric circuit.
Mark fuses.
* RZN 4308-E = T 2 A
RZN 4316-E = T 2,5 A
RZN 4332-E = T 6,3 A
RZN 4364-E = T 10 A
*
230 V supply
GP 509
(RZN 4364-E = 2x GP 509)
English English
Function of DIP- switches:
S1-1 on ON failure = alarm
S1-2 -no function-
Function of DIP- switches:
S1-1 on ON failure = alarm
S1-2 -no function-
Releases 1 2 4 6 8
cable 2 x 0,8 (2 x 2 x 0,6) 150 130 90 50 10 m
cable 2 x 1,5² 450 400 270 140 20 m
cable 2 x 2,5² 750 650 450 240 35 m
Pressure gas generators:
Cross section (mm²) = Cable lenght (m) x Total current
80
Automatic rain control:
If the automatic weather control is on, the system will close automatically when it starts to rain. A signal, if available, will be indicated on module/ plug-in unit
and on the control panel.
To test, place a moist finger on the surface. Clean rain detector electrodes and insulator with mild soap water in the case of dirt accumulation and rinse off
thoroughly.
Automatic temperature control:
Ventilation control is carried out by a room temperature controller, if available, and if the Automatic temperature control is switched on and if no wind / or rain
signal is indicated.
If a wind / or rain signal is present, this has priority and it will close the system.
Manual Control:
The system fully opens or closes fully by pressing the or button once briefly .
Pressing both buttons at the same time / or pressing the “Stop” button on the operator panel stops the system at any intermediate position.
Manual control is only enabled if no wind, rain or temperature signal is being processed or if the automatic control has been deactivated.
RZN 43xx-E RZN 43xx-E 13/2012/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
8 9 10 11
2 3 4 5 6 71
L (LT) n.c.
S
Z (LT)
A (LT)
N– (LT)
Z (LT)
A (LT)
E
Mot.a
Mot.b
8 9 10 11
2 3 4 5 6 71
L (LT) n.c.
n.c.
Z (LT)
A (LT)
N– (LT)
Z (LT)
A (LT)
n.c.
Mot.a
Mot.b
8 9 10 11
2 3 4 5 6 71
HLT+ (out) N–
AUTO I/O
SGI+
SGI–
HLT– (out)
Z
A
HLT+ (in)
HLT– (in)
N+ (in)
8 9 10 11
2 3 4 5 6 71
N+ ZZ2
N–
ZMP1
ZMP2
Regen
Wind
N–
AZ
ZZ1
T–
8 9 10 11
2 3 4 5 6 71
R (RM) ALA
S
n.c.
n.c.
(RM)
T (RT)
(RT)
K (RT)
A (RT)
Z (RT)
Connection assignment
1 2 3 4 5 6 7
N
-N
+
S
S
t-
S
A
L+
KZ
Z
E1 / E2
N–
N+
SSt
SAL
K
ZZ
8 9 10 11
2 3 4 5 6 71
R (RM) Z (RT)
S
K (RT)
A (RT)
(RM)
T (RT)
(RT)
E
A+
A–
526-DG
8 9 10 11
2 3 4 5 6 71
R (RM) n.c.
S
K (RT)
A (RT)
(RM)
T (RT)
(RT)
E
DG+
DG–
Connecting the
RT 45 malfunction LED
for displaying the
servicetimer
Connection – overview
2
8
316475
RT 45
28316475
RT 45
28316475
OK
Line
10kW
Alarm
Control
Line
CLOSE
Failure
n.c.
OK
(only LT 84U-SD)
LT 84-U (-SD)
LP
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
drive
Mot.b
Mot.a
HS
32
5
SD-O 371
32
SD-O 371
10kW
5
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
1 2 3 4 5 6
RZN 43xx-E
VE 520 / VE 530
Malfunction 1
Malfunction 2
LT out 1
LT in 1
LT out 2
LT in 2
X5
Connection – Parallel connection of RT 45 on LE 513
* Shunt connection by customer
2 2
8 8
3 31 16 64 47 7
5 5
RT 45
RT 45
2 28 83 31 16 64 47 7
5 5
RT 45 RT 45
2 28 83 31 16 64 47 7
5 5
OK OK
Line
Line
10kΩ
Alarm
Alarm
Control
Control
Line
Line
CLOSE
CLOSE
Failure
Failure
n.c.
n.c.
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
1 2 3 4 5 6
RZN 43xx-E
VE 520 / VE 530
Malfunction 1
Malfunction 2
LT out 1
LT in 1
LT out 2
LT in 2
X5
*
*
*
first to penultimate
button each
last button each
OK
10kΩ
English English
: Output emergency-supplied potential (–)
+ : Output emergency-supplied potential (+)
A (LT) : Input for OPEN signal through ventilation button
A (RT) : Output for line alarm, max. 60 mA
A– : Output for tripping devices (+)
A+ : Output for tripping devices (–)
ALA : Output (+) is switched off in cas of alarm, max. 1 A
AUTO I/O : Input automatic ON/OFF
AZ : Input for central ventilation OPEN signal
DG– : Output for pressure gas generators (–)
DG+ : Output for pressure gas generators (+)
E : Input for cable monitoring
HLT– (in) : Input BMS (–), GND
HLT+ (in) : Input BMS (+), 0 ... 20 mA, 4 ... 20 mA or 0 ... 10 V
HLT– (out) : Output for feedback to BMS (–), GND
HLT+ (out) : Output for feedback to BMS (+), 0 ... 10 V
K : Output for control / system OK, max. 60 mA
L : Output for OPEN indication ventilation button, max. 60 mA
Mot.a : Output for 24 V drives
Mot.b : Output for 24 V drives
n.c. : not connected
N– : Output not emergency-supplied potential (–) for ventilation functions
N+ : Output not emergency-supplied potential (+) for ventilation functions, max. 250 mA
N+ (in) : Input for emergency-supplied potential (+)
R : Input for automatic fire detectors or external control (+)
Regen : Input for rain CLOSE signal through rain detector
S : Output for local fault message of the plug-in unit, max. 60 mA
SAL : Output for general alarm (+), max. 1 A
SGI+ : Input from drive with SGI position indicator
SGI– : Input from drive with SGI position indicator
SSt : Output for general fault (+), max. 60 mA
T : Input for smoke vent buttons (+)
T– : Output for not emergency-supplied potential wind-rain-dependent potential - for room thermostat or timer, max. 100 mA
Wind : Input for wind CLOSE signal through wind sensor
Z : Input for CLOSE signal through smoke vent or ventilation button
ZMP1 : Output for weather CLOSE signal to further control panels, isolated, max. 60 V / 1 A
ZMP2 : Output for weather CLOSE signal to further control panels, isolated, max. 60 V / 1 A
ZZ : Input for central ventilation CLOSE signal
ZZ1 : Input for central ventilation CLOSE signal
ZZ2 : Input for central ventilation CLOSE signal
RZN 43xx-E RZN 43xx-E 13/2012/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
8 9 10 11
2 3 4 5 6 71
L (LT) n.c.
S
Z (LT)
A (LT)
N– (LT)
Z (LT)
A (LT)
E
Mot.a
Mot.b
8 9 10 11
2 3 4 5 6 71
L (LT) n.c.
n.c.
Z (LT)
A (LT)
N– (LT)
Z (LT)
A (LT)
n.c.
Mot.a
Mot.b
8 9 10 11
2 3 4 5 6 71
HLT+ (out) N–
AUTO I/O
SGI+
SGI–
HLT– (out)
Z
A
HLT+ (in)
HLT– (in)
N+ (in)
8 9 10 11
2 3 4 5 6 71
N+ ZZ2
N–
ZMP1
ZMP2
Regen
Wind
N–
AZ
ZZ1
T–
8 9 10 11
2 3 4 5 6 71
R (RM) ALA
S
n.c.
n.c.
(RM)
T (RT)
(RT)
K (RT)
A (RT)
Z (RT)
Connection assignment
1 2 3 4 5 6 7
N
-N
+
S
S
t-
S
A
L+
KZ
Z
E1 / E2
N–
N+
SSt
SAL
K
ZZ
8 9 10 11
2 3 4 5 6 71
R (RM) Z (RT)
S
K (RT)
A (RT)
(RM)
T (RT)
(RT)
E
A+
A–
526-DG
8 9 10 11
2 3 4 5 6 71
R (RM) n.c.
S
K (RT)
A (RT)
(RM)
T (RT)
(RT)
E
DG+
DG–
Connecting the
RT 45 malfunction LED
for displaying the
servicetimer
Connection – overview
2
8
316475
RT 45
28316475
RT 45
28316475
OK
Line
10kW
Alarm
Control
Line
CLOSE
Failure
n.c.
OK
(only LT 84U-SD)
LT 84-U (-SD)
LP
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
drive
Mot.b
Mot.a
HS
32
5
SD-O 371
32
SD-O 371
10kW
5
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
1 2 3 4 5 6
RZN 43xx-E
VE 520 / VE 530
Malfunction 1
Malfunction 2
LT out 1
LT in 1
LT out 2
LT in 2
X5
Connection – Parallel connection of RT 45 on LE 513
* Shunt connection by customer
2 2
8 8
3 31 16 64 47 7
5 5
RT 45
RT 45
2 28 83 31 16 64 47 7
5 5
RT 45 RT 45
2 28 83 31 16 64 47 7
5 5
OK OK
Line
Line
10kΩ
Alarm
Alarm
Control
Control
Line
Line
CLOSE
CLOSE
Failure
Failure
n.c.
n.c.
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
1 2 3 4 5 6
RZN 43xx-E
VE 520 / VE 530
Malfunction 1
Malfunction 2
LT out 1
LT in 1
LT out 2
LT in 2
X5
*
*
*
first to penultimate
button each
last button each
OK
10kΩ
English English
: Output emergency-supplied potential (–)
+ : Output emergency-supplied potential (+)
A (LT) : Input for OPEN signal through ventilation button
A (RT) : Output for line alarm, max. 60 mA
A– : Output for tripping devices (+)
A+ : Output for tripping devices (–)
ALA : Output (+) is switched off in cas of alarm, max. 1 A
AUTO I/O : Input automatic ON/OFF
AZ : Input for central ventilation OPEN signal
DG– : Output for pressure gas generators (–)
DG+ : Output for pressure gas generators (+)
E : Input for cable monitoring
HLT– (in) : Input BMS (–), GND
HLT+ (in) : Input BMS (+), 0 ... 20 mA, 4 ... 20 mA or 0 ... 10 V
HLT– (out) : Output for feedback to BMS (–), GND
HLT+ (out) : Output for feedback to BMS (+), 0 ... 10 V
K : Output for control / system OK, max. 60 mA
L : Output for OPEN indication ventilation button, max. 60 mA
Mot.a : Output for 24 V drives
Mot.b : Output for 24 V drives
n.c. : not connected
N– : Output not emergency-supplied potential (–) for ventilation functions
N+ : Output not emergency-supplied potential (+) for ventilation functions, max. 250 mA
N+ (in) : Input for emergency-supplied potential (+)
R : Input for automatic fire detectors or external control (+)
Regen : Input for rain CLOSE signal through rain detector
S : Output for local fault message of the plug-in unit, max. 60 mA
SAL : Output for general alarm (+), max. 1 A
SGI+ : Input from drive with SGI position indicator
SGI– : Input from drive with SGI position indicator
SSt : Output for general fault (+), max. 60 mA
T : Input for smoke vent buttons (+)
T– : Output for not emergency-supplied potential wind-rain-dependent potential - for room thermostat or timer, max. 100 mA
Wind : Input for wind CLOSE signal through wind sensor
Z : Input for CLOSE signal through smoke vent or ventilation button
ZMP1 : Output for weather CLOSE signal to further control panels, isolated, max. 60 V / 1 A
ZMP2 : Output for weather CLOSE signal to further control panels, isolated, max. 60 V / 1 A
ZZ : Input for central ventilation CLOSE signal
ZZ1 : Input for central ventilation CLOSE signal
ZZ2 : Input for central ventilation CLOSE signal
RZN 43xx-E RZN 43xx-E 15/2014/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Connection – Fire dectector or fire alarm system to LE 513
< optional >
Max. 14 fire detectors connectable. Only D+H approved detectors must be used.
Operating contact
Alarm resistor 1kW
FAS
Terminal resistor 10kW *
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
first to penultimate
fire detector
last
fire detector
SD-O 371
or
FD-T 271
EP 6
EM 2
1
C 3
IN 4
OUT 5
EP 6
EM 2
1
C 3
IN 4
OUT 5
10 kW
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
Connection – GE 628 V2
(only LT 84U-SD)
LT 84-U (-SD)
LP
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
Antrieb
Mot.b
Mot.a
HS
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6
RZN 43xx-E
VE 520 / VE 530
Malfunction 1
Malfunction 2
LT out 1
LT in 1
LT out 2
LT in 2
X5
Interruption of the
vent button function
OPEN after the
servicetimer
elapsed
Connection – SE 622
1 2 3 4 5 6 7
RZN 43xx-E
E1 / E2
N–
N+
SSt
SAL
K
ZZ
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
SE 622
+HLT (out)
–HLT (out)
Z
A
+HLT (in)
–HLT (in)
N+ (in)
N–
AUTO I/O
SGI+
SGI–
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
SGI
0 - 10 V
SG
0 - 10 V
0 - 20 mA
4 - 20 mA
BMS
0 - 10 V Drive
with -SGI
or ZA-SG
Connection – SE 622 with optional manual control
LT 84-U
P
LT 84-U-W
SP
Automatic
on/off
1 2 3 4 5 6 7
RZN 43xx-E
E1 / E2
N–
N+
SSt
SAL
K
ZZ
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
SE 622
+HLT (out)
–HLT (out)
Z
A
+HLT (in)
–HLT (in)
N+ (in)
N–
AUTO I/O
SGI+
SGI–
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
SGI
0 - 10 V
SG
0 - 10 V
0 - 20 mA
4 - 20 mA
BMS
0 - 10 V Drive
with -SGI
or ZA-SG
10kΩ
10kΩ
English English
* Terminal resistors for line monitoring
It is pinched in control panel for transport.
Take it off there and connect according to plan.
Terminal resistor must remain at terminal RM 1,2,
when no fire detector or external control exists!
RZN 43xx-E RZN 43xx-E 15/2014/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Connection – Fire dectector or fire alarm system to LE 513
< optional >
Max. 14 fire detectors connectable. Only D+H approved detectors must be used.
Operating contact
Alarm resistor 1kW
FAS
Terminal resistor 10kW *
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
first to penultimate
fire detector
last
fire detector
SD-O 371
or
FD-T 271
EP 6
EM 2
1
C 3
IN 4
OUT 5
EP 6
EM 2
1
C 3
IN 4
OUT 5
10 kW
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
LE 513
R
T
K
A
Z
ALA
S
n.c.
n.c.
Connection – GE 628 V2
(only LT 84U-SD)
LT 84-U (-SD)
LP
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
Antrieb
Mot.b
Mot.a
HS
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6
RZN 43xx-E
VE 520 / VE 530
Malfunction 1
Malfunction 2
LT out 1
LT in 1
LT out 2
LT in 2
X5
Interruption of the
vent button function
OPEN after the
servicetimer
elapsed
Connection – SE 622
1 2 3 4 5 6 7
RZN 43xx-E
E1 / E2
N–
N+
SSt
SAL
K
ZZ
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
SE 622
+HLT (out)
–HLT (out)
Z
A
+HLT (in)
–HLT (in)
N+ (in)
N–
AUTO I/O
SGI+
SGI–
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
SGI
0 - 10 V
SG
0 - 10 V
0 - 20 mA
4 - 20 mA
BMS
0 - 10 V Drive
with -SGI
or ZA-SG
Connection – SE 622 with optional manual control
LT 84-U
P
LT 84-U-W
SP
Automatic
on/off
1 2 3 4 5 6 7
RZN 43xx-E
E1 / E2
N–
N+
SSt
SAL
K
ZZ
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
LT MOT
GE 628 V2
L
N–
Z
A
E
Mot.a
Mot.b
n.c.
S
Z
A
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
SE 622
+HLT (out)
–HLT (out)
Z
A
+HLT (in)
–HLT (in)
N+ (in)
N–
AUTO I/O
SGI+
SGI–
EM 47 K
2x47kW
(BK)
(BK)
(OG)
Mot.b
Mot.a
HS
SGI
0 - 10 V
SG
0 - 10 V
0 - 20 mA
4 - 20 mA
BMS
0 - 10 V Drive
with -SGI
or ZA-SG
10kΩ
10kΩ
English English
* Terminal resistors for line monitoring
It is pinched in control panel for transport.
Take it off there and connect according to plan.
Terminal resistor must remain at terminal RM 1,2,
when no fire detector or external control exists!
RZN 43xx-E RZN 43xx-E 17/2016/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Connection – WE 516
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
WE 516
N+
Regen
Wind
N–
AZ
ZZ1
T–
ZZ2
N–
ZMP1
ZMP2
+
124357689
WRG 82
S 1/1
S 1/2
P3 P4
LT 84-U
P
LT 84-U-W
S51 3
P
Automatic
on/off
RTR 231
6 7
3 5
230 V AC
142
ITR 79
0
5
N
L
3412
67
°C
10 20
30
40
-10
CE
< optional >
Connection – AE 525-A
2
8
316475
RT 45
28316475
RT 45
28316475
OK
Line
10kW
Alarm
Control
Line
CLOSE
Failure
n.c.
OK
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
AE 525-A
R
T
E
A+
A–
Z
S
K
A
according to D+H table
for layout of cables
(see page 10)
Insert bridge! Tripping
devices
+
+
32
5
SD-O 371
32
SD-O 371
10kW
5
Connection – AE 526-DG
2
8
316475
RT 45
2 8 3 1 6 4 7 5
RT 45
2 8 3 1 6 4 7 5
OK
Line
10kW
Alarm
Control
Line
CLOSE
Failure
n.c.
OK
32
5
SD-O 371
32
SD-O 371
10kW
5
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
AE 526-DG
R
T
E
DG+
DG–
n.c.
S
K
A
according to D+H table
for layout of cables
(see page 10)
+
+
Pressure gas
generator
(max. 8 pcs.)
English English
potential free wind/rain indication
to further control panels
max. 60V / 1A
Alarm current
increase module
ICM 44
Alarm current
increase module
ICM 44
RZN 43xx-E RZN 43xx-E 17/2016/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Connection – WE 516
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
WE 516
N+
Regen
Wind
N–
AZ
ZZ1
T–
ZZ2
N–
ZMP1
ZMP2
+
124357689
WRG 82
S 1/1
S 1/2
P3 P4
LT 84-U
P
LT 84-U-W
S51 3
P
Automatic
on/off
RTR 231
6 7
3 5
230 V AC
142
ITR 79
0
5
N
L
3412
67
°C
10 20
30
40
-10
CE
< optional >
Connection – AE 525-A
2
8
316475
RT 45
28316475
RT 45
28316475
OK
Line
10kW
Alarm
Control
Line
CLOSE
Failure
n.c.
OK
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
AE 525-A
R
T
E
A+
A–
Z
S
K
A
according to D+H table
for layout of cables
(see page 10)
Insert bridge! Tripping
devices
+
+
32
5
SD-O 371
32
SD-O 371
10kW
5
Connection – AE 526-DG
2
8
316475
RT 45
2 8 3 1 6 4 7 5
RT 45
2 8 3 1 6 4 7 5
OK
Line
10kW
Alarm
Control
Line
CLOSE
Failure
n.c.
OK
32
5
SD-O 371
32
SD-O 371
10kW
5
1 2 3 4 5 6 7 8 9 10 11
RZN 43xx-E
RM RT
AE 526-DG
R
T
E
DG+
DG–
n.c.
S
K
A
according to D+H table
for layout of cables
(see page 10)
+
+
Pressure gas
generator
(max. 8 pcs.)
English English
potential free wind/rain indication
to further control panels
max. 60V / 1A
Alarm current
increase module
ICM 44
Alarm current
increase module
ICM 44
Inspection
Regular visual inspection between maintenance by the operator or
a trained person.
Immediately correct any defects.
Indicators:
- Green LEDs in the buttons must illuminate.
- Yellow LEDs in the buttons and the control panel are not allowed to
illuminate or flash (fault).
- If the green LEDs do not illuminate or if the yellow LEDs illuminate or
flash, contact After Sales service.
Examination:
- Check all appliances and cable connections for outer damage and dirt
accumulation.
- Fire detectors, smoke vent buttons, smoke vents and so on must not
be impaired in their function by goods in storage or structural
changings.
Once a year by a specialist company, who is authorized by the
appliance manufacturer.
Renew test badge, keep log book.
The respective current D+H maintenance instruction is decisive.
D+H authorized expert companies have been specially trained by D+H
for carrying out expertly this maintenance, and they get automatically
the latest maintenance instructions.
Following tests must be carried out in the course of maintenance:
- Outside examination / inspection of system components
- Checking of all relevant power supply units
- Functional testing of connected system components
- Record of competent carrying-out of maintenance, and designation
according to directions
Maintenance
RZN 43xx-E RZN 43xx-E 19/2018/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Please check following points, if the smoke vent system fails to function satisfactorily or the green control LED in the button fails to lighten. Diagnosis
must be carried out in following order: 1st supply plug-in card VE, 2nd line plug-in card LE, 3rd group plug-in card GE, 4th window lock plug-in card AE,
5th smoke detector and external control. Detected faults must be eliminated at once before the diagnosis is continued!
Trouble shooting
Symptoms
Pilot light extinguishes during closing
operation of drive, red LED diode
lightens, flap can't be closed.
Pilot light extinguishes during opening
operation of drive after approx. 20 sec.,
red LED diode lightens.
Detector cannot be reset, though
there is no smoke existing.
Detector fails to respond, when
checked with smoke.
Smoke vent is opens without external
alarm; smoke vent can be reset again.
Smoke vent opens without external alarm.
Smoke vent cannot be reset again.
Smoke vent is not opening, though
external system gives alarm.
Causes Remedy
Earth fault.
Malfunction in accumulator.
No 230 V power supply available.
Line is disconnected.
Malfunction in smoke detector or
smoke vent button line.
Malfunction in smoke detector line RM.
Malfunction in smoke vent button line RT.
Malfunction in group.
Malfunction in group.
Malfunction in group.
Malfunction in plug-in card.
Malfunction in smoke detector line RM.
Malfunction in smoke vent button line RT.
Malfunction in line to magnetic valve.
Detector is dirty or faulty.
Detector is faulty or wrong type.
External system gives possibly only
short contact by malfunction or has
given alarm or false alarm and has
been unknown reset again.
Ensure, that contact in external system
is opened. If external alarm is not
resettable by malfunction, search
there for malfunction.
Main contact is not closing.
Eliminate earth fault.
Check accumulator, connection and fuse.
Call in-house electrician immediately for eliminating
power failure.
Connect line.
For exact diagnosis proceed as follows.
1. Bridge diagnostic pin
against middle pin on line plug-in card.
Check fuse, connections, cables, terminal resistor,
clamps, smoke detectors and external control.
2. Bridge diagnostic pin
against middle pin on line plug-in card.
Check fuses, connections, cables, terminal resistors,
terminals and smoke vent buttons.
Check fuses, connections, cables, and
terminal resistor on drive.
Check terminal resistor or terminal module
between terminal 5 and 7.
Check terminal resistor or terminal module
between terminal 5 and 6.
For diagnosis proceed as follows.
Check fuse, terminals and loop resistance.
Exchange detector.
Exchange detector.
In case of repetition, disconnect contact.
Search for fault in external system.
Disconnect temporary perhaps, so that the
smoke vent remains operative.
Search for interruption; check whether
contact in external system is really closing.
LED lightens.
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
fails to lighten.
fails to lighten.
fails to lighten.
fails to lighten.
OK
OK
1. Bridge diagnostic pin
against middle pin on plug-in card.
Check fuses, connections, cables, terminal resistor,
terminals, smoke detectors and external control.
2. Bridge diagnostic pin
against middle pin on plug-in card.
Check fuses, connections, cables, terminal resistor,
terminals and smoke vent buttons.
To test the function of the earth fault checkup, the diagnosis pins on the VE must be bridgeover.
If the LED does not light, it might be necessary to check the grounding and connect it correctly.
Group plug-in card GE
Window-lock plug-in card AE
Smoke detector
External control
Line plug-in card LE
English English
Inspection
Regular visual inspection between maintenance by the operator or
a trained person.
Immediately correct any defects.
Indicators:
- Green LEDs in the buttons must illuminate.
- Yellow LEDs in the buttons and the control panel are not allowed to
illuminate or flash (fault).
- If the green LEDs do not illuminate or if the yellow LEDs illuminate or
flash, contact After Sales service.
Examination:
- Check all appliances and cable connections for outer damage and dirt
accumulation.
- Fire detectors, smoke vent buttons, smoke vents and so on must not
be impaired in their function by goods in storage or structural
changings.
Once a year by a specialist company, who is authorized by the
appliance manufacturer.
Renew test badge, keep log book.
The respective current D+H maintenance instruction is decisive.
D+H authorized expert companies have been specially trained by D+H
for carrying out expertly this maintenance, and they get automatically
the latest maintenance instructions.
Following tests must be carried out in the course of maintenance:
- Outside examination / inspection of system components
- Checking of all relevant power supply units
- Functional testing of connected system components
- Record of competent carrying-out of maintenance, and designation
according to directions
Maintenance
RZN 43xx-E RZN 43xx-E 19/2018/20 99.826.07 4.1/08/1899.826.07 4.1/08/18
Please check following points, if the smoke vent system fails to function satisfactorily or the green control LED in the button fails to lighten. Diagnosis
must be carried out in following order: 1st supply plug-in card VE, 2nd line plug-in card LE, 3rd group plug-in card GE, 4th window lock plug-in card AE,
5th smoke detector and external control. Detected faults must be eliminated at once before the diagnosis is continued!
Trouble shooting
Symptoms
Pilot light extinguishes during closing
operation of drive, red LED diode
lightens, flap can't be closed.
Pilot light extinguishes during opening
operation of drive after approx. 20 sec.,
red LED diode lightens.
Detector cannot be reset, though
there is no smoke existing.
Detector fails to respond, when
checked with smoke.
Smoke vent is opens without external
alarm; smoke vent can be reset again.
Smoke vent opens without external alarm.
Smoke vent cannot be reset again.
Smoke vent is not opening, though
external system gives alarm.
Causes Remedy
Earth fault.
Malfunction in accumulator.
No 230 V power supply available.
Line is disconnected.
Malfunction in smoke detector or
smoke vent button line.
Malfunction in smoke detector line RM.
Malfunction in smoke vent button line RT.
Malfunction in group.
Malfunction in group.
Malfunction in group.
Malfunction in plug-in card.
Malfunction in smoke detector line RM.
Malfunction in smoke vent button line RT.
Malfunction in line to magnetic valve.
Detector is dirty or faulty.
Detector is faulty or wrong type.
External system gives possibly only
short contact by malfunction or has
given alarm or false alarm and has
been unknown reset again.
Ensure, that contact in external system
is opened. If external alarm is not
resettable by malfunction, search
there for malfunction.
Main contact is not closing.
Eliminate earth fault.
Check accumulator, connection and fuse.
Call in-house electrician immediately for eliminating
power failure.
Connect line.
For exact diagnosis proceed as follows.
1. Bridge diagnostic pin
against middle pin on line plug-in card.
Check fuse, connections, cables, terminal resistor,
clamps, smoke detectors and external control.
2. Bridge diagnostic pin
against middle pin on line plug-in card.
Check fuses, connections, cables, terminal resistors,
terminals and smoke vent buttons.
Check fuses, connections, cables, and
terminal resistor on drive.
Check terminal resistor or terminal module
between terminal 5 and 7.
Check terminal resistor or terminal module
between terminal 5 and 6.
For diagnosis proceed as follows.
Check fuse, terminals and loop resistance.
Exchange detector.
Exchange detector.
In case of repetition, disconnect contact.
Search for fault in external system.
Disconnect temporary perhaps, so that the
smoke vent remains operative.
Search for interruption; check whether
contact in external system is really closing.
LED lightens.
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
lightens.
fails to lighten.
fails to lighten.
fails to lighten.
fails to lighten.
OK
OK
1. Bridge diagnostic pin
against middle pin on plug-in card.
Check fuses, connections, cables, terminal resistor,
terminals, smoke detectors and external control.
2. Bridge diagnostic pin
against middle pin on plug-in card.
Check fuses, connections, cables, terminal resistor,
terminals and smoke vent buttons.
To test the function of the earth fault checkup, the diagnosis pins on the VE must be bridgeover.
If the LED does not light, it might be necessary to check the grounding and connect it correctly.
Group plug-in card GE
Window-lock plug-in card AE
Smoke detector
External control
Line plug-in card LE
English English
D+H Mechatronic AG
Georg-Sasse-Str. 28-32
, Germany22949 Ammersbek
: +49 239Tel. 40-605 65
: +49Fax 40-605 65 254
E-Mail: info@dh-partner.com
www.dh-partner.com
© 2015 D+H Mechatronic AG, Ammersbek
Rights to technical modifications reserved.
99.826.07 4.1/08/18
English
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

D+H RZN 43xx-E Operating instructions

Category
Fire protection
Type
Operating instructions

D+H RZN 43xx-E is a modular smoke vent control panel designed for complex control requirements. Below you will find brief product information for D+H RZN 43xx-E:

  • It can be used to control lines and groups in any combination.
  • The control panel has comfort functions for daily ventilation.
  • It is suitable only for inside mounting.