VBESTLIFE SZC06 50A DIN Rail Digital Ammeter User manual

Category
Measuring, testing & control
Type
User manual
Din Rail Digital Ammeter 50A
Model: SZC06
User Manual
Ammeter Relay Button Description:
SET button; press and hold for 2 seconds to enter the setting mode, and then click to switch to
the next parameter settings.
Left shift key; Click this key to move the cursor one bit to the left.
Down key; Press this key to decrement the value of the menu parameter.
Increase key; press this key to increment the value of the menu parameter.
+ Press these 2 keys for 2 seconds at the same time to set the range. (That is, the
maximum display current value)
The transformer is 100/5A, set 100, 200A/5A, set 200, and so on…
Menu Function Description:
(Can set the upper and lower limit alarm, alarm return, alarm delay function)
Code Parameter Name Setup Instructions
Upper limit alarm value
Overcurrent alarm
When the display value is greater than this value,
the output relay will alarm
Lower limit alarm value
Undercurrent alarm
When the display value is lower than this value,
the output relay will alarm
Alarm return value
For example, the upper limit is set to
150
For example, when the conveyor belt motor is
blocked, the current exceeds 150A
SET
<
^
^
SET <
Return difference set 30
Alarm if the difference exceeds
150A;
The current drops to 120A to cancel
the alarm
Return value = 150-120 = 30
We set an upper limit of 150A, and the feeder
stops when it exceeds 150A.
The return difference is set to 30, and the
conveyor belt is motorized
After the current drops to 120A (upper limit 150
return 30 = 120)
The feeder then works.
Generate alarm delay value Delay before triggering (alarm after lasting more
than N seconds)
Release the alarm delay value Delay after power failure (delay disconnection
alarm)
Set ON: lock after alarm
Set OFF: alarm is not locked
Alarm lock; keep alerting after the alarm is
generated
Alarm is also generated when the non-alarm
condition is transferred
Alarm Relay Wiring Diagram:
Instrument auxiliary power supply Current signal input
POWER INPUT
110-220V AC power supply Connect to the current transformer CT
Relay alarm output
OUT
Contact capacity
NO COM NC 6A/250VAC; 6A/30VDC
Basic Functions:
The current smart meter is used for the measurement and display of a single current in an electrical
circuit, and can be attached to a relay alarm output.
Alarm delay and alarm return can be set. Real time current monitoring, alarm output function.
Precautions:
1. Before powering on, please reconfirm whether the auxiliary power supply, input signal, and wiring of
the instrument are correct. (The corresponding value of the auxiliary power supply must be matched,
otherwise the instrument will be burned out).
2. Monitoring a single current, the transformer cannot pass through multiple routes at the same time,
which will affect the measurement results.
3. Contact capacity 6A/250VAC, 6A/30VDC.