Generac GP6500 0056900 User manual

Category
Power generators
Type
User manual
www.generac.com or 1-888-436-3722
Owner's Manual
GP Series Portable Generator
MODELS: 005688-0, 005690-0,
005738-0
Introduction ............................................................. 1
Read this Manual Thoroughly ................................. 1
Safety Rules ........................................................... 2
Standards Index .............................................................3
General Information ................................................ 4
1.1 Unpacking ......................................................................4
1.1.1 Accessory Box ...................................................4
1.2 Assembly .......................................................................4
1.2.1 Assembling the Accessory Kit .............................4
Operation ................................................................ 4
2.1 Know the Generator .......................................................4
2.2 Hourmeter ......................................................................5
2.3 Cord Sets and Connection Plugs ....................................6
2.3.1 120 VAC, 20 Amp, Duplex Recepatcle.................6
2.3.2 120/240 VAC, 30 Amp Receptacle ......................6
2.4 How to Use the Generator ..............................................6
2.4.1 Grounding the Generator .....................................6
2.4.2 Connecting Electrical Loads ................................6
2.5 Don’t Overload the Generator ..........................................7
2.6 Wattage Reference Guide ...............................................7
2.7 Before Starting the Generator .........................................7
2.7.1 Adding Engine Oil ................................................7
2.7.2 Adding Gasoline ..................................................8
2.8 To Start the Engine .........................................................8
2.9 Stopping the Engine .......................................................9
2.10 Low Oil Level Shutdown System ....................................9
2.10.1 Sensing Low Oil Level .......................................9
Maintenance ........................................................... 9
3.1 Maintenance Schedule ...................................................9
3.2 Product Specifications ....................................................9
3.2.1 Generator Specifications .....................................9
3.2.2 Engine Specifications ..........................................9
3.3 General Recommendations ...........................................10
3.3.1 Generator Maintenance .....................................10
3.3.2 To Clean the Generator ......................................10
3.3.3 Engine Maintenance ..........................................10
3.3.4 Checking Oil Level ............................................10
3.3.5 Changing the Oil ...............................................10
3.3.6 Replacing the Spark Plug ..................................10
3.4 Service Air Filter ...........................................................11
3.5 Valve Clearance ............................................................11
3.6 General ........................................................................11
3.7 Long Term Storage .......................................................11
3.8 Other Storage Tips .......................................................11
Troubleshooting .................................................... 12
4.1 Troubleshooting Guide ..................................................12
Notes .................................................................... 13
Warranty ............................................................... 14
MANUAL DEL PROPIETARIO ............................. 15
MANUEL D'ENTRETIEN...................................... 31
Table of Contents
INTRODUCTION
Thank you for purchasing this model by Generac Power Systems,
Inc. This model is a compact, high performance, air-cooled,
engine driven generator designed to supply electrical power to
operate electrical loads where no utility power is available or in
place of utility due to a power outage.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest
Authorized Dealer for starting, operating and servicing procedures.
The operator is responsible for proper and safe use of the
equipment. We strongly recommend that the operator read this
manual and thoroughly understand all instructions before using the
equipment. We also strongly recommend instructing other users to
properly start and operate the unit. This prepares them if they need
to operate the equipment in an emergency. Save these instructions
for future reference. If you loan this unit to someone, ALWAYS loan
these instructions to the individual as well.
The generator can operate safely, efficiently and reliably only if it
is properly located, operated and maintained. Before operating or
servicing the generator:
Become familiar with and strictly adhere to all local, state and
national codes and regulations.
Study all safety warnings in this manual and on the product
carefully.
Become familiar with this manual and the unit before use.
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all inclusive.
If using a procedure, work method or operating technique that the
manufacturer does not specifically recommend, ensure that it is
safe for others. Also make sure the procedure, work method or
operating technique utilized does not render the generator unsafe.
THE INFORMATION CONTAINED HEREIN WAS BASED ON
MACHINES IN PRODUCTION AT THE TIME OF PUBLICATION.
GENERAC RESERVES THE RIGHT TO MODIFY THIS MANUAL AT
ANY TIME.
SAFETY RULES
Throughout this publication, and on tags and decals affixed to the
generator, DANGER, WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions about a particular
operation that may be hazardous if performed incorrectly or
carelessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR
ACTION WHICH, IF NOT AVOIDED, WILL RESULT
IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which,
if not avoided, could result in death or serious
injury.
Indicates a hazardous situation or action which,
if not avoided, could result in minor or moderate
injury.
NOTE:
Notes contain additional information important to a procedure
and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the action or service are essential to
preventing accidents.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates is as follows:

This symbol points out important safety
information that, if not followed, could
endanger personal safety and/or property of
others.
This symbol points out potential explosion
hazard.
This symbol points out potential fire hazard.

This symbol points out potential electrical
shock hazard.
GENERAL HAZARDS
Never operate in an enclosed area or indoors EVEN IF doors and
windows are open.
• For safety reasons, the manufacturer recommends that the
maintenance of this equipment is carried out by an Authorized
Dealer. Inspect the generator regularly, and contact the nearest
Authorized Dealer for parts needing repair or replacement.
Operate generator only on level surfaces and where it will not be
exposed to excessive moisture, dirt, dust or corrosive vapors.
Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving parts. Never remove any fan guard or shield
while the unit is operating.
Certain parts of the generator get extremely hot during
operation. Keep clear of the generator until it has cooled to
avoid severe burns.
Do NOT operate generator in the rain.
• Do not alter the construction of the generator or change
controls which might create an unsafe operating condition.
Never start or stop the unit with electrical loads connected
to receptacles AND with connected devices turned ON. Start
the engine and let it stabilize before connecting electrical
loads. Disconnect all electrical loads before shutting down the
generator.
Do not insert objects through unit’s cooling slots.
When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally
fatigued.
Introduction
1
Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in
dangerous operating conditions from leaking exhaust gases,
fuel leakage, oil leakage, etc.
On electric start models, disconnect the POSITIVE (+) battery
cable from the engine starter OR the NEGATIVE (-) battery
cable from the battery terminal, whichever is easier, before
transporting the generator.
EXHAUST & LOCATION HAZARDS
NEVER use inside, or in partly enclosed areas such as
garages, EVEN IF doors and windows are open! ONLY use
outdoors and far from windows, doors and vents. Only use in
an area that will not accumulate deadly exhaust.
The engine exhaust fumes contain carbon monoxide, which
you cannot see or smell. This poisonous gas, if breathed in
sufficient concentrations, can cause unconsciousness or even
death.
Adequate, unobstructed flow of cooling and ventilating air
is critical to correct generator operation. Do not alter the
installation or permit even partial blockage of ventilation
provisions, as this can seriously affect safe operation of the
generator. The generator MUST be operated outdoors.
This exhaust system must be properly maintained. Do nothing
that might render the exhaust system unsafe or in noncompliance
with any local codes and/or standards.
• Always use a battery operated carbon monoxide alarm indoors,
installed according to the manufacturers instructions.
If you start to feel sick, dizzy, or weak after the generator has
been running, move to fresh air IMMEDIATELY. See a doctor, as
you could have carbon monoxide poisoning.
ELECTRICAL HAZARDS
The generator produces dangerously high voltage when in
operation. Avoid contact with bare wires, terminals, connections,
etc., while the unit is running, even on equipment connected
to the generator. Ensure all appropriate covers, guards and
barriers are in place before operating the generator.
Never handle any kind of electrical cord or device while
standing in water, while barefoot or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
The National Electric Code (NEC) requires the frame and external
electrically conductive parts of the generator be properly
connected to an approved earth ground. Local electrical codes
may also require proper grounding of the generator. Consult
with a local electrician for grounding requirements in the area.
Use a ground fault circuit interrupter in any damp or highly
conductive area (such as metal decking or steel work).
Do not use worn, bare, frayed or otherwise damaged electrical
cord sets with the generator.
Before performing any maintenance on the generator, disconnect
the engine starting battery (if equipped) to prevent accidental
start up. Disconnect the cable from the battery post indicated
by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible,
attempt to free the victim from the live conductor. AVOID
DIRECT CONTACT WITH THE VICTIM. Use a non-conducting
implement, such as a rope or board, to free the victim from the
live conductor. If the victim is unconscious, apply first aid and
get immediate medical help.
FIRE HAZARDS
Gasoline is highly FLAMMABLE and its vapors are EXPLOSIVE.
Do not permit smoking, open flames, sparks or heat in the
vicinity while handling gasoline.
• Never add fuel while unit is running or hot. Allow engine to cool
completely before adding fuel.
Never fill fuel tank indoors. Comply with all laws regulating
storage and handling of gasoline.
Do not overfill the fuel tank. Always allow room for fuel
expansion. If tank is over-filled, fuel can overflow onto a hot
engine and cause FIRE or an EXPLOSION. Never store generator
with fuel in tank where gasoline vapors might reach an open
flame, spark or pilot light (as on a furnace, water heater or
clothes dryer). FIRE or EXPLOSION may result. Allow unit to
cool entirely before storage.
• Wipe up any fuel or oil spills immediately. Ensure that no
combustible materials are left on or near the generator. Keep the
area surrounding the generator clean and free from debris and
keep a clearance of five (5) feet on all side to allow for proper
ventilation of the generator.
Safety Rules
2
Do not insert objects through unit’s cooling slots.
• Do not operate the generator if connected electrical devices
overheat, if electrical output is lost, if engine or generator sparks
or if flames or smoke are observed while unit is running.
Keep a fire extinguisher near the generator at all times.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws,
the published information listed below may be used as a guideline
for operation of this equipment. Always reference the latest revision
available for the standards listed.
1. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC
CODE.
2. Article X, NATIONAL BUILDING CODE, available from the
American Insurance Association, 85 John Street, New York,
N.Y. 10038.
3. AGRICULTURAL WIRING HANDBOOK, available from the Food
and Energy Council, 909 University Avenue, Columbia, MO
65201.
4. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF
FARM STANDBY ELECTRICAL SYSTEMS, available from the
American Society of Agricultural Engineers, 2950 Niles Road,
St. Joseph, MI 49085.
MODEL NO:
SERIAL NO:
Unit ID Location
CALIFORNIA PROPOSITION 65 WARNING
Engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects
and other reproductive harm.
CALIFORNIA PROPOSITION 65 WARNING
This product contains or emits chemicals known to the
State of California to cause cancer, birth defects and
other reproductive harm.
Safety Rules
3
4
1.1 UNPACKING
Remove all packaging material.
Remove separate accessory box.
Remove the generator from carton.
1.1.1 ACCESSORY BOX
Check all contents. If any parts are missing or damaged locate an
authorized dealer at 1-888-436-3722.
Contents Include:
1 – Owner’s Manual • 1 - Left Handle Assembly
1 - Quart Oil SAE 30 • 1 - Right Handle Assembly
2 - Never-Flat Wheels • 1 - Frame Foot
1 - Foot Support
1 - Hardware Bag (containing the following):
2 - Rubber Feet 2 - 5/16” Bolts
2 - 5/16” Flat Washers 4 - 5/16” Locking Flange
Nuts
4 - 5/16” Carriage Bolts 2 - 5/16” Locking Cap Nuts
2 - 1/2” Axle Bolts 2 - 1/2” Locking Flange
Nuts
2 - 1/2" Flat Washers
1.2 ASSEMBLY
The generator requires some assembly prior to using it. If
problems arise when assembling the generator, please call the
Generator Helpline at 1-888-436-3722.
1.2.1 ASSEMBLING THE ACCESSORY KIT
The wheels are designed into the unit to greatly improve the
portability of the generator.
NOTE:
The wheels are not intended for over-the-road use.
1. Refer to Figure 1 and install Wheels as follows:
Slide the 1/2” Axle Bolt through the 1/2" Flat Washer, Wheel
and Wheel bracket on frame.
Install 1/2” Locking Flange Nuts onto 1/2” Flange Bolt.
2. Refer to Figure 1 and install Frame Foot, Foot Support and
Rubber Feet as shown.
Slide Rubber Bumper Stud through Foot Support and Frame
Foot, then install 5/16” Locking Flange Nuts.
Slide Frame Foot onto 5/16” Bolts; Install 5/16” Locking
Flange Nuts.
3. Refer to Figure 2 and install Handles as shown.
Remove top Curved Head Bolts and Cap Nuts (Cap Nuts will
be re-used).
Slide Handle Assembly over Frame Tube, aligning 2 holes.
Slide 5/16” Carriage Bolts through; Install 5/16” Cap Nuts.
Figure 1 – Wheel Assembly
FOOT SUPPORT
FOOT
Figure 2 – Install Handle Kit
2.1 KNOW THE GENERATOR
Read the Owner’s Manual and Safety Rules before operating this
generator.
Compare the generator to Figures 3 through 5 to become
familiarized with the locations of various controls and adjustments.
Save this manual for future reference.
1. 120 Volt AC, 20 Amp, Duplex Receptacle – Supplies electrical
power for the operation of 120 Volt AC, 20 Amp, single-phase,
60 Hz electrical lighting, appliance, tool and motor loads.
2. 120/240 Volt AC, 30 Amp Locking Receptacle – Supplies
electrical power for the operation of 120 and/or 240 Volt AC,
30 Amp, single-phase, 60 Hz, electrical lighting, appliance,
tool and motor loads.
3. Circuit Breakers (AC) – Each receptacle is provided with
a circuit breaker to protect the generator against electrical
overload.
General Information
5
Figure 3 - Control Panel
2
1
4
3
4. Hourmeter – Tracks hours of operation.
5. Air Filter – Filters intake air as it is drawn into the engine.
6. Choke Knob – Used when starting a cold engine.
7. Fuel Tank – Tank holds 6.6 U.S. gallons of fuel.
8. Grounding Lug – Ground the generator to an approved earth
ground here. See "Grounding the Generator" for details.
9. Run/Stop Switch – Controls the operation of the generator.
10. Muffler – Quiets the engine.
11. Handles – Pivot and retract for storage. Press the spring-
loaded button to move handles.
12. Gas Cap – Fuel fill location.
13. Fuel Gauge – Shows fuel level in tank.
14. Oil Fill – Add oil here.
15. Recoil Starter – Use to start engine manually.
16. Fuel Shut Off – Valve between fuel tank and carburetor.
17. Oil Drain – Use to drain engine oil.
Figure 4 - Generator Controls
Figure 5 - Generator Controls
2.2 HOURMETER
The Hourmeter tracks hours of operation for scheduled
maintenance:
There will be a "CHG OIL" message every 100 hours. The message
will flash one hour before and one hour after each 100 hour
interval, providing a two hour window to perform service.
This message will actually begin flashing at 99 hours and disable
itself at 101 hours, again providing a two hour window to perform
the service.
Every 200 hours the "SVC" icon on the lower left hand corner of
the display will flash. The message will flash one hour before and
one hour after each 200 hour interval providing a two hour window
to perform service.
When the hour meter is in the Flash Alert mode, the maintenance
message will always alternate with elapsed time in hours and
tenths. The hours will flash four times, then alternate with the
maintenance message four times until the meter resets itself.
100 hours - CHG OIL — Oil Change Interval (Every 100 hrs)
200 hours - SVC — Air Filter Interval (Every 200 hrs)
Operation
6
2.3 CORD SETS AND CONNECTION PLUGS
2.3.1 120 VAC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 20 Amp
push-to-reset circuit breaker (Figure 6). Use each socket to power
120 Volt AC, single phase, 60 Hz electrical loads requiring up to a
combined 2400 watts (2.4 kW) or 20 Amps of current. Use only
high quality, well-insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than
15 feet long, to prevent voltage drop and possible overheating of
wires.
Figure 6 - 120 Volt AC, 20 Amp, Duplex Receptacle
2.3.2 120/240 VAC, 30 AMP RECEPTACLE
Use a NEMA L14-30 plug with this receptacle (rotate to lock/
unlock). Connect a suitable 4-wire grounded cord set to the plug
and to the desired load. The cord set should be rated for 250 Volts
AC at 30 Amps (or greater) (Figure 7).
Figure 7 - 120/240 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase
loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or
240 Volt AC, 60 Hz, single phase loads requiring up to 7200 watts
(7.2 kW) of power at 30 Amps. The outlet is protected by 21/23/27
Amp (2-pole magnetic) circuit breakers for 5kW/5.5kW/6.5kW.
2.4 HOW TO USE THE GENERATOR
If there are any problems operating the generator, please call the
generator helpline at 1-888-436-3722.
2.4.1 GROUNDING THE GENERATOR
The National Electrical Code requires that the frame and
external electrically conductive parts of this generator be
properly connected to an approved earth ground (Figure 8).
Local electrical codes may also require proper grounding of the
unit. For that purpose, connecting a No. 10 AWG (American Wire
Gauge) stranded copper wire to the grounding lug and to an
earth-driven copper or brass grounding rod (electrode) provides
adequate protection against electrical shock. However, local codes
may vary widely. Consult with a local electrician for grounding
requirements in the area.
Figure 8 - Grounding the Generator
Proper grounding of the generator will help prevent electrical
shock in the event of a ground fault condition in the generator
or in connected electrical devices. Proper grounding also helps
dissipate static electricity, which often builds up in ungrounded
devices.
2.4.2 CONNECTING ELECTRICAL LOADS
DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT
connect 3-phase loads to the generator. DO NOT connect 50 Hz
loads to the generator.
• Let engine stabilize and warm up for a few minutes after
starting.
Plug in and turn on the desired 120 or 240 Volt AC, single
phase, 60 Hz electrical loads.
Add up the rated watts (or amps) of all loads to be connected
at one time. This total should not be greater than (a) the rated
wattage/amperage capacity of the generator or (b) circuit
breaker rating of the receptacle supplying the power. See "Don't
Overload the Generator".
Operation
7
2.5 DON’T OVERLOAD THE GENERATOR
Overloading a generator in excess of its rated wattage capacity
can result in damage to the generator and to connected electrical
devices. Observe the following to prevent overloading the unit:
Add up the total wattage of all electrical devices to be connected
at one time. This total should NOT be greater than the
generator's wattage capacity.
The rated wattage of lights can be taken from light bulbs. The
rated wattage of tools, appliances and motors can usually be
found on a data label or decal affixed to the device.
If the appliance, tool or motor does not give wattage, multiply
volts times ampere rating to determine watts (volts x amps =
watts).
Some electric motors, such as induction types, require about
three times more watts of power for starting than for running.
This surge of power lasts only a few seconds when starting
such motors. Make sure to allow for high starting wattage when
selecting electrical devices to connect to the generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other connected
loads.
The Wattage Reference Guide is provided to assist in determining
how many items the generator can operate at one time.
NOTE:
All figures are approximate. See data label on appliance for
wattage requirements.
2.6 WATTAGE REFERENCE GUIDE
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Running Watts
*Air Conditioner (12,000 Btu). . . . . . . . . . . . . . . . . . . . . . . . . . 1700
*Air Conditioner (24,000 Btu). . . . . . . . . . . . . . . . . . . . . . . . . . 3800
*Air Conditioner (40,000 Btu). . . . . . . . . . . . . . . . . . . . . . . . . . 6000
Battery Charger (20 Amp). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000
Chain Saw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Circular Saw (6-1/2") . . . . . . . . . . . . . . . . . . . . . . . . . . .800 to 1000
*Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5750
*Clothes Dryer (Gas) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
*Clothes Washer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1150
Coffee Maker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1750
*Compressor (1 HP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000
*Compressor (3/4 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800
*Compressor (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1400
Curling Iron. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
*Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 650
Disc Sander (9"). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Edge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Electric Blanket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400
Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Electric Range (per element). . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1250
*Freezer . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..700
*Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 875
*Garage Door Opener . . . . . . . . . . . . . . . . . . . . . . . . . . . .500 to 750
Hair Dryer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Hand Drill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250 to 1100
Hedge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Iron. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
*Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800
Lawn Mower. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Microwave Oven. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700 to 1000
*Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100
Oil Burner on Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Oil Fired Space Heater (140,000 Btu) . . . . . . . . . . . . . . . . . . . . . 400
Oil Fired Space Heater (85,000 Btu) . . . . . . . . . . . . . . . . . . . . . . 225
Oil Fired Space Heater (30,000 Btu) . . . . . . . . . . . . . . . . . . . . . . 150
*Paint Sprayer, Airless (1/3 HP) . . . . . . . . . . . . . . . . . . . . . . . . . 600
Paint Sprayer, Airless (handheld). . . . . . . . . . . . . . . . . . . . . . . . . 150
Radio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 to 200
*Refrigerator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
Slow Cooker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
*Submersible Pump (1-1/2 HP) . . . . . . . . . . . . . . . . . . . . . . . . 2800
*Submersible Pump (1 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000
*Submersible Pump (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
*Sump Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800 to 1050
*Table Saw (10") . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1750 to 2000
Television . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 to 500
Toaster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000 to 1650
Weed Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
* Allow 3 times the listed watts for starting these devices.
2.7 BEFORE STARTING THE GENERATOR
Prior to operating the generator, engine oil and gasoline will need
to be added, as follows:
2.7.1 ADDING ENGINE OIL
All oil should meet minimum American Petroleum Institute (API)
Service Class SJ, SL or better. Use no special additives. Select
the oil's viscosity grade according to the expected operating
temperature (also see chart).
Above 40° F, use SAE 30
Below 40° F and down to 10° F, use 10W-30
Below 10° F, use synthetic 5W-30
10W-30
10 W -30
SAE 30
SA E 30
Synthetic 5W-30
Sy nth e t ic 5 W-3 0
Operation
8

Any attempt to crank or start the engine
before it has been properly serviced with the
recommended oil may result in an engine
failure.
Place generator on a level surface.
Clean area around oil fill and remove oil fill cap and dipstick.
Wipe dipstick clean.
Slowly fill engine with oil through the oil fill opening until it
reaches the full mark. Stop filling occasionally to check oil level.
Be careful not to over fill.
Install oil fill cap and finger tighten securely.
Check engine oil level before starting each time thereafter.
2.7.2 ADDING GASOLINE

Never fill fuel tank indoors. Avoid spilling
gasoline on hot engine. Never fill fuel tank
when engine is running or hot. Allow unit/
engine to cool entirely before adding fuel. DO
NOT light a cigarette or smoke when filling
the fuel tank. Gasoline is highly flammable
and its vapors are explosive.

Do not overfill the fuel tank. Always leave
room for fuel expansion. If the fuel tank is
over-filled, fuel can over flow onto hot engine
and cause an explosion or fire.
Use regular UNLEADED gasoline with the generator engine. Do
not use any gasoline with more than 10% ethanol added. Do not
use E85 gasoline. Do not mix oil with gasoline.
Clean area around fuel fill cap, remove cap.
• Slowly add unleaded regular gasoline to fuel tank. Fill to bottom
of screen filter. Be careful not to overfill (Figure 9).
Install fuel cap and wipe up any spilled gasoline.
Figure 9 - Fuel Tank
DO NOT Fill Above Lip
Fuel
Fuel Tank
IMPORTANT: It is important to prevent gum deposits from forming
in fuel system parts such as the carburetor, fuel hose or tank
during storage. Alcohol-blended fuels (called gasohol, ethanol
or methanol) can attract moisture, which leads to separation and
formation of acids during storage. Acidic gas can damage the fuel
system of an engine while in storage. To avoid engine problems,
the fuel system should be emptied before storage of 30 days or
longer. See the "Storage" section. Never use engine or carburetor
cleaner products in the fuel tank as permanent damage may occur.
2.8 TO START THE ENGINE

Never start or stop engine with electrical
devices plugged into the receptacles AND
devices turned on.
Unplug all electrical loads from the unit's receptacles before
starting the engine.
Make sure the unit is in a level position.
OPEN the Fuel Shut-off Valve (Figures 10 and 11).
Figure 10 - Fuel Shut-off Valve
Figure 11 - Fuel Shut-off
Operation
9
Turn engine RUN/STOP switch to ON position (Figure 12).
• Pull engine CHOKE knob outward to FULL CHOKE position
(Figure 12).
To start engine, firmly grasp the recoil handle and pull slowly
until increased resistance is felt. Pull rapidly up and away.
When engine starts, move choke knob to 1/2-CHOKE position
until engine runs smoothly and then fully into RUN position. If
engine falters, move choke back out to 1/2-CHOKE position
until engine runs smoothly and then to RUN position.
NOTE:
If engine fires, but does not continue to run, move choke lever
to FULL CHOKE and repeat starting instructions.
Figure 12 - Choke Position
IMPORTANT: Do not overload the generator. Also, do not overload
individual panel receptacles. These outlets are protected against
overload with push-to-reset-type circuit breakers. If amperage
rating of any circuit breaker is exceeded, that breaker opens and
electrical output to that receptacle is lost. Read “Don’t Overload the
Generator” carefully.
2.9 STOPPING THE ENGINE
Shut off all loads, then unplug the electrical loads from
generator panel receptacles. Never start or stop the engine with
electrical devices plugged in and turned on.
Let engine run at no-load for several minutes to stabilize the
internal temperatures of engine and generator.
Move Run/Stop switch to OFF position.
Close fuel valve.
2.10 LOW OIL LEVEL SHUTDOWN SYSTEM
The engine is equipped with a low oil level sensor that shuts down
the engine automatically when the oil level drops below a specified
level. If the engine shuts down by itself and the fuel tank has
enough gasoline, check engine oil level.
2.10.1 SENSING LOW OIL LEVEL
If the system senses a low oil level during operation, the engine
shuts down. The engine will not run until the oil has been refilled
to the proper level.
3.1 MAINTENANCE SCHEDULE
Follow the calendar intervals. More frequent service is required
when operating in adverse conditions noted below.
Check Oil Level At Each Use
Change Oil *Every 100 hours or Every Season
Check Valve Clearance ***Every Season
Service Air Filter ** Every 200 hours or Every Season
Replace Spark Plug Every Season
* Change oil and oil filter every month when operating under heavy load or in high
temperatures.
** Clean more often under dirty or dusty operating conditions. Replace air filter
parts if they cannot be adequately cleaned.
*** Check valve clearance and adjust if necessary after first 50 hours of
operation and every 100 hours thereafter.
3.2 PRODUCT SPECIFICATIONS
3.2.1 GENERATOR SPECIFICATIONS
Rated. Power ..............................................................5.0/5.5/6.5 kW**
Surge Power ...............................................................6.25/6.88/8.0 kW
Rated AC Voltage ......................................................................120/240
Rated AC Load
Current @ 240V (5.0/5.5/6.5 kW) ..................20.8/22.9/27.1 Amps**
Current @ 120V (5.0/5.5/6.5 kW) ..................41.7/45.8/54.2 Amps**
Rated Frequency .................................................... 60 Hz @ 3600 RPM
Phase ................................................................................Single Phase
** Maximum wattage and current are subject to, and limited by, such factors
as fuel Btu content, ambient temperature, altitude, engine condition, etc..
Maximum power decreases about 3.5% for each 1,000 feet above sea level;
and will also decrease about 1% for each 6° C (10° F) above 16° C (60° F)
ambient temperature.
3.2.2 ENGINE SPECIFICATIONS
Displacement .............................................................................. 389 cc
Spark Plug Type ................................NHSP F7RTC or Champion RN9YC
Spark Plug Gap (5.0/6.5 kW) ........0.028-0.031 inch or (0.70-0.80 mm)
Gasoline Capacity ......................................................... 6.6 U.S. gallons
Oil Type.................. See Chart in "Before Starting the Generator" Section
Oil Capacity .................................................................1.1 L (1.16 Qts.)
Class II Emission Certified*
* The engine manufacturer must warrant the emission control system
for a period of two years. This warranty coverage is in addition to
the warranty provided by Generac, and may cover the engine even if
Generac’s warranty does not.
Maintenance
10
3.3 GENERAL RECOMMENDATIONS
The warranty of the generator does not cover items that have been
subjected to operator abuse or negligence. To receive full value
from the warranty, the operator must maintain the generator as
instructed in this manual.
Some adjustments will need to be made periodically to properly
maintain the generator.
All adjustments in the Maintenance section of this manual should
be made at least once each season. Follow the requirements in the
"Maintenance Schedule".
NOTE:
Once a year replace the spark plug and replace the air filter.
A new spark plug and clean air filter assure proper fuel-air
mixture and help the engine run better and last longer.
3.3.1 GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and dry.
Operate and store the unit in a clean dry environment where it will
not be exposed to excessive dust, dirt, moisture or any corrosive
vapors. Cooling air slots in the generator must not become
clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the generator frequently and clean when
dust, dirt, oil, moisture or other foreign substances are visible on
its exterior surface.

Never insert any object or tool through the
air cooling slots, even if the engine is not
running.
NOTE:
DO NOT use a garden hose to clean generator. Water can enter
the engine fuel system and cause problems. In addition, if water
enters the generator through cooling air slots, some water will
be retained in voids and crevices of the rotor and stator winding
insulation. Water and dirt buildup on the generator internal
windings will eventually decrease the insulation resistance of
these windings.
3.3.2 TO CLEAN THE GENERATOR
Use a damp cloth to wipe exterior surfaces clean.
A soft, bristle brush may be used to loosen caked on dirt, oil,
etc.
A vacuum cleaner may be used to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi) may be used to
blow away dirt. Inspect cooling air slots and openings
on the generator. These openings must be kept clean and
unobstructed.
3.3.3 ENGINE MAINTENANCE

When working on the generator, always
disconnect negative cable from battery. Also
disconnect spark plug wires from spark plug
and keep wire away from spark plug.
3.3.4 CHECKING OIL LEVEL
See the “Before Starting the Generator” section for information on
checking the oil level. The oil level should be checked before each
use, or at least every eight hours of operation. Keep the oil level
maintained.
3.3.5 CHANGING THE OIL
Change the oil every 100 hours. If running this unit under dirty or
dusty conditions, or in extremely hot weather, change the oil more
often.

Hot oil may cause burns. Allow engine to
cool before draining oil. Avoid prolonged
or repeated skin exposure with used oil.
Thoroughly wash exposed areas with soap.
NOTE:
Whenever possible, run engine for approximately five (5)
minutes to get the engine oil hot. This will aid in draining the oil.
Use the following instructions to change the oil while the engine
is still warm:
Clean area around oil drain plug.
Remove oil drain plug from engine and oil fill plug to drain oil
completely into a suitable container.
• When oil has completely drained, install oil drain plug and
tighten securely.
Fill oil sump with recommended oil. (See “Before Starting the
Generator” for oil recommendations).
Wipe up any spilled oil.
Dispose of used oil at a proper collection center.
3.3.6 REPLACING THE SPARK PLUG
Use Champion RN9YC spark plug or equivalent. Replace the plug
once each year. This will help the engine start easier and run
better.
1. Stop the engine and pull the spark plug wire off of the spark
plug.
2. Clean the area around the spark plug and remove it from the
cylinder head.
3. Set the spark plug's gap to 0.70-0.80 mm (0.028-0.031 in.).
Install the correctly gapped spark plug into the cylinder head
(Figure 13).
Figure 13 - Spark Plug Gap
Maintenance
11
3.4 SERVICE AIR FILTER
The engine will not run properly and may be damaged if using a
dirty air filter. Clean the air filter every 200 hours or once a year
(Figure 14). Clean or replace more often if operating under dusty
conditions.
Remove air filter cover.
• Wash in soapy water. Squeeze filter dry in clean cloth (DO NOT
TWIST).
Clean air filter cover before re-installing it.
NOTE:
To order a new air filter, please contact the nearest authorized
service center at 1-888-436-3722.
Figure 14 - Air Filter
3.5 VALVE CLEARANCE
Intake — 0.15 ± 0.02mm (cold), (0.006" ± 0.0008" inches)
• Exhaust — 0.0020 ± 0.02mm (cold) (0.008" ± 0.0008"
inches)
After the first 50 hours of operation, check the valve clearance
in the engine and adjust if necessary.
Important: If feeling uncomfortable about doing this procedure or
the proper tools are not available, please take the generator to the
nearest service center to have the valve clearance adjusted. This is
a very important step to insure longest life for the engine.
3.6 GENERAL
The generator should be started at least once every seven days
and be allowed to run at least 30 minutes. If this cannot be done
and the unit must be stored for more than 30 days, use the
following information as a guide to prepare it for storage.
NEVER store engine with fuel in tank indoors
or in enclosed, poorly ventilated areas where
fumes may reach an open flame, spark or
pilot light as on a furnace, water heater,
clothes dryer or other gas appliance.
3.7 LONG TERM STORAGE
It is important to prevent gum deposits from forming in essential
fuel system parts such as the carburetor, fuel hose or tank during
storage. Also, experience indicates that alcohol-blended fuels
(called gasohol, ethanol or methanol) can attract moisture, which
leads to separation and formation of acids during storage. Acidic
gas can damage the fuel system of an engine while in storage.
To avoid engine problems, the fuel system should be emptied
before storage of 30 days or longer, as follows:
Remove all gasoline from the fuel tank.
Drain fuel into approved container outdoors,
away from open flame. Be sure engine is
cool. Do not smoke.
Start and run engine until engine stops from lack of fuel.
While engine is still warm, drain oil from crankcase. Refill with
recommended grade.
Remove spark plugs and pour about 1/2 ounce (15 ml) of
engine oil into the cylinders. Cover spark plug hole with rag.
Pull the recoil starter a couple times to lubricate the piston rings
and cylinder bore..

Avoid spray from spark plug holes when
cranking engine.
Install and tighten spark plugs. Do not connect spark plug wires.
• Clean the generator outer surfaces. Check that cooling air slots
and openings on generator are open and unobstructed.
Store the unit in a clean, dry place.
3.8 OTHER STORAGE TIPS
Do not store gasoline from one season to another.
Replace the gasoline can if it starts to rust. Rust and/or dirt in
the gasoline will cause problems with the carburetor and fuel
system.
• If possible, store the unit indoors and cover it to give protection
from dust and dirt. BE SURE TO EMPTY THE FUEL TANK.
If it is not practical to empty the fuel tank and the unit is to
be stored for some time, use a commercially available fuel
stabilizer added to the gasoline to increase the life of the
gasoline.
Cover the unit with a suitable protective cover that does not
retain moisture.

NEVER cover the generator while engine and
exhaust area are warm.
11
Maintenance
12
4.1 TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
Engine is running, but no AC output
is available.
1. Circuit breaker is open.
2. Poor connection or defective cord set.
3. Connected device is bad.
4. Fault in generator.
1. Reset circuit breaker.
2. Check and repair.
3. Connect another device that is in good condition.
4. Contact Authorized Service Facility.
Engine runs good but bogs down
when loads are connected.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Engine speed is too slow.
4. Shorted generator circuit.
1. Disconnect shorted electrical load.
2. See “Don’t Overload the Generator” .
3. Contact Authorized Service Facility.
4. Contact Authorized Service Facility.
Engine will not start; or starts and
runs rough.
1. Fuel shut-off is OFF.
2. Dirty air filter.
3. Out of gasoline.
4. Stale gasoline.
5. Spark plug wire not connected to spark plug.
6. Bad spark plug.
7. Water in gasoline.
8. Overchoking.
9. Low oil level.
10. Excessive rich fuel mixture.
11. Intake valve stuck open or closed.
12. Engine has lost compression.
1. Turn fuel shut-off ON.
2. Clean or replace air filter.
3. Fill fuel tank.
4. Drain fuel tank and fill with fresh fuel.
5. Connect wire to spark plug.
6. Replace spark plug.
7. Drain fuel tank; fill with fresh fuel.
8. Put choke knob to No Choke position.
9. Fill crankcase to proper level.
10. Contact Authorized Service Facility.
11. Contact Authorized Service Facility.
12. Contact Authorized Service Facility.
Engine shuts down during
operation.
1. Out of gasoline.
2. Low oil level.
3. Fault in engine.
1. Fill fuel tank.
2. Fill crankcase to proper level.
3. Contact Authorized Service Facility.
Engine lacks power. 1. Load is too high.
2. Dirty air filter.
3. Engine needs to be serviced.
1. Reduce load (see “Don’t Overload the Generator”).
2. Clean or replace air filter.
3. Contact Authorized Service Facility.
Engine “hunts” or falters. 1. Choke is opened too soon.
2. Carburetor is running too rich or too lean.
1. Move choke to halfway position until engine runs
smoothly.
2. Contact Authorized Service Facility.
Troubleshooting
Manual Part No. 0H0965 Rev B (04/14/11) Printed in U.S.A.
Warranty
GENERAC POWER SYSTEMS “TWO YEAR” LIMITED WARRANTY FOR
GP SERIES PORTABLE GENERATORS
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants its GP Series generators will be free from defects in
materials and workmanship for the items and period set forth below. Generac will, at its option, repair or replace any part which, upon examination, inspection and
testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective. Any equipment that the purchaser/owner claims to be defective must
be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory,
are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac GP Series portable generators and is not transferable from original
purchaser. Save your proof-of-purchase receipt. If you do not provide proof of the initial purchase date, the manufacturer’s shipping date of the product will be used
to determine the warranty period.
WARRANTY SCHEDULE
Consumer applications are warranted for two (2) years. Commercial and Rental applications are warranted for one (1) year or 1000 hours maximum, whichever comes first.
CONSUMER APPLICATION
YEARS ONE and TWO - 100% (one hundred percent) coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
• Engine- All Components
• Alternator- All Components
COMMERCIAL/RENTAL APPLICATION
YEAR ONE – 100% (one hundred percent) coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
• Engine- All Components
• Alternator- All Components
NOTE: For the purpose of this warranty “consumer use” means personal residential household or recreational use by original purchaser. This warranty does not apply to units
used for Prime Power in place of utility where utility power service is present or where utility power service does not normally exist. Once a generator has experienced
commercial or rental use, it shall thereafter be considered a non-consumer use generator for the purpose of this warranty.
All warranty expense allowances are subject to the conditions defined in Generac’s Warranty Policies, Procedures and Flat Rate Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
Generac built portable generators built prior to May 2008.
Generac portable generators that utilize non-Generac replacement parts.
Costs of normal maintenance and adjustments.
Failures caused by any contaminated fuels, oils or lack of proper oil levels.
Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by Generac Power Systems.
Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper use. As with all mechanical devices, the Generac engines need periodic
part(s) service and replacement to perform as designed. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earth-quake, windstorm, hail,
volcanic eruption, water or flood, tornado or hurricane.
Damage related to rodent and/or insect infestation.
Products that are modified or altered in a manner not authorized by Generac in writing.
Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
Failure due to misapplication.
Telephone, cellular phone, facsimile, internet access or other communication expenses.
Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
Expenses related to “customer instruction” or troubleshooting where no manufacturing defect is found.
Rental equipment used while warranty repairs are being performed.
Overnight freight or special shipping costs for replacement part(s).
Overtime, holiday or emergency labor.
Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Any implied warranties allowed by law shall be limited in duration to the terms of the express warranty
provided herein. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. GENERAC’S ONLY LIABILITY SHALL
BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES,
EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC’S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages,
so the above limitation may not apply to you. This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC POWER SYSTEMS, INC.
P.O. BOX 8 • Waukesha, WI 53187
Ph: (888) GENERAC (436-3722) • Fax: (262) 544-4851
To locate the nearest Authorized Dealer visit our website www.generac.com
Part No. 0G9451 Revision E (05/19/10)
15
www.generac.com o 1-888-436-3722
Manual del propietario
Generadores portátiles serie GP
MODELOS: 005688-0, 005690-0,
005738-0
2 AÑOS
GARANTÍA
LIMITADA
19
ÍNDICE DE ESTÁNDARES
En ausencia de los estándares, códigos, regulaciones o leyes pertinentes,
la información publicada listada abajo puede usarse como guía para
la operación de este equipo. Siempre consulte la revisión más reciente
aplicable para el estándar listado.
1. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC CODE.
2. Article X, NATIONAL BUILDING CODE, disponible en la American
Insurance Association, 85 John Street, New York, N.Y. 10038.
3. AGRICULTURAL WIRING HANDBOOK, disponible en la Food and
Energy Council, 909 University Avenue, Columbia, MO 65201.
4. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF FARM
STANDBY ELECTRICAL SYSTEMS, disponible en la American Society
of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
MODELO Nº:
Nº DE SERIE:
Ubicación del IP de la unidad
CALCOMANÍA
DE DATOS DEL
MODELO
ADVERTENCIA PROPOSICIÓN 65 DE CALIFORNIA
El Estado de California sabe que el escape del motor y algunos
de sus componentes causan cáncer, defectos de
nacimiento y otros daños reproductivos.
ADVERTENCIA PROPOSICIÓN 65 DE CALIFORNIA
Este producto contiene o emite químicos que el Estado
de California sabe que causan cáncer, defectos de
nacimiento u otros daños reproductivos.
Reglas de seguridad
31
www.generac.com ou 1-888-436-3722
Manuel d'entretien
Générateur portable série GP
MODÈLES : 005688-0, 005690-0,
005738-0
GARANTIE
LIMITÉE DE
2 ANS2 ANS
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Generac GP6500 0056900 User manual

Category
Power generators
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI