Greenheck 462105 Support Mullions for use in Oversize Openings Operating instructions

Type
Operating instructions

Greenheck 462105 Support Mullions for use in Oversize Openings are designed to allow for the installation of static fire dampers into vertical openings that are larger than the largest UL rated size for that damper. The mullions enable the construction of a fire barrier that is larger than the maximum available size. They are constructed from steel and are intended for use in concrete block or solid concrete walls. The mullions can be used vertically, horizontally, or both to split up a vertical wall opening requiring the use of a damper having a 11⁄2 hour fire resistance rating.

Greenheck 462105 Support Mullions for use in Oversize Openings are designed to allow for the installation of static fire dampers into vertical openings that are larger than the largest UL rated size for that damper. The mullions enable the construction of a fire barrier that is larger than the maximum available size. They are constructed from steel and are intended for use in concrete block or solid concrete walls. The mullions can be used vertically, horizontally, or both to split up a vertical wall opening requiring the use of a damper having a 11⁄2 hour fire resistance rating.

These installation instructions apply to the fabrication and construction of generic support mullions. Support mullions
are necessary whenever static fire dampers are installed into a vertical opening that is larger than the largest UL
rated size for that damper. The mullions allow construction of a fire barrier that is larger than the maximum available
size.
The opening must not exceed 120 in. (3048mm) high but, can be any width provided a vertical support mullion is
used with a maximum of every 120 inches (3048mm).
To properly use support mullions, they must be fabricated and installed according to the following instructions.
Application
Generic steel mullions can be used to separate vertically mounted galvanized steel fire dampers in wall openings
larger than the UL permitted multiple damper assembly size. Mullions can either be used vertically, horizontally,
or both to split up a vertical wall opening requiring the use of a damper having a 1
1
2 hour fire resistance rating.
Maximum mullion span is 120 in. (3048mm) plus expansion allowance when used either horizontally or vertically.
E
E
F
F
D
D
G
G
G
G
Wall Mullion Cap
B-B (Typical)
Mullion Assembly
A-A (Typical)
Retaining Angles (Typical)
Sleeve (Typical)
Horz. to Vert.
Mullion Cap
C-C (Typical)
Special Note:
Support mullions may only
be used with static-rated fire
damper assemblies; they cannot
be used to install combination
fire smoke dampers in wall
openings that exceed the
maximum UL approved size for
the fire smoke damper model
being installed.
®
462105 Support Mullions 1
®
Document 462105
Fabrication and Field Installation Instructions
for Support Mullions in Oversized Openings
FD Series
Wall Opening
Steel mullions are intended for use in concrete block or
solid concrete wall.
Hollow concrete blocks are to be filled with concrete
(minimum 3,500 psi) to permit proper mullion anchoring.
Wall thickness is to be 7 in. (178mm) minimum, 12 in.
(305mm) maximum.
Support mullion assemblies consist of three basic parts:
the wall mullion cap, the horizontal to vertical mullion
cap, and the mullion sections. Determine the quantity of
each piece required to complete the installation.
Opening Width/
Height
D H
12 (305) 11½ (292) 3¼ (83)
24 (610) 23½ (597) 3
3
8 (86)
36 (914) 33
3
8 (847) 3½ (89)
48 (1219) 47¼ (1200) 3
5
8 (92)
60 (1524) 59
1
8 (1501) 3¾ (95)
72 (1829) 71 (1803) 3
7
8 (98)
84 (2134) 82
7
8 (2105) 4 (102)
96 (2438) 94¾ (2406) 4
1
8 (105)
108 (2743) 106¾ (2711) 4 ¼ (108)
120 (3048) 118¾ (3016) 4
3
8 (111)
Table 1
Dimensional information shown in inches (mm)
E = Wall thickness -
1
2 in. (13mm)
F = Wall thickness +
1
4 in. (6mm)
Fabrication of Wall Mullion Caps
Wall mullion caps must be constructed from 12 ga.
(2.7mm) steel with a minimum yield strength of 42,000
psi.
1. Fabricate the formed section as shown to the
right.
2. Shear the cap end plate to required dimensions.
3. Weld the cap end plates to the formed section
with
1
8 in. (3mm) fillet welds completely around
the top edges of the formed section.
4. Drill and countersink 8 holes (4 on each side) for
1
4-20 flat head machine screws.
Fabrication of Mullion Sections
Mullions must be constructed from 16 ga. (1.5mm) steel
with a minimum yield strength of 42,000 psi.
Important: The “D” dimension shown has been
calculated to include the necessary clearances required
for thermal expansion in the mullions. The values can be
found using the wall opening dimensions and Table 1.
1. Form two identical pieces of mullion section as
shown.
2. Connect the two mullion sections together. Use
3
16 in. (4.7mm) steel blind rivets of
3
4 in. (19mm)
long intermittent welds 12 in. (305mm) on center
and a 6 in. (152mm) maximum from both ends.
Both sides of the mullion piece should be fastened
using the method described below.
2 2C-4
3
3
/
8
3
/
4
7
/
8
3
1
/
2
D
Formed Section View (2 req’d)
C= Wall Thickness
Assembled View
3/16 in. blind rivet (stl) or 3/4 in.
long intermittent welds 12 in. on
center, 6 in. maximum from both
ends, both sides of assembly.
3/16 in. typical
rivet location
Detail A-A
Mullion Assembly
All dimensions shown are in inches.
462105 Support Mullions2
®
Detail B-B
Wall Mullion Cap
H
2 2
1
13
/
16
3
1
/
4
H
E
E/4
E/4
E/4
E/8
3
1
/4
H
E/8
Formed Section
End View
Cap End Plate
(2 req’d)
Weld
Wall Mullion Cap
Assembled View
Fabrication of Horizontal to Vertical
Mullion Caps
Horizontal to vertical mullion caps must be constructed
from 12 ga. (2.7mm) steel with a minimum yield strength
of 42, 000 psi.
Important: The H, E, and F dimensions shown have
been calculated to provide the correct performance.
The values can be found by using the wall opening
dimensions and Table 1.
1. Form the horizontal mullion channel as shown.
2. Drill 12-
3
16 in. (4.7mm) diameter holes into the
horizontal mullion channel using the dimensions
shown.
3. Form the center channel as shown.
Note: If the center channel is to be made from two
pieces, weld them together with an
1
8 in. (3mm) fillet
weld.
4. Shear the end plates to the dimensions required.
5. Weld the end plates to the center channel with
1
8
in. (3mm) fillet welds completely around the top
edges of the center section.
Mullion Installation
Before the static fire dampers are installed into the
wall the mullions must first be anchored into the wall.
The fire dampers may then be installed into the mullion
assembly.
To correctly attach the mullions to the wall, follow these
steps:
1. Anchor wall mullion caps to wall using
1
4-20
x
5
16 in. long flat head steel bolts and
3
8 in.
(9.5mm) diameter by 1 in. (25mm) long concrete
expansion anchors (Hilti). If steel lintels are
present, use two 1 in. (25mm) long welds on
each side of mullion caps.
Note: End caps must be inserted into the ends of the
mullions before they are anchored to the wall.
2. Anchor horizontal mullion caps to vertical mullion
caps with
3
16 in. (4.7mm) diameter steel blind
rivets in 12 places.
Note: Mullion caps must be inserted into the ends of
the mullions before they are anchored to the vertical
mullions or wall.
6
F
3
/16 in. dia.
(12 holes)
1
3
/
4
1
1
/2
3
/
4
1
1
/
2
1
/
2
Horizontal Mullion Channel
End View
Side View
Top View
E
H
3
1
/4
1
13
/16
One or two piece
Side View
End View
End Plate
Center Channel
Weld
1
3
/8
3
/16
Use
3
/16 dia. steel blind
rivets at installation
Weld
Assembled View
1
6
F
3
/16 in. dia.
(12 holes)
1
3
/
4
1
1
/2
3
/
4
1
1
/
2
1
/
2
Horizontal Mullion Channel
End View
Side View
Top View
E
H
3
1
/4
1
13
/16
One or two piece
Side View
End View
End Plate
Center Channel
Weld
1
3
/8
3
/16
Use
3
/16 dia. steel blind
rivets at installation
Weld
Assembled View
1
6
F
3
/16 in. dia.
(12 holes)
1
3
/
4
1
1
/2
3
/
4
1
1
/
2
1
/
2
Horizontal Mullion Channel
End View
Side View
Top View
E
H
3
1
/4
1
13
/16
One or two piece
Side View
End View
End Plate
Center Channel
Weld
1
3
/8
3
/16
Use
3
/
16
dia. steel blin
d
rivets at installation
Weld
Assembled View
1
462105 Support Mullions 3
®
Static Fire Damper Installation
Galvanized steel static fire dampers must be UL
classified for 1
1
2 hour fire resistance. They must be
installed in galvanized steel sleeves and be retained
by minimum 1
1
2 in. x 1
1
2 in. (38mm x 38mm), 16 ga.
(1.5mm) retaining angles on each side of the wall.
Retaining angles must overlap mullions or wall by 1
in. (25mm) minimum. Fasten to the sleeve using
1
4 in.
(6mm) dia. bolts,
3
16 in. (4.7mm) steel rivets, welding,
or #10 sheet metal screws. All must be attached 6
in. (152mm) on centers, 2 in. (51mm) maximum from
corners. Do not fasten retaining to the wall or mullions.
Mullions must be free to float.
Total expansion clearance between sleeve and wall/
mullion of
1
8 in. (3mm) per foot of wall opening or
mullion span should be allowed. Maximum clearance is
1
1
4 inches (31mm).
End Cap
1
/4" Min.
Detail G-G
Wall Thickness
7"min. & 12" max.
Detail F-F
Detail D-D
Retaining
Angles
1" min.
Detail E-E
E
E
F
F
D
D
G
G
G
G
Wall
Sleeve
Sleeve
1 1/2 in. x 1 1/2 in.
min. 16 ga.
galvanized
retaining angle
Mullion
Mullion
Mullion
Mullion Cap
End Cap
1
/4" Min.
Detail G-G
Wall Thickness
7"min. & 12" max.
Detail F-F
Detail D-D
Retaining
Angles
1" min.
Detail E-E
E
E
F
F
D
D
G
G
G
G
Wall
Sleeve
Sleeve
1 1/2 in. x 1 1/2 in.
min. 16 ga.
galvanized
retaining angle
Mullion
Mullion
Mullion
Mullion Cap
Wall Thickness
7"min. & 12" max.
Detail F-F
Mullion
Mullion Cap
End Cap
1
/4" Min.
Detail G-G
Wall Thickness
7"min. & 12" max.
Detail F-F
Detail D-D
Retaining
Angles
1" min.
Detail E-E
E
E
F
F
D
D
G
G
G
G
Wall
Sleeve
Sleeve
1 1/2 in. x 1 1/2 in.
min. 16 ga.
galvanized
retaining angle
Mullion
Mullion
Mullion
Mullion Cap
462105 • Support Mullions, Rev. 8, May 2019 Copyright 2019 © Greenheck Fan Corporation4
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.
Our Commitment
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Greenheck 462105 Support Mullions for use in Oversize Openings Operating instructions

Type
Operating instructions

Greenheck 462105 Support Mullions for use in Oversize Openings are designed to allow for the installation of static fire dampers into vertical openings that are larger than the largest UL rated size for that damper. The mullions enable the construction of a fire barrier that is larger than the maximum available size. They are constructed from steel and are intended for use in concrete block or solid concrete walls. The mullions can be used vertically, horizontally, or both to split up a vertical wall opening requiring the use of a damper having a 11⁄2 hour fire resistance rating.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI