Ever UPS SINLINE RT 1000/1200/2000/3000, UPS SINLINE RT XL 850/1250/1650/2250/3000 User manual

  • Hello, I'm your chat assistant and I've reviewed the EVER instruction manual for SINLINE RT and SINLINE RT XL series UPS units. This document provides comprehensive information on how to use, maintain, and troubleshoot the UPS devices. It covers everything from safety instructions and installation to advanced functions such as network management and battery replacement. I'm ready to answer your questions about the features and functions of the devices described in the manual.
  • Can the UPS unit be used with medical equipment?
    Can I replace the batteries by myself?
    What type of network connection does the UPS use?
    Does the UPS have surge protection?
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
2
CONTENTS
INTRODUCTION .......................................................................................................................................................... 3
GENERAL FEATURES OF THE UPS UNIT ............................................................................................................. 4
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ...................................................................................... 6
TECHNICAL DESCRIPTION.................................................................................................................................... 12
UNPACKING THE PRODUCT..................................................................................................................................... 12
What’s in the box? ................................................................................................................................................ 12
ELEMENTS OF THE UPS - REAR PANEL ................................................................................................................. 13
HOW IT WORKS........................................................................................................................................................... 13
LCD DISPLAY ICONS ................................................................................................................................................. 16
DESCRIPTION OF LCD DISPLAY ICONS ......................................................................................................... 17
USER INTERFACE MENU STRUCTURE .................................................................................................................. 19
DESCRIPTION OF SCREENS SHOWN IN THE LCD DISPLAY .............................................................................. 20
Information screens .............................................................................................................................................. 20
Main menu ............................................................................................................................................................ 23
CONTROL submenu ............................................................................................................................................. 23
CONFIGURATION Submenu ............................................................................................................................... 25
INFORMATIONS submenu ................................................................................................................................... 30
MEASUREMENTS submenu ................................................................................................................................. 31
STATISTICS submenu ........................................................................................................................................... 33
UPS OPERATION MODES .......................................................................................................................................... 35
PROTECTIONS AND SAFEGUARDS ......................................................................................................................... 37
Overload protection .............................................................................................................................................. 37
Short-circuit protection ......................................................................................................................................... 37
Against overvoltage (Anti-surge) .......................................................................................................................... 38
Thermal protection ............................................................................................................................................... 38
EPO (expansion card - optional equipment for SINLINE RT XL UPS units) ....................................................... 38
INSTALLATION .......................................................................................................................................................... 39
INSTALLING THE UPS UNIT ..................................................................................................................................... 39
Input installation ................................................................................................................................................... 40
Output installation ................................................................................................................................................ 41
TOWER VERSION UPS INSTALLATION .................................................................................................................. 42
Installation of the UPS with a battery module (applies to SINLINE RT XL UPS units) ....................................... 43
RACK VERSION UPS INSTALLATION ..................................................................................................................... 46
Installation of the UPS with a battery module (applies to SINLINE RT XL UPS units) ....................................... 48
DISCONNECTING THE BATTERY MODULE (applies to SINLINE RT XL) .......................................................... 50
FIRST START-UP OF THE UPS .................................................................................................................................. 51
STARTING UP THE UPS UNIT (power supply from the mains) ................................................................................. 52
STARTING THE UPS UP FROM THE BATERY (cold start) ..................................................................................... 52
SWITCHING THE UPS OFF ......................................................................................................................................... 53
REPLACING THE UPS UNIT'S INTERNAL BATTERY ...................................................................................... 54
REPLACING THE BATTERY IN THE UPS ................................................................................................................ 55
SINLINE RT 1000 - 1200 and SINLINE RT XL 650 - 850 .................................................................................... 55
SINLINE RT 1600 - 3000 and SINLINE RT XL 1250 - 2250 ................................................................................ 56
SINLINE RT XL 3000 ........................................................................................................................................... 58
REPLACING THE BATTERIES IN THE BATTERY MODULE ................................................................................ 59
COMMUNICATION WITH PC ................................................................................................................................. 62
COMMUNICATION USING USB HID DEVICES ...................................................................................................... 62
SNMP/HTTP NETWORK MANAGEMENT CARD .................................................................................................... 62
EXPANSION CARDS (applies to SINLINE RT XL UPS units) .............................................................................. 63
EPO CARD..................................................................................................................................................................... 63
Installation of the card .......................................................................................................................................... 63
OPERATING INSTRUCTIONS ................................................................................................................................. 65
INTERACTION WITH ELECTRICAL GENERATORS .............................................................................................. 66
STORAGE, MAINTENANCE AND TRANSPORT ..................................................................................................... 66
DISPOSAL ..................................................................................................................................................................... 67
TECHNICAL PARAMETERS - SINLINE RT series ............................................................................................... 69
TECHNICAL PARAMETERS - SINLINE RT XL series ........................................................................................ 71
DIAGNOSTICS OF ERRORS REPORTED BY THE UPS ..................................................................................... 73
LEGAL REGULATIONS AND WARRANTY .......................................................................................................... 75
DECLARATION OF CONFORMITY ........................................................................................................................... 75
WARRANTY ................................................................................................................................................................. 75
EVER UPS SINLINE RT / RT XL series instruction manual
3
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
INTRODUCTION
Thank you for purchasing the EVER SINLINE RT / SINLINE RT XL UPS system. This
UPS unit has been designed and engineered to provide the highest standard of
protection against power failure. We hope that the purchased UPS unit will meet your
expectations.
This manual contains all relevant information to ensure correct and safe operation of
the unit. Please read this manual carefully and thoroughly prior to using the EVER
SINLINE RT / SINLINE RT XL unit. This will help to operate the unit correctly and
safely. The UPS unit has been designed, engineered and manufactured in Poland. Its
design and construction are fully compliant with the CE marking standards.
SINLINE RT / SINLINE RT XL is the newest range of technologically advanced UPS
units designed mainly for computer servers, small computer networks, workstations
and other electrical, electronic ad IT systems. With the universal rack / tower housing,
the UPS orientation can be changed quickly.
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
4
GENERAL FEATURES OF THE UPS UNIT
The SINLINE RT / SINLINE RT XL units are LINE-INTERACTIVE (VI) class units
designed to work with equipment supplied from ~ 230 VAC single-phase electric power
mains. They provide energy for practically any device whose power rating is not greater
than the UPS unit’s power rating.
Alongside their excellent performance and reliability, the SINLINE RT / SINLINE RT
XL range of UPS units offer a number of other advantages:
The universal rack / tower housing, thanks to which the UPS orientation can be
changed quickly. The LCD's rack / tower mode selection is done via software.
Network interface as a default feature (supports SNMPv1 and HTTP) - for remote
management of the UPS unit through SNMPv1 protocol (compatible with
RFC1628) or a website browser.
HID USB communication interface - the UPS can operate with other devices
without the necessity to install software
Firmware that can be updated by the user - as soon as the new version is
available, the user can enjoy its new functionalities.
CDS System (Clear Digital Sinus) - generates a clear sine wave in the unit's
output (in battery mode)
AVR, a system for regulating (increasing and decreasing) the mains voltage - for
adapting incorrect input voltage to a level that is acceptable to the receivers,
without the use of the battery
The LCD display grants the user complete control over the UPS.
The unit's battery charging system with thermal compensation additionally
protects the built-in batteries, prolongs their life and consequently leads to
reduced maintenance costs.
Back-up time prediction - for determining the UPS autonomous operation (in
back-up mode) in real time.
The start-on-battery function allows to start the UPS even if there is no power in
the mains (so-called "cold start").
The battery can be replaced by the user.
EVER UPS SINLINE RT / RT XL series instruction manual
5
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
Moreover, the SINLINE RT XL units have the following features:
Output active power is equal to apparent power (PF=1).
Manageable outputs - customized operation for specific needs of the more
demanding receivers.
LAN filter (1 Gbit/s) for protecting the network card against power surges.
Possibility of connecting a battery module - the back-up time is extended thanks
to the external battery module.
Remote Emergency Power Off (Remote EPO) functionality which interrupts
power supply from the UPS output to loads in extreme situations or emergencies,
such as a fire (optional).
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
6
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General remarks
CAUTION! Before starting the procedures described in this manual,
please read the general safety instructions (including the instructions
found in this document), health & safety information, environmental
protection information and legal regulations that may apply. Always
observe the instructions and recommendations in these documents.
CAUTION! The user is strictly forbidden from performing any repairs, as
this would constitute a health hazard and may result in death. Any repairs
and replacement of batteries should be carried out only by suitably
qualified service technicians with professional licenses required by law.
CAUTION! The unit should be operated and stored in conditions
complying with the requirements set in the specification (technical
documentation).
CAUTION! The device is completely disconnected from the mains only
when the power lead is removed from the mains socket (the plug is
removed from the mains socket).
CAUTION! The unit is equipped with an internal power source (batteries)
or it may operate in combination with a fixed, external source of power
(battery packs). Dangerous voltage may be present at the output
terminal(s), even if the unit has been disconnected from the mains.
CAUTION! The user should place warning labels on all remotely installed
primary isolation switches in order to warn electrical service technicians
that the circuit is powered by a UPS unit. The following (or equivalent) text
should be used on such warning labels:
DISCONNECT THE UPS SYSTEM BEFORE STARTING WORK ON THIS
CIRCUIT.
EVER UPS SINLINE RT / RT XL series instruction manual
7
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
CAUTION! Opening the unit’s casing may result in electric shock.
CAUTION! Do not touch any electrical connectors, terminals and internal
metal elements, unless power supply has been properly disconnected.
CAUTION! All openings and spaces designed to provide access to the
unit's electrical connections must remain covered (with applicable
covers). Failure to observe this requirement may create hazard potentially
resulting in injury or death for persons who touch such connectors. It may
also cause damage to the unit.
CAUTION! In the event of a short circuit, the resulting high current may
cause serious burns or scalds.
CAUTION! There are no user-serviceable parts inside the UPS unit.
CAUTION! SINLINE RT / SINLINE RT XL UPS units are not intended for
use directly with medical equipment, life support systems or equipment
that may affect health.
B) Installation information and requirements
CAUTION! Before installation of the UPS unit, the staff and users must
become familiar with the Health and Safety regulations when working and
handling electrical equipment up to 1 kV voltage.
CAUTION! Before connecting any cables or making any connections
within the UPS unit or in the electrical system, make sure there is no
dangerous voltage on electrical terminals and cables in the system.
CAUTION! The UPS may only be connected to a ~230V mains socket
with a grounding connection (a bolt). The facility's electrical system to
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
8
which the UPS unit is connected must be fitted with overload and short-
circuit protection.
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS
unit's input side, and only TN-S configuration is allowed on the UPS unit's
output side.
CAUTION! No extension cords should be used for connecting the UPS
unit.
CAUTION! Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
Technicians must not work alone in hazardous conditions that may be dangerous
to health and/or life.
Shortly after the UPS unit has been moved from a cold environment to a warm
environment, moisture condensation may appear. The UPS unit must be
completely dry before installation and operation. The acclimatization time should
be at least 2 hours.
UPS units and battery packs must not be installed in humid environment.
UPS units and battery packs must not be installed in places where they would be
exposed to direct sunlight. They must not be installed near sources of heat.
Ventilation openings in the UPS unit casing must not be blocked. Always observe
distances to ventilation openings specified in the manual.
Before connecting the units, is necessary to check the condition of all leads, cables,
connectors, sockets and plugs, as well as that of the unit itself.
The device must be connected to a power circuit (mains socket) with three terminals
(phase, neutral and grounding), including a PE grounding conductor. Failure to
observe this requirement may result in electric shock.
To reduce the risk of electric shock (in case the grounding cannot be checked), the
unit must be disconnected from the mains before installation or connecting to other
equipment. The power lead may only be connected again after making all required
connections.
A device powered through a lead with a plug has a grounding conductor that carries
away the leakage current from the receivers. The leakage currents of all loads
EVER UPS SINLINE RT / RT XL series instruction manual
9
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
connected to the UPS unit's output are combined in the UPS unit's power lead. The
summary leakage current may trigger protective devices (RCD) and result in
disconnecting power to the loads.
When connecting and disconnecting signal cables, all actions should be performed
with one hand only (if feasible). This is to avoid electric shock when touching two
surfaces with different electrical potentials.
Leads connected to the UPS's output should not be longer than 10 m, in order to
maintain conformance with the EMC directive for products sold in Europe.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in
emergency, the UPS unit from the connected loads regardless of the mode in which
the UPS is operating.
To minimize the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least a 3 mm
insulating air gap.
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All these instructions must be executed step by step. If any problems emerge when
executing the instructions given in this document, please contact EVER service
support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the building's
electrical system, as this will disable the UPS unit's protective grounding.
There may be voltage on the UPS's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in the
device's internal batteries).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
WARNING: This is a C2 category UPS. If installed in residential environment, this
product may interfere with radio signals, which may require additional precautions
to be employed by the user.
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
10
D) Maintenance, repair and breakdown information
Dangerously high voltages are present in the UPS unit. Only qualified service
technicians may perform maintenance works.
CAUTION - Risk of electric shock! Even if the unit has been disconnected from the
mains (from terminals of the electrical power supply), parts inside the UPS unit
remain connected to the batteries, which may create hazards. Disconnect the
battery before carrying out any service and/or maintenance works. Make sure there
is no dangerous voltage on the DC circuit internal elements.
WARNING: Only properly authorized and qualified service technicians who have
legally required protection gear may replace batteries.
CAUTION - Risk of electric shock! Dangerous voltage may be present between the
battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
remove jewellery, watches, rings and other metal items,
only use tools with insulated handles.
When replacing batteries, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
Always dispose of used batteries according to relevant instructions.
WARNING: Disposing of batteries in a fire may result in explosion.
WARNING: Opening or damaging batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the mains or power supply system,
always replace broken or blown fuses with fuses of the same type and parameters.
Disconnect the device from the mains before cleaning. Do not use liquid or sprayed
cleaning agents.
UPS units may only be disassembled by suitably qualified service technicians.
EVER UPS SINLINE RT / RT XL series instruction manual
11
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
E) Transport and packaging requirements
Exercise particular care when transporting the device.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable
ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be recharged
at least every 6 months. The recharging procedure must always be recorded and
documented.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the batteries have not been recharged. If this
occurs, contact service support.
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
12
TECHNICAL DESCRIPTION
UNPACKING THE PRODUCT
The UPS unit must be properly examined upon delivery or handover. Although the
product is carefully packaged, the appliance could have been damaged due to shocks
experienced during transport. Should any product damage be discovered, the carrier
or the vendor must be notified immediately, and a protocol must be made, with photos
of the damage.
Keep the packaging for future transportation operations.
CAUTION! The product is supplied with the batteries connected.
CAUTION! Water vapor may condensate on the UPS unit's elements if
packaging is removed from the device in low temperatures. Do not install
the UPS until its interior and housing are completely dry (electric shock
risk).
What’s in the box?
Check carefully the contents of the packaging. The packaging should contain:
- the UPS unit,
- a sticker describing the layout of the unit's rear panel,
- tower type supports (2 pcs) for installing the unit vertically,
- 1 x USB cable,
- a warranty card,
- a quick-start guide book,
Depending on the PSU unit:
- 1 x power cord CEE 7/7 - IEC 320 C13 10 A,
or
- 1 x power cord CEE 7/7 - IEC 320 C19 16 A,
EVER UPS SINLINE RT / RT XL series instruction manual
13
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
ELEMENTS OF THE UPS - REAR PANEL
Figures 1 - 4 present the elements found in rear panels of SINLINE RT / SINLINE RT
XL units.
1. Output sockets
PN-E-93201 (10 A)
2. Output sockets
IEC 320 C13 (10 A):
white - controlled
black - non-controlled
3. Automatic fuse
4. Mains input:
IEC 320 C14 (10 A)
SINLINE RT 1000 1200
SINLINE RT XL 650 - 850
IEC 320 C20 (16 A)
SINLINE RT 1600 3000
SINLINE RT XL 1250 3000
5. Fan
6. Ethernet communication port
7. USB communication port
8. Expansion card compartment
9. Telecommunication filter
10. Output socket
IEC 320 C19 (16 A)
Fig. 1: View of the rear panel of SINLINE RT 1000 - 1200
Fig. 2: View of the rear panel of SINLINE RT XL 650 - 850
Fig. 3: View of the rear panel of SINLINE RT 1600 - 3000
Fig. 4: View of the rear panel of SINLINE RT XL 1250 - 3000
HOW IT WORKS
The PSU unit comes with a graphic LCD display with three, multi-function buttons and
a signal LED. Figure 7 shows the elements of the front panel of SINLINE RT / SINLINE
RT XL units and the description of such elements. Table 1 presents the description of
the buttons of the control panel and Table 2 presents the description of sound and
visual signals informing about the PSU's various operating modes.
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
14
1. Signaling LED
2. LCD display
3. Multi-function buttons: A, B, C
Fig. 5. View of the front panel of SINLINE RT / SINLINE RT XL units
Table 1. Functions of the control panel buttons
Button
Function
Description
A
Switching on
Press and keep the button depressed for over 1 second to switch the unit on
(power supply is switched on).
Switching off
When the UPS is on and the LCD display shows one of the information screens
(screensavers), press and keep the button depressed for over 1 second to
switch the unit off (power supply is switched off).
Access to main
menu
When an information screen is displayed, press the button shortly to enter the
main menu.
Confirming /
canceling the
current setting
When in MENU screen, press the button briefly to select or change the
highlighted option (depending on what option is selected, the button's action is
indicated by an icon shown on the LCD display, next to the button).
When the value edit mode is selected, press the button briefly to change the
active object (edited values or command keys). When in command selection
mode, keep the button depressed to execute the operation assigned to the
object.
B
Switching the unit
on logically
When the UPS is not on logically (not operating in back-up or normal mode),
and the LCD display shows one of the information screens, press and keep
the button depressed for over 1 second to switch the unit on logically (power
supply to receiver's connected to the UPS's output is switched on).
Switching the unit
off logically
When the UPS is on logically (operating in back-up or normal mode), and the
LCD display shows one of the information screens, press and keep the button
depressed for over 1 second to switch the unit off logically (power supply to
receiver's connected to the UPS's output is switched off).
Scrolling up
Press the button shortly to scroll up between information screens.
Press the button shortly to navigate up the menu options.
Navigating to the
beginning of the
submenu
Press and keep the button depressed for over 1 second to navigate to the
beginning of the submenu.
EVER UPS SINLINE RT / RT XL series instruction manual
15
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
Canceling
messages
Press the button to cancel the currently displayed message.
Increasing the value
of parameters
Press the button to increase the value of the edited parameter.
C
Scrolling down
Press the button shortly to scroll down between information screens.
Press the button shortly to navigate down the menu options.
Switching the sound
alarm on/off
Press and keep the button depressed for over 1 second to switch the UPS
unit's sound alarm on/off. The function is only accessible from information
screens.
Navigating to the
end of the submenu
Press and keep the button depressed for over 1 second to navigate to the end
of the submenu.
Decreasing the
value of parameters
Press the button shortly to decrease the value of the edited parameter.
Confirming
messages
Press the button shortly to confirm the currently displayed message.
Table 2. Sound and visual signaling of specific states of the UPS unit
Event
Sound signal
Visual signal
MAINS (normal) mode
No sound signal.
Green LED on.
BACK-UP (battery)
mode
Intermittent signal; frequency increases
proportionally to the level of discharging of the
batteries, until it turns into a continuous
sound. The alarm is only active if activated
(Configuration; Sound signal; Back-up mode)
and if the MUTE function is inactive.
Red LED on.
STANDBY mode
No sound signal
Red LED pulsating (100 ms ON / 5 s
OFF).
INI mode (initialization)
No sound signal
Red and green LED pulsating
intermittently (0.5 ms ON / 0.5 s
OFF).
EMERGENCY mode
Red LED pulsating (100 ms ON / 100 ms OFF) with sound alarm on (the signal is
switched on and off with the LED). The alarm is active even if the MUTE function is
inactive.
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
16
Event
Sound signal
Visual signal
Enforced switching to
STANDBY mode (from
BACK-UP mode)
Red LED pulsating with sound alarm in sequences: dual visual and sound signal / 2.5
s pause. The sound signal is on only if the MUTE function is inactive.
Waiting to reach
minimum load
No sound signal
Green LED pulsating (100 ms ON / 5
s OFF).
Overload
Continuous signal
No visual signal.
Overheating
Continuous signal
No visual signal.
LCD DISPLAY ICONS
The front panel of the UPS unit presents useful information concerning the current
functional state of the UPS unit: the operation mode, input and output parameters
values, load level, alarms and messages.
Figure 6 shows the display. Table 3 presents the description of information icons that
may be shown on the LCD display depending on the UPS unit's operating mode.
Fig. 6: LCD display screen with information icons
EVER UPS SINLINE RT / RT XL series instruction manual
17
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
DESCRIPTION OF LCD DISPLAY ICONS
Table 3. Description of LCD display icons
Symbol
Description
1 UPS output load indicator
Load level signaling. Further segments of the icon light up while the load
increases.
2 LAN connection indicator
Signal confirming that the UPS is connected to LAN and visualization of the
direction of transferred data. Packets sent to the network (icon ), packets
received from the network (icon ).
3 - USB connection indicator
The icon is displayed if the UPS is connected with the PC through USB.
4 - Battery charge level indicator
Battery charge level indicator. Further segments of the icon light up as the
battery charge level increases.
5 - MUTE function indicator
Icon indicating the activation / deactivation of sound signal when the UPS is in
back-up (battery) mode. The UPS alarm states is not muted.
6 GREEN function indicator
Icon activating / deactivating the function of saving energy stored in the batteries.
When the UPS is in back-up (battery) mode and there are no receivers
connected or power consumption is below the threshold value of 30 W, the UPS
will automatically switch off after 15 minutes.
7 UPS operation indicator
The icon is displayed if one of the following operation modes is activated:
EMERGENCY, STOP or READY.
The UPS is on logically, the mains parameters are correct. After the UPS
switches from the STANDBY mode, the unit waits until the battery is charged to
a minimal, required level declared in % (CONFIGURATION; UPS; STB Charge).
The UPS operates in STANDBY mode. The mains voltage fails to satisfy the
correctness criteria, the UPS is on logically.
The UPS operates in back-up (battery) mode - there is no mains power supply
or threshold frequency value or effective value of supply voltage are exceeded.
The UPS operates in mains (normal) mode.
The UPS operates in INIT (initialization) mode.
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
18
8 Messages
AVR system activity signalization (increasing value).
AVR system activity signalization (decreasing value).
Low battery charge level.
The icon is displayed in case of an overload of the UPS.
Battery is used up and must be replaced. In order to replace the battery and to
deactivate the icon, please contact EVER Support Centre.
The icon is displayed if the permissible temperature of the battery or inverter is
exceeded.
There are no messages or they are not shown in graphical form (but are available
from the Messages screen).
9 Alarms
If the icon is activated, the UPS unit's output is overloaded or shorted, or there
is reversed voltage. The detailed description is available from the Alarms screen.
The icon is displayed in case of: internal error, EPO triggering or if the
permissible temperature of the battery or inverter is exceeded. The detailed
description is available from the Alarms screen. If there is an internal error,
please contact the service department.
No alarms.
EVER UPS SINLINE RT / RT XL series instruction manual
19
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
USER INTERFACE MENU STRUCTURE
The menu structure of SINLINE RT / SINLINE RT XL UPS units is show in Fig. 7. All
screens shown on the LCD display are described in further sections of the manual.
Fig. 7: Layout of user interface screens
EVER UPS SINLINE RT / RT XL series instruction manual
2023-11-13 12:17
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
20
DESCRIPTION OF SCREENS SHOWN IN THE LCD DISPLAY
Information screens
Information screens (screensavers) include seven, separate screens (UPS STATUS,
INPUT, OUTPUT, NETWORK CARD, UPS MODE, MESSAGES, ALARMS) that
display useful information about the UPS unit's functional status. After the UPS is
switched on, the LCD display shows a start screen, followed by the default UPS
STATUS screen. Switching between individual screens is done by using the
keys. To go to the main menu from any screensaver press the key. To
go back from the menu to the default UPS STATUS screen press the key.
UPS STATUS
Description: UPS unit's basic parameters
Type: Readout
Parameters:
Load
UPS load level in %
Au.tm.
expected duration of UPS backup operation
BatChrg
battery charge level in %
InVolt
- input voltage value
OutVolt
- output voltage value
OutPower
- value of active output power (consumed by receivers)
Screen:
Thanks to the incorporation of an advanced time calculation algorithm, the unit
can accurately predict the duration of autonomous operation in real time. The
algorithm to calculate expected battery operating time offers the highest precision
when recommended types of batteries are used (for the list of recommended battery
types, please go to www.ever.eu). In case when batteries other than recommended
are used, indications may become imprecise, which means the actual available time
of backup operation may differ from the indicated time (Au.tm).
INPUT
Description: The UPS unit’s input parameters
/