red lion PAXLCL User manual

Type
User manual

This manual is also suitable for

Inside US: +1 (877) 432-9908 Bulletin No. PAXLCL-E
Outside US: +1 (717) 767-6511 Drawing No. LP0567
www.redlion.net Released 2018-01-26
-1-
MODELPAXLCL‐PAXLITECURRENTLOOPMETER
DUAL RANGE, 4 to 20 mA or 10 to 50 mA *
3 1/2-DIGIT, 0.56" (14.2 mm) HIGH RED LED READOUT
24 VDC EXCITATION SUPPLY
WIDE SPAN & OFFSET SCALING RANGE
OVER-RANGE INDICATION
SELECTABLE DECIMAL POINTS
NEMA 4X/IP65 SEALED FRONT BEZEL
OPTIONAL CUSTOM UNITS OVERLAY W/BACKLIGHT
* Also adapts to 0 to 50, 0 to 20, 0 to 10, 1 to 5 mA ranges as well as
bi-polar inputs.
GENERALDESCRIPTION
The features of the PAX Lite Series can be applied to measurement of
process variables. With its high sensitivity and programmability, the PAX
Lite Current Loop Meter can be set up for a wide variety of applications.
The PAXLCL can be used for most current loop meter needs for readout
of pressure, flow, temperature, level and other variables. The meter has
been specifically designed for harsh industrial environments. With NEMA
4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
This allows the PAXLCL to be used in dirty, hostile environments and in
wash-down areas. The 3 1/2-digit bi-polar display (minus sign displayed
when current or voltage is negative) features 0.56" (14.2 mm) high, 7-
segment LEDs for easy reading.
SAFETYSUMMARY
All safety related regulations, local codes and instructions that appear
in the literature or on equipment must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment
connected to it. If equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.
CAUTION: Risk Of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONSIninches(mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
1
2
3
4
5
6
7
8
9
10
3.60 (91.4)
(44.5)
1.75
(96.5)
3.80
1.95
(49.5)
(2.5)
.10
(104.1)
4.10
(44.5)
1.75

mA
C
US LISTED
U
L
R
PROC. CONT. EQ.
E179259
-2-
Bulletin No. PAXLCL-E Released 2018-01-26
Drawing No. LP0567
Ordering Information ................................................................ 2
General Meter Specifications ................................................... 2
Accessories.............................................................................. 2
Installing the Meter ................................................................... 3
Setting the Switches................................................................. 3
Wiring the Meter ....................................................................... 3
Scaling the Meter. .................................................................... 5
Calibrating the Meter................................................................. 6
Applications .............................................................................. 7
TABLEOFCONTENTS
MeterPartNumbers
AccessoriesPartNumbers
PAXL
0
0
CL - Current Loop Meter
CL
MODEL NO. DESCRIPTION PART NUMBER
PAXLBK Units Label Kit Accessory PAXLBK30
ORDERINGINFORMATION
1. DISPLAY: 3 1/2-digit, 0.56" (14.2 mm) high, 7-segment red LED, (-)
minus sign displayed when current or voltage is negative. Decimal
points inserted before 1st, 2nd, or 3rd least significant digits by DIP
switch selection.
2. OVER-RANGE INDICATION: Indicated by blanking 3 least significant
digits.
3. POWER:
AC Power: 85 to 250 VAC, 50/60 HZ, 6 VA
Isolation: 2300 Vrms for 1 min. between input and supply (300 V
working voltage).
4. INPUT SENSITIVITY: (Numerical Readout Change/mA)
260 units/mA @ 4 to 20 mA input
105 units/mA @ 10 to 50 mA input
(max. allowable input current, 170 mA).
5. COMPLIANCE: Voltage drop across input at max. signal current, less
than 600 mV for both 4 to 20 and 10 to 50 mA ranges.
6. INPUT RESISTANCE:
4 to 20 mA - 29.2
10 to 50 mA - 11.8
7. SCALING RANGE:
SPAN: 32 coarse steps (binary progression with 5 DIP switches) Each
step providing approx. 8.125 numerical units/mA/step sensitivity for 4
to 20 mA input and 3.25 units/mA/step for 10 to 50 mA input.
OFFSET: 16 coarse steps (binary progression with 4 DIP switches)
with ± switch to add or subtract offset. Each step adds or subtracts
approximately 175 from the numerical display for a total offset range
of ±2700.
8. LINEARITY: ±(0.05% ±1 digit)
9. READING RATE: 2.5 updated readings / second, nominal.
10.RESPONSE TIME: 1 second to settle for step change.
11. LOW FREQUENCY NOISE REJECTION:
Normal Mode Rejection: 63 dB @ 50/60 Hz
Common Mode Rejection: 100 dB, DC to 50/60 Hz
12. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0° to 60°C
Storage Temperature: -40° to 80°C
Operating and Storage Humidity: 85% max. relative humidity
(non-condensing)
Span Temperature Coeff.: 100 PPM/°C
Offset Temperature Coeff.: 100 PPM/°C
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 30 g.
Altitude: Up to 2000 meters
13. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class B
Safety requirements for electrical equipment for measurement, control,
and laboratory use:
EN 61010-1: General Requirements
EN61010-2-030: Particular Requirements for Testing and Measuring
Circuits
RoHS Compliant
UL Listed: File #E179259
Type 4X Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
14. EXCITATION SUPPLY: 24 VDC @ 50 mA max. Regulated
and isolated.
15. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
16. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Panel gasket and mounting clip included.
17. WEIGHT: 0.65 lbs. (0.24 kg)
GENERALMETERSPECIFICATIONS
ACCESSORIES
UNITSLABELKIT(PAXLBK)
Each meter has a units indicator with backlighting that can be customized using
the Units Label Kit (PAXLBK30). The backlight is controlled by a DIP switch.
-3-
Released 2018-01-26 Bulletin No. PAXLCL-E
Drawing No. LP0567
The meter has switches which must be checked and/or changed prior
to applying power. To access the switch, remove the meter base from the
case by firmly squeezing and pulling back on the side rear finger tabs.
This should lower the latch below the case slot (which is located just in
front of the finger tabs). It is recommended to release the latch on one
side, then start the other side latch.
SetUpDIPSwitches
Two banks of DIP switches are located inside the meter. The 10
position bank of switches are used for calibrating the meter. The values of
these switches are discussed in section 5.0 Calibrating the Meter.
The bank of 4 switches located near the front display are used for the
selection of decimal points and backlight annunciator. Selecting “ON”
position enables the function.
SWITCH FUNCTION
1 Decimal Point 1 (000.0)
2 Decimal Point 2 (00.00)
3 Decimal Point 3 (0.000)
4 Backlight Annunciator for Units Label
Main
Circuit
Board
D.P./ BACKLIGHT
REAR TERMINALS
FRONT DISPLAY
4
3
2
1
ON
OFFSET
SPAN
ON
1
2
3
4
5
6
7
8
9
10
OFFSET
SPAN
1.0INSTALLINGTHEMETER
INSTALLATION
The PAX meets NEMA 4X/IP65 requirements when properly installed.
The unit is intended to be mounted into an enclosed panel. Prepare the
panel cutout to the dimensions shown. Remove the panel latch from the
unit. Slide the panel gasket over the rear of the unit to the back of the
bezel. The unit should be installed fully assembled. Insert the unit into the
panel cutout.
While holding the unit in place, push the panel latch over the rear of the
unit so that the tabs of the panel latch engage in the slots on the case.
The panel latch should be engaged in the farthest forward slot possible.
To achieve a proper seal, tighten the latch screws evenly until the unit is
snug in the panel (Torque to approximately 7 in-lbs [79N-cm]). Do not
over-tighten the screws.
INSTALLATIONENVIRONMENT
The unit should be installed in a location that does not exceed the
maximum operating temperature and provides good air circulation.
Placing the unit near devices that generate excessive heat should be
avoided.
The bezel should be cleaned only with a soft cloth and neutral soap
product. Do NOT use solvents. Continuous exposure to direct sunlight
may accelerate the aging process of the bezel.
PANEL CUT-OUT
LATCHING
TABS
PANEL
LATCH
PANEL
MOUNTING
SCREWS
LATCHING
SLOTS
PANEL
GASKET
BEZEL
PANEL
-.00
(92 )
-.0
+.8
3.62
+.03
(45 )
1.77
-.0
+.5
-.00
+.02
2.0SETTINGTHESWITCHES
3.0WIRINGTHEMETER
WIRINGOVERVIEW
Electrical connections are made via screw-clamp terminals located on
the back of the meter. All conductors should conform to the meter’s
voltage and current ratings. All cabling should conform to appropriate
standards of good installation, local codes and regulations. It is
recommended that power supplied to the meter (AC) be protected by a
fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back
of the meter case against those shown in wiring drawings for proper wire
position. Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead
exposed (stranded wires should be tinned with solder.) Insert the lead
under the correct screw-clamp terminal and tighten until the wire is
secure. (Pull wire to verify tightness.)
-4-
Bulletin No. PAXLCL-E Released 2018-01-26
Drawing No. LP0567
EMCINSTALLATIONGUIDELINES
Although Red Lion Controls Products are designed with a high degree
of immunity to Electromagnetic Interference (EMI), proper installation and
wiring methods must be followed to ensure compatibility in each
application. The type of the electrical noise, source or coupling method
into a unit may be different for various installations. Cable length, routing,
and shield termination are very important and can mean the difference
between a successful or troublesome installation. Listed are some EMI
guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The
shield connection should be made as short as possible. The
connection point for the shield depends somewhat upon the
application. Listed below are the recommended methods of connecting
the shield, in order of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end
where the unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually
when the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with
AC power lines, conductors feeding motors, solenoids, SCR controls,
and heaters, etc. The cables should be run in metal conduit that is
properly grounded. This is especially useful in applications where cable
runs are long and portable two-way radios are used in close proximity
or if the installation is near a commercial radio transmitter. Also, Signal
or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
4. Long cable runs are more susceptible to EMI pickup than short cable
runs.
5. In extremely high EMI environments, the use of external EMI
suppression devices such as Ferrite Suppression Cores for signal and
control cables is effective. The following EMI suppression devices (or
equivalent) are recommended:
Fair-Rite # 0443167251 (RLC part number FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize
radiated and conducted noise (EMI), some type of contact protection
network is normally installed across the load, the contacts or both. The
most effective location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal
oxide varistor (MOV) across an AC inductive load is very effective at
reducing EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a
transistor switch, care must be taken not to exceed the breakdown
voltage of the transistor when the load is switched. One of the most
effective ways is to place a diode across the inductive load. Most
RLC products with solid state outputs have internal zener diode
protection. However external diode protection at the load is always a
good design practice to limit EMI. Although the use of a snubber or
varistor could be used.
RLC part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the
instrument. When a separate input and output common is provided,
they should not be mixed. Therefore a sensor common should NOT be
connected to an output common. This would cause EMI on the
sensitive input common, which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/emi for more information
on EMI guidelines, Safety and CE issues as they relate to Red Lion
Controls products.
3.1POWERWIRING
3.2INPUTWIRING
NOTES
1. When shielded wire leads are used, connect the shield to earth ground at the meter and insulate the other end to avoid contact with machine ground.
2. Never run signal leads in conduit, bundles, or race ways with power conductors. Avoid runs close to contactors, relays, solenoids, transformers, and
other potential sources of electrical noise.
5
4
3
4-20MA
-LOOP
10-50MA
-LOOP
+LOOP
K1
2
1
PAXLCL
4-20MA
XDUCER
EXTERNAL LOOP
POWER SUPPLY
A.C. POWER
(+)
(-)
(+)
4-20mA
POWER SUPPLY
EXTERNAL LOOP
XDUCER
10-50MA
10-50mA
1
2
+LOOP
-LOOP
10-50MA
4-20MA
-LOOP
K1
4
3
5
A.C. POWER
(+)
PAXLCL
(-)
(+)
5
4
3
4-20MA
-LOOP
10-50MA
-LOOP
+LOOP
K1
2
1
PAXLCL
4-20MA
XDUCER
A.C. POWER
(+)
4-20mA
10-50mA
1
2
+LOOP
-LOOP
10-50MA
4-20MA
-LOOP
K1
4
3
5
A.C. POWER
7
(-)
(+)
6
24 VDC
AT 50mA
EXCITATION
SUPPLY
(-)
(-)
7
EXCITATION
SUPPLY
24 VDC
AT 50mA
(+)
6
10-50MA
XDUCER
(-)
(+)
PAXLCL
5
4
3
4-20MA
-LOOP
10-50MA
-LOOP
+LOOP
K1
2
1
PAXLCL
4-20MA
XDUCER
A.C. POWER
(+)
4-20mA
10-50mA
1
2
+LOOP
-LOOP
10-50MA
4-20MA
-LOOP
K1
4
3
5
A.C. POWER
7
(-)
(+)
6
24 VDC
AT 50mA
EXCITATION
SUPPLY
(-)
(-)
7
EXCITATION
SUPPLY
24 VDC
AT 50mA
(+)
6
10-50MA
XDUCER
(-)
(+)
PAXLCL
(+)
EXCITATION
(+)
EXCITATION
2-WIRE, EXTERNAL EXCITATION
2-WIRE, WITH EXCITATION (Series Conn.)
2-WIRE, WITH EXCITATION (Parallel Conn.)
AC Power
Terminal 1: VAC
Terminal 2: VAC
85-250 VAC
-5-
Released 2018-01-26 Bulletin No. PAXLCL-E
Drawing No. LP0567
INPUT CURRENT SIGNAL
17.4 :
RANGE
10-50MA
11.8 :
3
+LOOP
4
(-)
-LOOP
RANGE
4-20MA
(-)
5
-LOOP
K2
5.5K
S6
R
S7
2R
S8
4R
S9
8R
S10
16R
12R
(+)
S5
32R
S1
S4 S3 S2
50R
16R
8R
4R
25R
OFFSET
DIRECTION
SWITCH
(+)
ADD
(-)
SUBTRACT
FINE
OFFSET
ADJUST
25K
R
+V -V
R
CURRENT
SHUNT
RESISTORS
K2
V
II
V
FINE SPAN ADJ.
5K
SPAN=150
SPAN=0
INPUT SIGNAL SCALING CIRCUIT
BUFFER
AMP
SPAN ADJUST
OFFSET ADJUST
A/D
VOLTMETER
CIRCUIT
S3 S2 S1
DIGITAL DISPLAY
DECIMAL
POINT
SWITCHES
DIGITAL VOLTMETER
O
V
1400
700
350
175
2100
1050
525
260
130
mA
S4
SWITCH
ANNUNCIATOR
BACKLIGHT
PAXCL SCHEMATIC
4.0SCALINGTHEMETER
DESCRIPTIONOFOPERATION
The PAX Lite Current Loop Meter consists of a digital volt meter
combined with an analog scaling circuit (shown above). The unit was
designed primarily for use with 4-20 mA and 10-50 mA current loop signal
circuits. However, it can also be adapted to other current ranges, such as
0-50 mA, 0-20 mA, 0-10 mA, and in a great many applications it can be
used even with 0-5 mA and 1-5 mA current loops. In addition, input
current can be reversed in polarity resulting in negative numerical
readout with a minus (-) sign displayed. Input terminals 3 and 4 are
connected in series with 10-50 mA current loops, and Terminal 3 and 5
are series connected with 4-20 mA loops. In either case, the voltage drop
generated across the shunt resistor(s) ranges from approximately 0.12 V
min. (@ 4 or 10 mA) to 0.59 V max. (@ 20 or 50 mA). The buffer amplifier
(K1) conditions and filters the input signal voltage and applies it to the
input of the scaling circuit. The procedure for scaling PAX Lite Current
Loop Meters is simplified by dividing the scaling process into two
separate components, span adjustments and offset adjustments which
are defined in the following discussion.
SPANADJUSTMENTS
Span is defined as the numerical range that the display traverses,
disregarding decimal points, when the input signal current is varied from
minimum (4 or 10 mA) to maximum (20 or 50 mA). For example, if a unit
is to display 25.0 @ 4 mA and 100.0 @ 20 mA, the span is 750 (the
difference between 250 and 1000). Had the minimum display been -25.0
@ 4 mA and +100.0 @ 20 mA, the span would be 1250 (1000 - (-250) =
1250). (Note: the terms “GAIN”, “SCALE”, and “SENSITIVITY” are also
frequently used interchangeably with the term “SPAN.”) The PAX Lite
Current Loop Meter can be set up over
a very wide span range by means of the
coarse DIP switches S6-S10, and the
fine screwdriver adjustment pot, located
at the back cover. The coarse span
switches add parallel input resistors to
the summing amplifier (K2), thereby
increasing its gain, or sensitivity, as
more summing resistors are added.
Effectively, adding more parallel input
resistors, increases the slope of the
transfer curve (at right) and increases
the numerical readout for a given input signal current change. The input
summing resistor values are weighted in a binary progression, so they
can be switched in combinations to give 32 discrete steps of span. The
fine adjust control brackets these coarse steps and can be adjusted to
the exact span needed.
The approximate span contributed by each switch is shown on the rear
label. These values are based on the standard current-loop spans of 4 to
20 mA (16 mA current variation) and 10-50 mA (40 mA current variation).
In other words, if S7 only is turned “ON”, the numerical readout will
display a change approximately 1050 for a current swing of 16 mA (4-20
mA input) or 40 mA (10-50 mA input). If S8 were also turned “ON”, the
numerical readout would swing approximately 1575 (1050 for S7 + 525
for S8) for the same signal current variation. The fine control has a
continuous span range of approximately 0-150.
OFFSETADJUSTMENTS
In the foregoing discussion of span, the transfer curves were shown as
“ZERO-BASED”, i.e., the numerical readout displays “0” when the
signal current goes to zero. With current loop ranges such as 0-5 or 0-10,
or 0-20 mA, and with Bi-Polar (+/-) signals, this is often the desired
condition. However, with 4-20 and 10-50 mA current loops, the minimum
current level of 4 or 10 mA usually
represents the zero level of the
parameter being displayed. There
are also many applications where
the minimum (or zero level)
represents some value that does
not fall on a zero based transfer
curve. To accommodate non-zero
based applications, the PAX Lite
Current Loop Meter has provisions
for offsetting the transfer curve
over a wide range. Essentially,
offset moves the transfer curve up
or down to change its intercept with the numerical readout axis, but it
does not change the slope (SPAN) of the transfer curve. In the PAX Lite
Current Loop Meter, offset is accomplished by adding (or subtracting) a
constant at the input of the summing amplifier (K2). This offset constant is
summed in with a switched binary resistor network and a fine adjust
offset control in a similar manner to that used for span adjustment.
Switches S2-S5 can be turned on in combinations to give 16 different
coarse offset levels. Each switch is labeled to show the approximate
amount of offset contributed when it is turned “ON”. Switch 1 selects the
polarity of the switched-in offset value and allows offsetting the transfer
curve “UP” (adding the offset constant) or “DOWN” (subtracting). The fine
offset control has a numerical readout range of ±100 and brackets all the
coarse switched ranges.turned on in combinations to give 16 different
coarse offset levels. Each switch is labeled to show the approximate
amount of offset contributed when it is turned “ON.” Switch 1 selects the
polarity of the switched-in offset value and allows offsetting the transfer
curve “UP” (adding the offset constant) or “DOWN” (subtracting). The
offset adjust pot has a numerical readout range of +/-100 and brackets all
the coarse switched ranges.
-500
NUMERICAL READOUT
0
4 8 12 16 20
+500
+1000
+1500
+1999
INPUT SIGNAL CURRENT
Span Adjustment
SPAN 525 (S8 ON)
SPAN 2100 (S6 ON)
SPAN 1050 (S7 ON)
-500
+500
0
+1000
+1500
+1999
INPUT SIGNAL CURRENT
+500 OFFSET
NUMERICAL READOUT
4812 16 20
Offset Adjustment
"ZERO BASE" NO OFFSET
-300 OFFSET
-300
OFFSET
+500
OFFSET
-6-
Bulletin No. PAXLCL-E Released 2018-01-26
Drawing No. LP0567
5.0CALIBRATINGTHEMETER
Direct calibration in the signal loop is usually not practical due to the
difficulty in varying the measured parameter and the confusing interaction
that occurs between span and offset adjustments. However, the PAXLCL
can be quickly and easily bench calibrated using a commercially available
current calibrator or the calibration set-up shown below.
CALIBRATIONPROCEDURE
The procedure outlined below minimizes span/offset interaction and
simplifies calibration. In Steps 1 to 4 the unit is “nulled” to zero readout
with zero input signal current. In Steps 5 and 6, the span adjustments are
made to establish the required slope of the transfer curve. Then in Step 7,
the transfer curve is shifted up or down as required by setting the offset
adjustments. In Step 8, the final “tweaking” adjustments are made at
minimum and maximum signal current. Setting the decimal points in Step
9 completes the calibration.
Before calibrating, the READOUT SPAN (Rs) and SWING CURRENT
(Is) must be determined.
WHERE:
Rs =(Max. Numerical Display) - (Min. Numerical Display) (Disregard Decimal
Points)
Is = (Current @ Max. Display) - (Current @ Min. Display)
Example:
Readout is to be 0.00 @ 4 mA and 10.00 @ 20 mA.
READOUT SPAN (Rs) = 1000 - 0 = 1000
SWING CURRENT (Is) = 20 mA - 4 mA = 16
CALIBRATIONSTEPS
1. Power down the meter and remove it from its case. Turn off all offset
and span adjustment switches (S2-S10 down). S1 has no effect when
zeroing and can be in either position.
2. Turn the span control pot. fully counter-clockwise (20 turns max.).
3. Turn on a combination of span adjust switches (6-10) to obtain a total
value closest to (but not greater than) the READOUT SPAN (Rs)
desired (1000 in this example). The following chart gives an
approximate span adjustment value for each switch:
4. Place unit in its case and apply power. Apply zero current. Adjust the
indicator to read zero using the offset adjustment pot.
5. Apply the SWING CURRENT (Is) (16 mA in this example) to the input.
Set the exact READOUT SPAN value (1000) with span adj. pot.
6. Apply zero current to see if the zero value has shifted. If it has, re-zero
with the offset pot, then repeat Step 5.
7. After the span has been adjusted, set the signal voltage to the
minimum level (4 mA in the example). Record the meter reading (in
this example the reading will be 250). Subtract the desired reading at
minimum current value (0 in the example) from the recorded reading
(0-250 = - 250). Power down the meter and remove it from its case. Set
the offset add/subtract switch S1 (subtract = on), and the offset
switches (S2-S5) to obtain a total value closest to (but no more than)
the difference between the desired reading at minimum current value
and the observed reading. The following chart gives an approximate
offset adjustment value for each switch:
Place the meter in its case and apply power. Using the offset adjust
pot, adjust the readout to equal the minimum current value (0 in the
example).
8. Adjust the input signal voltage to its maximum value to see if the proper
readout is obtained (1000 @ 20 mA in the example). If the readout is
slightly off, adjust the span pot to obtain the true reading. Then,
recheck the reading at the minimum input voltage (4 mA) and readjust
the offset pot if necessary. Repeat the maximum and minimum readout
adjustments until the unit displays the proper readout at both extremes.
9. Set decimal points as desired using the three decimal point switches.
The unit can now be installed.
TROUBLES HOOTING
If for any reason you have trouble operating, connecting, or simply
have questions concerning your new unit, contact Red Lion’s technical
support.
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
SWITCH NUMBER SPAN VALUE
6 2100
7 1050
8 525
9 260
10 130
SWITCH NUMBER SPAN VALUE
2 1400
3700
4350
5175
-7-
Released 2018-01-26 Bulletin No. PAXLCL-E
Drawing No. LP0567
6.0APPLICATIONS
Example1:
A PAXLCL is to be calibrated to match a flow transducer whose output
is 10 mA @ 0 GPM and 50 mA @ 1375 GPM.
READOUT SPAN (Rs) = 1375 - 0 = 1375
SWING CURRENT (Is) = 50 mA - 10 mA = 40 mA
ADJUSTMENTS(Refertothetransfercurvebelow)
Null the unit to zero readout @ 0
current per Steps 1 to 4 of the
calibration steps.
Set the coarse and fine span
adjustments to get a readout of
1375 @ 40 mA per Steps 5 and 6.
Note: With the full standard swing
of 40 mA, the coarse span switch
reference markings can be used to
determine settings as follows:
S7 ON (1050) + S9 ON (260) =
1310 Span set with switches.
375 (needed) - 1310 (with SW’s)
= 65 w. fine span adj.
Set offset to readout 0 @ 10 mA per Step 7. Note: The read out
observed when the 10 mA min. current is first applied can be used to
determine the offset switch settings.) In this example the readout will
be (+) 344 when the 10 mA min. current is first applied. Applying -344
offset then reduces the readout to zero @ 10 mA.
Check readout at max. (50 mA) and min. (10 mA) and fine tune
(tweak) as required per Step 8.
Example2(NegativeSlope):
A level measuring device puts out 6 mA when a storage tank is full and
15 mA when the tank is empty. The PAXLCL is to readout 90.0 tons at full
tank and zero when empty.
READOUT SPAN (Rs) = 900 - 0 = 900 (Disregard Decimal Points)
SWING CURRENT (Is) = 6 mA (@ max rdg) - 15 mA (@ min rdg) = -9 mA
In this case, the signal current is reversed [Term 3 (-) with respect to
Term 5 (+)] causing the readout to go “down” (increasingly negative) as
the negative current increases.
ADJUSTMENTS
Null the unit per Steps 1 to 4.
Set slope of transfer curve
with span adjustments to get
readout of -900 @ -9 mA per
Steps 5 and 6.
Move transfer curve up by
applying (+) offset per Step 7
until readout is +900 @ -6 mA.
Check extreme readings per
Step 8, 0 readout @ -15 mA
and +900 readout @ -6 mA.
Set D.P. Switch S1 and replace
unit in case.
Example3Display):
A differential pressure transducer has a range of ±1500 PSI with a 4 to
20 mA output (-1500 @ 4 mA, +1500 @ 20 mA).
READOUT SPAN (Rs) = +1500 - (-1500) = 3000
SWING CURRENT (Is) = 20 mA (max) - 4 mA (min) = 16 mA
Note: Since the display readout is limited to 1999 numerical
indication, the full READOUT SPAN of 3000 cannot be obtained
during zero based span adjustment. However, dividing both the
READOUT SPAN and SWING CURRENT by two, i.e. 1500
readout @ 8 mA, allows the span adjustment to be made for the
proper transfer curve slope.
ADJUSTMENTS
Null the unit per Steps 1 to 4.
Set transfer curve slope with span
adjustments per Steps 5 and 6, to
get a readout of +1500 @ 8 mA.
Apply (-) offset per Step 7 to get a
reading of -1500 @ 4 mA.
Check min. and max. extremes
and tweak if required to get desired
readout @ 4 and 20 mA per Step 8.
SPAN
OFFSET
CURRENT
(-)
4
MA
B
8
MA
20
MA
-1500
NULL
A
(+)
C
READOUT
+1500
D
CHECK
CHECK
D
1375
OFFSET
READOUT
NULL
40
B SPAN
10
50
MA
MA
MA
CURRENT
D
CHECK
C
A
C
A
D
CHECK
READOUT
B
CURRENT
(+)(-)
-15
MA
-9
MA
-6
MA
-900
+900
OFFSET
NULL
SPAN
-8-
Bulletin No. PAXLCL-E Released 2018-01-26
Drawing No. LP0567
LIMITED WARRANTY
(a) Red Lion Controls Inc, (the “Company”) warrants that all Products shall be free from defects in material and
workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at
www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-
STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE
PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR A
PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY
RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE OF
PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a
Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result
of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii) Customer
alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if
Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH
IN PARAGRAPH (a).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

red lion PAXLCL User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI