Unbranded JT4BF Installation guide

Category
Heat pumps
Type
Installation guide
OUTDOOR SPLIT SYSTEM HEAT PUMP 16 SEER
TWO-STAGE, R-410A MODELS
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being able to install
the product according to strict safety guidelines and instructing the customer on how to operate and
maintain the equipment for the life of the product. Safety should always be the deciding factor when
installing this product and using common sense plays an important role as well. Pay attention to all safety
warnings and any other special notes highlighted in the manual. Improper installation of the furnace or
failure to follow safety warnings could result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of
this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please
read all instructions carefully before starting the installation. Return these instructions to the customer’s package
for future reference.
DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
INSTALLATION INSTRUCTIONS
IMPORTANT SAFETY INFORMATION ............... 2
HEAT PUMP INSTALLATION .............................. 3
General Information ............................................ 3
Before You Install the Heat Pump ....................... 3
Locating the Heat Pump ..................................... 3
Packaging Removal ............................................3
Ground Level.......................................................3
Rooftop ............................................................... 3
Connecting Refrigerant Tubing Between the
Indoor & Outdoor Unit ......................................... 4
ELECTRICAL WIRING ......................................... 4
Pre-Electrical Checklist ....................................... 4
Line Voltage ........................................................4
Grounding ........................................................... 5
Thermostat / Low Voltage Connections .............. 5
Comfort Alert
TM
Diagnostics Module ................... 5
24 VAC Power Wiring ........................................ 6
Thermostat Demand Wiring .............................. 6
Interpreting the Diagnostic LED’s .....................6
LED Description ................................................ 6
Outdoor Fan Motor .............................................. 6
Optional Equipment ............................................6
Transformer Upgrade Kit ...................................6
START UP & ADJUSTMENTS ............................ 7
Pre-Start Check List ............................................ 7
Start-Up Procedures ...........................................7
Air Circulation - Indoor Blower .......................... 7
System Cooling ................................................. 7
System Heating (Optional) ................................ 7
Short Cycle Protection ........................................ 7
Defrost Cycle Control .......................................... 7
Defrost Test Procedure
....................................... 8
Anti Short Cycle Timer Test ................................ 8
Heating Mode .................................................... 8
Cooling Mode .................................................... 8
REFRIGERANT CHARGING ............................... 8
Charging the Unit in AC Mode ............................ 9
Charging Charts & Application Notes ................. 9
Figure 4. Charging Chart for 2 Ton Units ...........10
Figure 5. Charging Chart for 3 Ton Units ...........10
Figure 6. Charging Chart for 4 Ton Units ...........11
Figure 7. Charging Chart for 5 Ton Units ...........11
Figure 8. Heat Mode Charging Chart ................ 12
WIRING DIAGRAMS ............................................ 13
Figure 9. W.D. for 2 Ton Models Without
Comfort Alert ...................................... 13
Figure 10. W.D. for 2 Ton Models With
Comfort Alert .................................... 14
Figure 11. W.D. for 3 Ton Models Without
Comfort Alert .................................... 15
Figure 12. W.D. for 3 Ton Models With
Comfort Alert .................................... 16
Figure 13. W.D. for 4 & 5 Ton Models Without
Comfort Alert .................................... 17
Figure 14. W.D. for 4 & 5 Ton Models With
Comfort Alert .................................... 18
COMFORT ALERT TROUBLESHOOTING.......... 19
Table 4. LED Diagnostics .................................. 19
Table 5. Module Wiring Troubleshooting ............ 21
HEAT PUMP MAINTENANCE ............................. 22
REPLACEMENT PARTS ...................................... 22
INSTALLATION / PERFORMANCE CHECKLIST 24
2
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Beforeservicing,disconnectallelectricalpower
to the equipment.
• Whenservicingcontrols,labelallwiresprior
to disconnecting. Reconnect wires correctly.
• Verifyproperoperationafterservicing.
WARNING:
This split system heat pump is shipped charged
with R410A refrigerant and ready for installation.
If repairs make it necessary for evacuation and
charging, it should only be attempted by qualified
trained personnel thoroughly familiar with this
equipment. Under no circumstances should
the owner attempt to install and/or service this
equipment. Failure to comply with this warning
could result in property damage, personal injury,
or death.
CAUTION:
This unit uses R-410A refrigerant. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.
WARNING:
Unless noted otherwise in these instructions,
only factory authorized parts or accessory
kits may be used with this product. Improper
installation, service, adjustment, or maintenance
may cause explosion, fire, electrical shock or
other hazardous conditions which may result in
personal injury or property damage.
Installation of equipment may require brazing
operations. Installer must comply with safety codes
and wear appropriate safety equipment (safety glasses,
work gloves, fire extinguisher, etc.) when performing
brazingoperations.
• Followall precautionsintheliterature,ontags,and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment.
• Usecautionwhenhandlingthisapplianceorremoving
components. Personal injury can occur from sharp
metal edges present in all sheet metal constructed
equipment.
WARNING:
The information listed below and the next page
must be followed during the installation, service,
and operation of this furnace. Failure to follow
safety recommendations could result in possible
damage to the equipment, serious personal
injury or death.
• The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes and
the National Electrical Code (ANSI CI) for special
installation requirements.
• Allelectricalwiringmustbecompletedinaccordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
• Thisequipmentcontainsliquidandgaseousrefrigerant
under high pressure. DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by
qualified trained personnel thoroughly familiar with this
type equipment.
• Fullyannealed,refrigerantgradecoppertubingshould
be used when installing the system. Refrigerant suction
line tubing should be fully insulated.
• Thisunitisdesignedforoutdoorinstallationsonlyand
should be positioned as described on page 3.
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNINGindicatesapotentiallyhazardous
situation that if not avoided, could result in personal injury
or death. CAUTION indicates a potentially hazardous
situation that if not avoided, may result in minor or moderate
injury or property damage.
3
HEAT PUMP INSTALLATION
General Information
Split system heat pumps are designed only for outdoor
rooftop or ground level installations. This unit has been
tested for capacity and efficiency in accordance with
AHRI Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and
createunsafehazards.
Toachieveoptimumperformanceandminimizeequipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain
mechanical skills and tools.
Before You Install the Heat Pump
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to
the indoor unit's installation instructions for installation
details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage
prior to installing the equipment at the job site. Verify
coil fins are straight. If necessary, comb fins to remove
flattened or bent fins. Claims for damage (apparent or
concealed) should be filed immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read
all instructions before installing the unit.
Locating the Heat Pump
• Surveythejobsitetodeterminethebestlocationfor
mounting the outdoor unit.
• Overhead obstructions (Figure 1), poorly ventilated
areas, and areas subject to accumulation of debris
should be avoided.
• Sufcientclearanceforunobstructedairowthroughthe
outdoor coil must be maintained in order to achieve rated
performance. See Figure 1 for minimum clearances to
obstructions.
• Considerationshouldbegiventoavailabilityofelectric
power, service access, noise, and shade.
Packaging Removal
To prevent damage to the tubing onnections, carefully
remove the carton and user’s manual from the equipment.
Discard the shipping carton.
Ground Level
Ground level installations must be located according to
local building codes or ordinances and these requirements:
• Clearancesmustbeinaccordancewiththoseshown
in Figure 1.
• A suitable mounting pad must be provided and be
separate from the building foundation. The pad must
be level and strong enough to support the unit’s weight.
The slab height must be a minimum of 2” (5 cm) above
grade and with adequate drainage. See Figure 1.
Rooftop
• Themethodofmountingshouldbedesignedsothatit
does not overload roof structures or transmit noise to
the interior of the structure. The roof must be structurally
capable of handling the weight of the unit.
• Full perimeter support is required under the unit.
Support must be made of weather resistant materials
and installed prior to unit installation.
• Thesupportmustbebuilttoraisetheunit6"abovethe
roof.
6"
24" for
Service Access
12" See
Note
12"
See Note
DO NOT
OBSTRUCT
TOP OF UNIT
NOTE: Units require full perimeter clearances. Installer must maintain
18” between two units or 12” between single unit and structure.
Building or Structure
2”
48”
Figure 1. Clearance Requirements
4
Connecting Refrigerant Tubing Between
the Indoor & Outdoor Unit
CAUTION:
When servicing, cover or seal openings to
minimize the exposure of the refrigerant system
to air to prevent accumulation of moisture and
other contaminants.
After outdoor and indoor unit placement has been
determined, route refrigerant tubing between the
equipment in accordance with sound installation practices.
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be flowing through the
jointsduringbrazing.Thiswillpreventinternaloxidation
and scaling from occurring.
• Refrigeranttubingshouldberoutedinamannerthat
minimizesthelengthoftubingandthenumberofbends
in the tubing.
• Refrigeranttubingshouldbesupportedinamanner
that the tubing will not vibrate or abrade during system
operation.
• Tubingshouldbekeptcleanofforeigndebrisduring
installation.
• Everyeffortshouldbemadebytheinstallertoensure
that the field installed refrigerant containing components
of the system have been installed in accordance with
these instructions and sound installation practices to
insure reliable system operation and longevity.
The maximum recommended interconnecting
refrigerant line length is 75 feet, and the vertical elevation
difference between the indoor and outdoor sections
should not exceed 20 feet.
• If precise forming of refrigerant lines is required, a
copper tubing bender is recommended. Avoid sharp
bends and contact of the refrigerant lines with metal
surfaces.
• A lter dryer is provided with the unit and must be
installed in the liquid line of the system. If the installation
replaces a system with a filter dryer already present
in the liquid line, the filter dryer must be replaced with
ELECTRICAL WIRING
WARNING:
To avoid risk of electrical shock, personal
injury, or death, disconnect all electrical power
to the unit before performing any maintenance
or service. The unit may have more than one
electrical supply.
Label all wires prior to disconnection when
servicing the unit. Wiring errors can cause
improper and dangerous operation
• Allelectricalconnectionsmustbeincompliancewith
all applicable local codes and ordinances, and with the
current revision of the National Electric Code (ANSI/
NFPA 70).
• ForCanadianinstallationstheelectricalconnections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the
supply source match the specifications on the unit
rating plate.
Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper high and low
voltage wiring.
Verify factory wiring is in accordance with the units
wiring diagram. See Figure 9, (page 13), Figure 10,
(page 14), Figure 11, (page 15), Figure 12, (page
16), Figure 13, (page 17), & Figure 14, (page 18).
Inspect for loose connections.
LineVoltage
• Awiringdiagramislocatedontheinsidecoverofthe
electrical box of the outdoor unit. The installer should
become familiar with the wiring diagram before making
any electrical connections to the outdoor unit.
• An electrical disconnect must be located within
sight of and readily accessible to the unit. This
switch shall be capableofelectrically de-energizing
the outdoor unit.
• Line voltage to the unit should be supplied from a
dedicated branch circuit containing the correct fuse
or circuit breaker for the unit. Incoming field wiring
andminimumsizeofelectricalconductorsandcircuit
protection must be in compliance with information listed
on the outdoor unit data label. Any other wiring methods
must be acceptable to authority having jurisdiction.
Table 1. Copper Wire Size
COPPER WIRE SIZE — AWG
(1%VOLTAGEDROP)
SUPPLY WIRE LENGTH-FEET
SUPPLY CIRCUIT
AMPACITY
200 150 100 50
6 8 10 14 15
4 6 8 12 20
4 6 8 10 25
4 4 6 10 30
3 4 6 8 35
3 4 6 8 40
2 3 4 6 45
2 3 4 6 50
2 3 4 6 55
1 2 3 4 60
WireSizebasedonN.E.C.for60°typecopperconductors.
the one supplied with the unit. The filter dryer must be
installed in strict accordance with the manufacturer’s
installation instructions.
• Optionalequipmentsuchasliquidlinesolenoidvalves,
low ambient, etc., should be installed in strict accordance
with the manufacturer’s installation instructions.
5
Figure 2. Typical 2 - Stage Heat Pump w/ Optional
OutdoorThermostatandVariableSpeedAirHandler
GRW2 CEOY1
Thermostat
OD
Stat
O
Y1
R
C
Air Handler
Heat Pump OD
Section
W
2
E
W2
W1
O
Y/Y2
G
R
C
Y2
Y2
W1
W3
Y1
NOTE: Jumper
W1 & W2 together
for shorter staging
time.
• Theoutdoorunitrequiresbothpowerandcontrolcircuit
electrical connections. Refer to the wiring diagrams for
identification and location of outdoor unit field wiring
interfaces. Make all electrical connections in accordance
with all applicable codes and ordinances.
• Overcurrentprotectionmustbeprovidedatthebranch
circuitdistributionpanelandsizedasshownontheunit
rating label and according to applicable local codes.
See the unit rating plate for minimum circuit ampacity
and maximum overcurrent protection limits.
• Providepowersupplyfortheunitinaccordancewiththe
unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment.
• Useonlycopperwireforthelinevoltagepowersupply
to this unit as listed in Table 1, (page 4). Use proper
code agency listed conduit and a conduit connector
for connecting the supply wires to the unit. Use of rain
tight conduit is recommended.
• 208/230Voltunitsareshippedfromthefactorywired
for 230 volt operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
• Optionalequipmentrequiringconnectiontothepower
or control circuits must be wired in strict accordance
of the NEC (ANSI/NFPA 70), applicable local codes,
and the instructions provided with the equipment.
Table 2. Thermostat Wire Gauge
THERMOSTAT
WIRE GAUGE
MAXIMUM RECOMMENDED
THERMOSTATWIRELENGTH(FT)
24 25
22 45
20 70
18 110
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box for grounding the unit.
Thermostat/LowVoltageConnections
• Thermostatconnectionsshouldbemadeinaccordance
with the instructions supplied with the thermostat and
the indoor equipment. A typical installation with a heat
pump thermostat and air handler is shown in Figure 2.
• Theoutdoorunitisdesignedtooperatefroma24VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having
jurisdiction.
• Thelowvoltagewiresmustbeproperlyconnectedto
the units low voltage terminal block. Recommended
wire gauge and wire lengths for typical thermostat
connections are listed in Table 2.
• The thermostat should be mounted about 5 feet
above the floor on an inside wall. DO NOT install the
thermostat on an outside wall or any other location
where its operation may be adversely affected by radiant
heat from fireplaces, sunlight, or lighting fixtures, and
convective heat from warm air registers or electrical
appliances. Refer to the thermostat manufacturer’s
instruction sheet for detailed mounting and installation
information.
Comfort Alert
TM
Diagnostics Module
(Select Models Only)
The Comfort Alert
TM
Diagnostics Module; shown in
Figure 3, (page 6), is a breakthrough innovation for
troubleshooting heat pump and air conditioning system
failures. The module installs easily in the electrical box
of the outdoor unit near the compressor contactor. By
monitoringandanalyzingdatafromtheCopelandscroll
compressor and the thermostat demand, the module can
accurately detect the cause of electrical and system related
failures without any sensors. A flashing LED indicator
communicates the ALERT code and a diagnostic key is
also imprinted on the side of the module to quickly direct
the technician to the root cause of a problem. NOTE: This
module does not provide safety protection! The Comfort
Alert
TM
Diagnostics Module is a monitoring device and
cannot control or shut down other devices.
6
24 VAC Power Wiring
The Comfort Alert
TM
module requires a constant nominal
24 VAC power supply. The module cannot be powered by
the C terminal on a defrost board or other control board
without experiencing nuisance alerts. NOTE: The wiring
to the module’s R & C terminals must be routed directly
from the indoor unit or thermostat.
If the constant 24 VAC (R wire) is not present in the outdoor
unit, use one of the spare wires in the thermostat cable to
bring power to the module. Connect the other end of the
spare wire to R at the indoor unit or thermostat.
Thermostat Demand Wiring
The Comfort Alert
TM
module requires a thermostat demand
signal to operate properly. The thermostat demand
signal input (labeled Y on the module), should always be
connected to the compressor contactor coil. NOTE: When
thecoilisenergized,thedemandsignalinputis24VAC.
Whenthecoilisnotenergized,thedemandsignalinput
should be less than 0.5 VAC.
NOTES:
• Factory installed modules have different thermostat
demand signal wiring. Always follow manufacturer
wiring instructions when replacing the module.
• Afterthethermostatdemandsignalisconnected,verify
that 24 VAC across Y & C when demand is present.
Interpreting the Diagnostic LED’s
When an abnormal system condition occurs, the Comfort
Alert
TM
module displays the appropriate ALERT and/or
TRIP LED will flash a number of times consecutively,
pause and then repeat the process. To identify a Flash
Code number, count the number of consecutive flashes.
Each time the module powers up, the last ALERT Flash
Code that occurred prior to shut down is displayed for
one minute. The module will continue to display the LED
until the condition returns to normal or if 24 VAC power
is removed from the module. See Table 4, (page 19)
for flash code identification or Table 5, (page 21) for
module wiring troubleshooting.
LED Description
• POWERLED(Green):indicatesvoltageispresentat
the power connection of the module.
• ALERT LED (Yellow): communicates an abnormal
system condition through a unique flash code.
NOTE: The ALERT LED will flash consecutively, pause
and then repeat the process. The number of consecutive
flashes, referred to as the Flash Code, correlates to a
particular abnormal condition. Detailed descriptions of
these ALERT Flash Codes are listed in Table 4.
• TRIPLED(Red):indicatesademandsignalisreceived
from the thermostat, but current to the compressor is
not detected by the module. The TRIP LED typically
indicates if the compressor protector is open or the
compressor has no power.
The scroll compressor’s R (run), C (common), and S
(start) wires are routed through the holes in the Comfort
Alert
TM
module marked R, C, & S. NOTE: The common
wire does not need to be routed through the module for
it to operate.
Outdoor Fan Motor
Iftheunitutilizesa2-speedcondenserfanmotor,this
motor will operate on low speed when in low cooling,
and on high speed when in high cooling. A relay within
the control area switches the fan motor from low to high
speed using the call for high cooling as the trigger. Other
modelsthatutilizeBLDCxedtorquevariablespeedfan
motors will not require a relay.
Optional Equipment
Optional equipment requiring connection to the power
or control circuits must be wired in strict accordance
with current provisions of the NEC (ANSI/NFPA 70),
with applicable local codes having jurisdiction, and the
installation instructions provided with the equipment.
Optional Equipment (low ambient control, hard start
kits, etc.) should be installed in strict accordance with
the manufacturer’s installation instructions. A functional
checkout should be performed in accordance with the
checkout procedures supplied with the equipment.
Transformer Upgrade Kit
If this 2-stage heat pump is installed in conjunction with
a gas furnace and fossil fuel kit, the furnace transformer
MUST be upgraded to one with a 60 VA rating or using
the transformer upgrade kit (904077). To upgrade the
transformer:
• Removetheexistingtransformerandinstallthenew
60 VA transformer.
• Removethe3ampfuseonthefurnacecontrolboard
and install the 5 amp fuse provided.
NOTE: The new transformer may be larger than the
existing transformer that is mounted in the furnace. If this
happens, mount the 60 VA transformer using one of the
mounting holes in the furnace panel. On the other side
either drill a 0.149 hole in the panel and use the existing
fastener, or use a self-drilling fastener to secure the other
side of the transformer.
Figure 3. Comfort Alert
TM
Diagnostics Module
POWER LED
(Green)
TRIP LED
(Red)
ALERT LED
(Yellow)
Diagnostics
Key
7
System Heating (Optional)
1. If heating equipment (furnace, air handler) is provided
with the system, lower the thermostat setpoint
temperature to the lowest temperature setting and
change the thermostat’s system mode to HEAT.
2. Gradually increase the thermostat’s setpoint
temperature to the maximum setting.
3. Verify the optional heating equipment (furnace or
electricheat)andindoorblowerenergize.Feeltheair
being circulated by the indoor blower and verify that
it is warmer than ambient temperature. Listen for any
unusual noises. If unusual sounds occur, determine the
source of the noise and correct as necessary.
NOTE: Other sources for heating (electric furnace, fossil
fuel furnace, air handler with electric heat options, etc.)
that interface with the heat pump should be functionally
checked to verify system operation and compatibility
with the heat pump. Refer to the installation instructions
for this equipment and perform a functional checkout in
accordance with the manufacturer’s instructions.
Short Cycle Protection
1. With the system operating in COOLING mode, record
the setpoint temperature setting of the thermostat.
2. Gradually raise the setpoint temperature until the outdoor
unitandindoorblowerde-energize.
3. Immediately lower the setpoint temperature of the
thermostat to its original setting and verify that the
indoorblowerisenergizedand thatthe outdoorunit
remainsde-energized.
4. After approximately 3 minutes, verify that the outdoor
unitenergizesandthetemperatureoftheairsupplied
to the facility is cooler than ambient temperature.
Defrost Cycle Control
The defrost cycle is controlled by an Adaptive Demand
Defrost algorithm that monitors coil temperature and
ambient temperature. Other features of the of the demand
defrost board include:
• 4 Field selectable defrost termination temperatures
(50°F-80°Fcoiltemperature).
• Fieldselectablecompressordelayfeature.
• Highpressureandlowpressureswitches.
• Sensingofsecondstagecompressordemand.
• Test/speedupcapability.
• Anti short cycle timer (3 minutes) for compressor
protection.
• On board diagnostics with ashing LED for quicker
troubleshooting. See Table 3, (page 8).
Control is uncalibrated when power is applied. Calibration
occurs after a defrost cycle. The control initiates this
sacrificial defrost after 34 minutes of accumulated
compressor run time in heating with coil temperature
below35°F.Thedefrostcycleterminatesifcoilsensor
reaches selected termination temperature or after 14
minutes defrost.
Defrost function is disabled if coil temperature is above
35°F.IfAmbientsensorisdetectedasopenorshorted,
demand defrost will not operate and control will revert
to time/temperature defrost operation. If the outdoor coil
START UP & ADJUSTMENTS
Pre-Start Check List
Verify the unit is level and has sufficient clearances for
unobstructed airflow.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/
control panels are in place.
Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
Verify that the low voltage wires are securely connected
to the correct leads on the low voltage terminal strip.
Verify that the power supply branch circuit overcurrent
protectionissizedproperly.
Verify that the thermostat is wired correctly.
Start-Up Procedures
WARNING:
This unit is equipped with a crankcase heater.
Allow 24 hours prior to continuing the start up
procedures to allow for heating of the refrigerant
compressor crankcase. Failure to comply may
result in damage and could cause premature
failure of the system. This warning should be
followed at initial start up and any time the power
has been removed for 12 hours or longer.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan
mode to ON.
2. Verify the blower runs continuously. Check the air delivery
at the supply registers and adjust register openings for
balanced air distribution. If insufficient air is detected,
examine ductwork for leaks or obstructions.
3. Set the thermostat fan mode to AUTO and verify the
blower stops running.
System Cooling
1. Set the thermostat’s system mode to COOL and the
fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and
verifytheoutdoorunitandindoorblowerenergize.
2. Verify blower wheel is spinning in direction indicated by
arrow. Feel the air being circulated by the indoor blower
and verify that it is cooler than ambient temperature.
Listen for any unusual noises. If unusual sounds occur,
determine the source of the noise and correct as
necessary.
3. Verify HI and LO refrigerant pressures.
NOTE: If refrigerant pressures are abnormal and the
compressor is rotating backwards, shut off main power to
the unit and switch any two field wires at the disconnect.
DO NOT alter unit wiring.
4. Allow the system to operate for several minutes and then
set the temperature selector above room temperature.
Verify the fan and compressor cycle off with the
thermostat. NOTE: The blower should also stop unless
fan switch is set to the ON position.
8
sensor is detected as open or shorted, the control will not
perform demand or time/temperature defrost operation.
NOTE: When the defrost cycle initiates, there will be a
30 second compressor delay going into and out of the
defrost cycle. This delay may be removed by removing
P6 connector on the board.
This 2-stage unit will defrost in second stage regardless
of the stage called for by the thermostat.
NOTE: All units are shipped from the factory with the
defaultterminationtemperaturesetat70°F.
Defrost Test Procedure
1. Terminals R - C must have 18-30VAC present between
them in order for defrost sequences to be initiated.
2 With heat mode thermostat demand (Y connected to
R), short and hold the TEST pins together. This will
energize reversing valve to initiate a forced defrost.
NOTE: This will bypass the ASCD and allow the high
stage compressor to come on immediately (if the
REMOVE FOR NO DELAY jumper at P6 is removed). If
the REMOVE FOR NO DELAY jumper at P6 is installed,
thecompressorwillenergizeimmediatelyfollowinga
30-second delay.
3. Remove the short on the TEST pins.
• If the Coil temperature is above the Terminate
Temperature selection setting, the defrost cycle will
beterminated(reversingvalvewillde-energized).
• If the coil temperature is below the Terminate
Temperature election setting, the defrost cycle will
continue for 14 minutes or until the coil temperature
rises above the Terminate Temperature selection
setting. NOTE: Short the TEST pins for 1 second
or more to force the control out of defrost and back
to heating mode (reversing valve de-energized).
Compressor will turn on immediately (if the REMOVE
FOR NO DELAY jumper is removed).
• IftheREMOVEFORNODELAYjumperisinstalled,
thecompressorwillenergizeimmediatelyfollowing
a 30-second delay.
NOTE:IftheY2thermostatinputisenergized(2-stage
system), the second stage will turn on. If the steps above
do not initiate a defrost, replace the defrost board.
Anti Short Cycle Timer Test
The 3-minute time delay feature can be bypassed by
shorting the TEST pins together.
Heating Mode
When the TEST pins are shorted together for more than
1-second, the control will switch between defrost mode
and heating mode (as described in the Defrost Test
Procedure section).
Cooling Mode
When the TEST pins are shorted together for more than
1-second, the Anti Short Cycle Timer will be bypassed.
REFRIGERANT CHARGING
WARNING:
This split system heat pump is shipped charged
with R410A refrigerant and ready for installation.
If repairs make it necessary for evacuation and
charging, it should only be attempted by qualified
trained personnel thoroughly familiar with this
equipment. Under no circumstances should
the owner attempt to install and/or service this
equipment. Failure to comply with this warning
could result in property damage, personal injury,
or death.
After refrigerant line connections are completed, it is
required that you leak check and evacuate the indoor
section and all line connections (using proper methods)
beforenalizingthefullsystemrefrigerantcharge.
• Toachieveratedcapacityandefciency,thecompressor
must be exposed to refrigerant for at least 24 hours
prior to running and then the compressor must be run
for a minimum of 12 hours.
• Therefrigerantchargecanbecheckedandadjusted
through the service ports provided external to the
outdoor unit. Use only gage line sets which have a
“Schrader” depression device present to actuate the
valve. A common suction port for heating mode charging
is included and located on the compressor access panel
above the outdoor unit service valves.
• Figure 8, (page 12) is provided for quick reference
when the unit is in heating mode and for the inspection
of the liquid line pressures and temperatures.
• A high-pressure switch is factory installed and located
internally on the compressor discharge line of the
outdoor unit. If the discharge pressure rises above 650
psig,theswitchwillopenandde-energizetheoutdoor
unit. The switch will close again after the discharge
pressure decreases to 460 psig. NOTE: When the
switch opens and then closes, there will be a 3 minute
shortcyclingdelaybeforetheoutdoorunitwillenergize.
Under normal conditions the switch is closed
• A low-pressure switch is factory installed and located
internally on the suction line of the outdoor unit. The
switch is designed to protect the compressor from a
loss of charge by interrupting the thermostat inputs to
the unit.
DIAGNOSTIC DESCRIPTION
LED
STATUS
Control Fault (No Power) Off
Normal Operation On
ASCD Delay Active (with compressor demand) 1 Flash
Low Pressure Switch Lockout 2 Flashes
High Pressure Switch Lockout 3 Flashes
Ambient Sensor Fault 4 Flashes
Coil Sensor Fault 5 Flashes
Low Pressure Switch Open 6 Flashes
High Pressure Switch Open 7 Flashes
Table 3. Control Diagnostic
9
Charging Charts & Application Notes
• This equipment’s cooling system contains
refrigerant under high pressure. Always use safe
and environmentally sound methods when handling
refrigerant handling or servicing the unit. Review
the factory literature and safety warnings prior to
servicing.
• Cooling mode charging charts are applicable only
to matched assemblies of this equipment and listed
airflows for the indoor coil. Outdoor units with non-
AHRI lsited indoor coils are not recommended and
deviations from rated airflows or non-listed combinations
may require modification to the expansion device and
refrigerant charging procedures for proper and efficient
system operation. Refer to Figure 4, (page 10), Figure
5, (page 10), Figure 6, (page 11) & Figure 7, (page
11) for correct system charging.
• Whenrepairingsystemleaks,alwaysuseanitrogen
(inert) gas to protect the refrigerant system and pressure
check the repair before re-charging. Always replace
the filter-dryers when performing any repair to the
refrigeration system with one capable of acid removal.
After completing the repairs, evacuate the system to
350 - 500 microns and weigh in the refrigerant to the
amount specified on the unit rating label.
• Chargingchartsarevalidforavarietyofindoor,return
air conditions and are most influenced by the outdoor
ambient temperature, outdoor fan operation and the
unit operating voltage. Before using these charts, make
sure the unit is in a stable operating mode.
• AsshowninFigure 4, Figure 5, Figure 6 & Figure 7 the
ideal system sub-cooling can vary over the range of
operation. Reference the charts to determine the ideal
amount of sub-cooling for a given liquid pressure. Units
charged to other values will not perform at the rated unit
efficiency (EER) or rated Coefficient of Performance
(COP) in heating mode.
To inspect a systems operation using quality
instruments, match the measured liquid temperature to
the units chart. The measured liquid pressure reading
should be within 3% of the charts value for most
installations.
• Forsystemsthatareoperatingwithmorethana5%
deviation, inspect the unit for the proper voltage and
phase balance and the refrigeration system for leaks.
• Unitsthatareoperatingatlessthen95%ofthenominal
voltage or with a 2% phase imbalance may see a more
significant deviation than the amount stated above.
• DO NOT use the charts in systems that have a fan cycling
under low-ambient control. Refer to the low-ambient kit
instructions for more information. (If applicable)
• Ifthesuctionpressurefallsbelow5psig,theswitchwill
openandde-energizetheoutdoorunit.Theswitchwill
close again when the suction pressure increases above
20 psig. When the switch opens and then closes, there
is a 3 minute short cycling delay before the outdoor
unitwillenergize.Undernormalconditionstheswitch
is closed.
To properly charge these units:
1. Read all Installation Instructions first.
2.Complete any brazing operations. (e.g. Split system
line-sets)
3. Leak check and evacuate the whole system using proper
methods.
4. Purge the nitrogen holding charge.
5. Evacuate the unit to 350-500 microns.
6. Allow the unit to remain under vacuum for at least 30
min.
7. Weigh-In the proper amount of new (or reclaimed)
R-410A refrigerant. Refer to the units Quick Reference
Data Sheet to determine the correct amount of charge.
Charging the Unit in AC Mode
(At outdoor temperatures above 55° F for
optimized sub-cooling of 10° F - 12° F.)
1. With the system operating at steady-state, measure the
liquid refrigerant pressure (in psig) at the outdoor unit
service valve.
2. Measure the liquid refrigerant temperature (in
Fahrenheit) at the service valve.
3. Determine the required liquid refrigerant pressure. See
Figure 3, Figure 4, Figure 5, & Figure 6.
• IfthepressuremeasuredinStep1isgreaterthan
the required liquid refrigerant pressure determined in
Step 3, then there is too much charge in the system.
Remove refrigerant and repeat Steps 1 through 3
until the system is correctly charged.
• IfthepressuremeasuredinStep1islessthanthe
required liquid refrigerant pressure determined in
Step 3, there is too little charge in the system. Add
refrigerant and repeat Steps 1 through 3 until the
system is correctly charged.
10
Figure 4. Charging Chart for 2 Ton Units
250
275
300
325
350
375
400
425
450
475
70 75 80 85 90 95 100105 110 115 120 125
Liquid Temperature (° F)
Liquid Pressure (psig)
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 5. Charging Chart for 3 Ton Units
Liquid Temperature (° F)
Liquid Pressure (psig)
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105110 115 120 125
Remove refrigerant when above curve
Add refrigerant when below curve
11
Figure 6. Charging Chart for 4 Ton Units
Liquid Temperature (° F)
Liquid Pressure (psig)
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105 110 115120 125
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 7. Charging Chart for 5 Ton Units
Liquid Temperature (° F)
Liquid Pressure (psig)
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105 110 115120 125
Remove refrigerant when above curve
Add refrigerant when below curve
12
Figure 8. Heat Mode Charging Chart
Liquid Temperature (° F)
Liquid Pressure (psig)
200
225
250
275
300
325
350
375
400
50 55 60 65 70 75 80 85 90
Remove refrigerant when above curve
Add refrigerant when below curve
13
WIRING DIAGRAMS
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2 IN
L
COIL
C
Y
O
R
AMBDF1DF2
RV
OUTDOOR
FAN MOTOR
T1 T2
L1
L2
RIGHT
COMPRESSOR
HPS
LPS
RV COIL
C
R
S
CCH
BLACK
YELLOW
RED
C
H
C
TO THERMOSTAT
AMB SENSOR
OD SENSOR
CAPACITOR
CONTACTOR
LEFT
DEFROST BOARD
C
GRND L1 L2
SINGLE PHASE
FIELD SUPPLY
GROUNDING
SCREW
F
BLACK
ORANGE
S
R
BLUE
C
S
R
H
C
F
208/230V .zH 06 / esahP egniSrotoM naF CSP dna tsorfeD dnameD htiW )noitceS roodtuO( pmuP taeH metsyS tilpS egatS owT
WIRING DIAGRAM
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 deg C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler
installation instructions for control circuit and optional
relay/transformer kits.
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
711120A
0713
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
BLACK
BLACK
YELLOW
YELLOW
YELLOW
BLACK
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2
IN
L
COIL
C
Y
O
R
AMBDF1DF2
RV
DEFROST BOARD
RV COIL
LPS
HPS
R
S
C
CCH
L2
L1
T2
T1
OUTDOOR
FAN MOTOR
COMPRESSOR
CAPACITOR
CC
Y
R
O
C
W2
Y2
L
CSC
AMB
SENSOR
COIL
SENSOR
208/230V
CC- Contactor Coil
CCH - Crankcase Heater
CSC - Compressor Solenoid Coil
LPS - Low Pressure Switch
HPS - High Pressure Switch
RVS - Reversing Valve Solenoid
Figure 9. W.D. for 2 Ton Models Without Comfort Alert
14
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2 IN
L
COIL
C
Y
O
R
AMBDF1 DF2
RV
OUTDOOR
FAN MOTOR
Y2
Y
L
R
C
DC SOL
COMFORT
ALERT MODULE
COMPRESSOR
HPS
LPS
RV COIL
CCH
TO THERMOSTAT
AMB SENSOR
OD SENSOR
CONTACTOR
T1 T2
L1 L2
LEFT
RIGHT
DEFROST BOARD
RED
BLACK
YELLOW
GRND
GROUNDING
SCREW
L1
L2
ROUTE THIS WIRE
THROUGH THE “R”
OPENING IN COMFORT
ALERT MODULE
ROUTE THIS WIRE
THROUGH THE “C”
OPENING IN
COMFORT ALERT
MODULE
ROUTE THIS WIRE
THROUGH THE “S”
OPENING IN
COMFORT ALERT
MODULE
C
R
S
C
CAPACITOR
SINGLE PHASE FIELD SUPPLY
C
R
S
H
C
F
BLACK
ORANGE
BLUE
BLACK
YELLOW
YELLOW
BLACK
BLUE
YELLOW
BLACK
RED
BROWN
H
C
F
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2
IN
L
COIL
C
Y
O
R
AMBDF1DF2
RV
DEFROST BOARD
RV COIL
LPS
HPS
CCH
L2
L1
T2
T1
OUTDOOR
FAN MOTOR
COMPRESSOR
CAPACITOR
COMFORT ALERT
Y
R
O
C
W1
Y2
L
CC
Y2
Y
LR
C
DC
SOL
CSC
AMB
SENSOR
COIL
SENSOR
208/230V
208/230V
Two Stage Split System Heat Pump (Outdoor Section) With Demand Defrost and PSC Fan Motor Single Phase / 60 Hz.
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
°C
NOTES:
Module has power
Status LED
Green “POWER”
Yellow “ALERT” Flash Code 1
Red “TRIP”
Yellow “ALERT” Flash Code 2
Yellow “ALERT” Flash Code 3
Thermostat demand signal Y is present,but the compressor is not running
Yellow “ALERT” Flash Code 4
Yellow “ALERT” Flash Code 5
Yellow “ALERT” Flash Code 6
Yellow “ALERT” Flash Code 7
Yellow “ALERT” Flash Code 8
Status LED Description
LONG RUN TIME - Compressor is running extremely long run cycle
SYSTEM PRESSURE TRIP - Discharge or suction pressure out of limits
or compressor overloaded
SHORT CYCLING - Compressor is running only briefly
LOCKED ROTOR
OPEN CIRCUIT
OPEN START CIRCUIT - Current only in run circuit
WELDED CONTACTOR - Compressor always runs
Yellow “ALERT” Flash Code 9
OPEN RUN CIRCUIT - Current only in start circuit
LOW VOLTAGE - Control circuit < 17 VAC
CC- Contactor Coil
CCH - Crankcase Heater
CSC - Compressor Solenoid Coil
LPS - Low Pressure Switch
HPS - High Pressure Switch
RVS - Reversing Valve Solenoid
BLACK
WHITE
BLUE
ORANGE
BROWN
YELLOW
RED
R
S
C
C
R
S
WIRING DIAGRAM
711117-0
0710
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
Figure 10. W.D. for 2 Ton Models With Comfort Alert
15
AMB
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2 IN
L
COIL
C
Y
O
R
DF1 DF2
RV
BLACK
RED
OUTDOOR
FAN MOTOR
T1 T2
L1 L2
COMPRESSOR
HPS
LPS
RV COIL
CCH
BLACK
RED
BLUE
ORANGE
H
F
C
R
S
TO THERMOSTAT
AMB SENSOR
OD SENSOR
CONTACTOR
DEFROST BOARD
LFT
RT
S
L
H
C
NC
NO
COM
GRND
GROUNDING
SCREW
FAN RELAY
CAPACITOR
L1 L2
YELLOW
C
TERMINAL
BLOCK
D
RED
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2
IN
COIL
C
Y
O
AMBDF1DF2
RV
DEFROST BOARD
S
L
H
R
H
F
C
RV COIL
LPS
HPS
WIRING DIAGRAM
711016
1209
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
YELLOW
BLACK
YELLOW
BLACK
BLACK
BLACK
BLACK
BLUE
YELLOW
R
S
C
OFR
CCH
L2
L1
T2
T1
OUTDOOR
FAN MOTOR
COMPRESSOR
CAPACITOR
CC
FRC
Y
O
C
Y2
CSC
AMB
SENSOR
COIL
SENSOR
208/230V
208/230V
Two Stage Split System Heat Pump With Demand Defrost and Two Speed Fan Motor Single Phase / 60 Hz.
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
°C
YELLOW
ORANGE
BLACK
WHITE
BLUE
BROWN
W1
¢711016q¤
Figure 11. W.D. for 3 Ton Models Without Comfort Alert
16
AMB
HPS
W2 OUT
LPS
Y2
OUT
Y
OUT
Y2
W2 IN
L
COIL
C
Y
O
R
DF1DF2
RV
BLACK
RED
OUTDOOR
FAN MOTOR
Y2
Y
L
R
C
DC SOL
COMFORT
ALERT MODULE
T1 T2
L1 L2
COMPRESSOR
HPS
LPS
RV COIL
CCH
BLACK
RED
BLUE
ORANGE
H
F
C
R
S
TO THERMOSTAT
AMB SENSOR
OD SENSOR
CONTACTOR
DEFROST BOARD
LFT
RT
S
L
H
C
ROUTE THIS WIRE
THROUGH THE “R”
OPENING IN COMFORT
ALERT MODULE
ROUTE THIS WIRE
THROUGH THE “C”
OPENING IN
COMFORT ALERT
MODULE
ROUTE THIS WIRE THROUGH
THE “S” OPENING IN COMFORT
ALERT MODULE
NC
NO
COM
GRND
GROUNDING
SCREW
FAN RELAY
CAPACITOR
L1 L2
YELLOW
RED
BROWN
CC- Contactor Coil
CCH - Crankcase Heater
CSC - Compressor Solenoid Coil
LPS - Low Pressure Switch
HPS - High Pressure Switch
RVS - Reversing Valve Solenoid
OFR - Outdoor Fan Relay
FRC - Fan Relay Coil
HPS
W2 OUT
LPS
Y2
OUT
Y
OUT
Y2
W2
IN
L
COIL
C
Y
O
R
AMBDF1DF2
RV
DEFROST BOARD
S
L
H
R
H
F
C
Y2
Y
LR
C
DC
SOL
RV COIL
LPS
HPS
WIRING DIAGRAM
710964A
(Replaces 7109640)
0811
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
YELLOW
BLACK
YELLOW
RED
BLACK
BLUE
BLACK
BLACK
BLACK
BLUE
YELLOW
R
S
C
OFR
CCH
L2
L1
T2
T1
OUTDOOR
FAN MOTOR
COMPRESSOR
CAPACITOR
COMFORT ALERT
CC
FRC
Y
R
O
C
Y2
L
CSC
AMB
SENSOR
COIL
SENSOR
208/230V
208/230V
Two Stage Split System Heat Pump With Demand Defrost and Two Speed Fan Motor Single Phase / 60 Hz.
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
°C
Module has power
Status LED
Green “POWER”
Yellow “ALERT” Flash Code 1
Red “TRIP”
Yellow “ALERT” Flash Code 2
Yellow “ALERT” Flash Code 3
Thermostat demand signal Y is present,but the compressor is not running
Yellow “ALERT” Flash Code 4
Yellow “ALERT” Flash Code 5
Yellow “ALERT” Flash Code 6
Yellow “ALERT” Flash Code 7
Yellow “ALERTFlash Code 8
Status LED Description
LONG RUN TIME - Compressor is running extremely long run cycle
SYSTEM PRESSURE TRIP - Discharge or suction pressure out of limits
or compressor overloaded
SHORT CYCLING - Compressor is running only briefly
LOCKED ROTOR
OPEN CIRCUIT
OPEN START CIRCUIT - Current only in run circuit
WELDED CONTACTOR - Compressor always runs
Yellow “ALERT” Flash Code 9
OPEN RUN CIRCUIT - Current only in start circuit
LOW VOLTAGE - Control circuit < 17 VAC
YELLOW
ORANGE
BLACK
WHITE
BLUE
BROWN
W1
Figure 12. W.D. for 3 Ton Models With Comfort Alert
17
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2 IN
L
COIL
C
Y
O
R
AMBDF1DF2
RV
OUTDOOR
FAN MOTOR
COMPRESSOR
HPS
LPS
RV COIL
CCH
WHITE
YELLOW
HC
TO THERMOSTAT
AMB SENSOR
OD SENSOR
BROWN
BLACK
CONTACTOR
T1 T2
L1 L2
LEFT
RIGHT
Y1
C
Y2
ECM
L2
L1
DEFROST BOARD
RED
BLACK
YELLOW
GRND
GROUNDING
SCREW
L1
L2
C
R
S
BLUE
C
TERMINAL
BLOCK
D
GREEN
TO UNIT
GROUND LUG
6
BLUE
BLACK
YELLOW
BLACK
YELLOW
Y1
C
Y2
ECM
L2
L1
WIRING DIAGRAM
711017B
(Replaces 711017A)
0312
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
HPS
W2 OUT
LPS
Y
OUT
Y2
OUT
Y2
W2
IN
L
COIL
C
Y
O
R
AMBDF1 DF2
RV
DEFROST BOARD
RV COIL
LPS
HPS
CCH
L2
L1
T2
T1
OUTDOOR
FAN MOTOR
COMPRESSOR
CAPACITOR
Y
R
O
C
W1
Y2
L
CC
CSC
AMB
SENSOR
COIL
SENSOR
208/230V
HC
208/230V
Two Stage Split System Heat Pump (Outdoor Section) With Demand Defrost and ECM Fan Motor Single Phase / 60 Hz.
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
°C
NOTES:
BLACK
WHITE
BLUE
ORANGE
BROWN
YELLOW
RED
R
S
C
¢711017w¤
CC- Contactor Coil
CCH - Crankcase Heater
CSC - Compressor Solenoid Coil
LPS - Low Pressure Switch
HPS - High Pressure Switch
RVS - Reversing Valve Solenoid
Figure 13. W.D. for 4 & 5 Ton Models Without Comfort Alert
18
HPS
W2 OUT
LPS
Y2
OUT
Y
OUT
Y2
W2 IN
L
COIL
C
Y
O
R
AMBDF1 DF2
RV
OUTDOOR
FAN MOTOR
Y2
Y
L
R
C
DC SOL
COMFORT
ALERT MODULE
COMPRESSOR
HPS
LPS
RV COIL
CCH
WHITE
YELLOW
HC
TO THERMOSTAT
AMB SENSOR
OD SENSOR
BROWN
BLACK
CONTACTOR
T1 T2
L1 L2
LEFT
RIGHT
Y1
C
Y2
ECM
L2
L1
DEFROST BOARD
RED
BLACK
YELLOW
GRND
GROUNDING
SCREW
L1
L2
ROUTE THIS WIRE
THROUGH THE “R”
OPENING IN COMFORT
ALERT MODULE
ROUTE THIS WIRE
THROUGH THE “C”
OPENING IN
COMFORT ALERT
MODULE
ROUTE THIS WIRE
THROUGH THE “S”
OPENING IN
COMFORT ALERT
MODULE
C
R
S
BLUE
BLACK
YELLOW
YELLOW
BLACK
BLUE
YELLOW
BLACK
RED
BROWN
Y1
C
Y2
ECM
L2
L1
WIRING DIAGRAM
710965A
(Replaces 7109650)
0811
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
HPS
W2 OUT
LPS
Y2
OUT
Y
OUT
Y2
W2
IN
L
COIL
C
Y
O
R
AMBDF1 DF2
RV
DEFROST BOARD
RV COIL
LPS
HPS
CCH
L2
L1
T2
T1
OUTDOOR
FAN MOTOR
COMPRESSOR
CAPACITOR
COMFORT ALERT
Y
R
O
C
W1
Y2
L
CC
Y2
Y
LR
C
DC
SOL
CSC
AMB
SENSOR
COIL
SENSOR
208/230V
HC
208/230V
Two Stage Split System Heat Pump (Outdoor Section) With Demand Defrost and ECM Fan Motor Single Phase / 60 Hz.
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
°C
NOTES:
Module has power
Status LED
Green “POWER”
Yellow “ALERT” Flash Code 1
Red “TRIP”
Yellow “ALERT” Flash Code 2
Yellow “ALERT” Flash Code 3
Thermostat demand signal Y is present,but the compressor is not running
Yellow “ALERT” Flash Code 4
Yellow “ALERT” Flash Code 5
Yellow “ALERT” Flash Code 6
Yellow “ALERT” Flash Code 7
Yellow “ALERT” Flash Code 8
Status LED Description
LONG RUN TIME - Compressor is running extremely long run cycle
SYSTEM PRESSURE TRIP - Discharge or suction pressure out of limits
or compressor overloaded
SHORT CYCLING - Compressor is running only briefly
LOCKED ROTOR
OPEN CIRCUIT
OPEN START CIRCUIT - Current only in run circuit
WELDED CONTACTOR - Compressor always runs
Yellow “ALERTFlash Code 9
OPEN RUN CIRCUIT - Current only in start circuit
LOW VOLTAGE - Control circuit < 17 VAC
CC- Contactor Coil
CCH - Crankcase Heater
CSC - Compressor Solenoid Coil
LPS - Low Pressure Switch
HPS - High Pressure Switch
RVS - Reversing Valve Solenoid
NOTE:
The Yellow Wire from Y1 is not
connected in the 2 ton models,
and the White Wire from Y2 is
connected to contactor left
BLACK
WHITE
BLUE
ORANGE
BROWN
YELLOW
RED
R
S
C
Figure 14. W.D. for 4 & 5 Ton Models With Comfort Alert
19
COMFORT ALERT TROUBLESHOOTING
Table 4. LED Diagnostics
STATUS LED STATUS LED DESCRIPTION STATUS LED TROUBLESHOOTING INFORMATION
POWER
(Green LED)
Module has power Supply voltage is present at module terminals
TRIP
(Red LED)
Thermostat demand signal Y is
present, but compressor is not
running
• Compressorprotectorisopen
• Checkforhighheadpressure
• Checkcompressorsupplyvoltage
• Outdoorunitpowerdisconnectisopen
• Compressorcircuitbreakerorfuse(s)isopen
• Brokenwireorconnectorisnotmakingcontact
• Lowpressureswitchopenifpresentinsystem
• Compressorcontactorhasfailedopen
ALERT
Flash Code 1
(Yellow LED)
Long Run Time Compressor is
running extremely long run cycles
• Lowrefrigerantcharge
• Evaporatorblowerisnotrunning
— Check blower relay coil and contacts
— Check blower motor capacitor
— Check blower motor for failure or blockage
— Check evaporator blower wiring and connectors
— Check indoor blower control board
— Check thermostat wiring for open circuit
• Evaporatorcoilisfrozen
— Check for low suction pressure
— Check for excessively low thermostat setting
— Check evaporator airflow (coil blockages or return airfilter)
— Check ductwork or registers for blockage
• Faultymeteringdevice
—CheckTXVbulbinstallation(size,locationandcontact)
— Check if TXV/fixed orifice is stuck closed or defective
• Condensercoilisdirty
• Liquidlinerestriction(lterdrierblockedifpresentinsystem)
• Thermostatismalfunctioning
— Solenoid plug not connected
— Y2 not wired at Comfort Alert
— Check thermostat sub-base or wiring for short circuit
— Check thermostat installation (location, level)
• ComfortAlertfailure
ALERT
Flash Code 2
(Yellow LED)
System Pressure Trip
• Highheadpressure
— Check high pressure switch if present in system
— Check if system is overcharged with refrigerant
— Check for non-condensable in system
Discharge or suction • Condensercoilpooraircirculation(dirty,blocked,damaged)
pressure out of limits
• Condenserfanisnotrunning
— Check fan capacitor
— Check fan wiring and connectors
— Check fan motor for failure or blockage
compressor overloaded
• Returnairducthassubstantialleakage
• Iflowpressureswitchpresentinsystem,checkFlashCode1information
20
COMFORT ALERT TROUBLESHOOTING - CONTINUED
Table 4. LED Diagnostics - Continued
STATUS LED STATUS LED DESCRIPTION STATUS LED TROUBLESHOOTING INFORMATION
ALERT
Flash Code 3
(Yellow LED)
Short Cycling / Compressor is
running only briefly
• Thermostatdemandsignalisintermittent
• Lowlinevoltage(contactutilityifvoltageatdisconnectislow)
• Excessiveliquidrefrigerantincompressor
• Compressorbearingsareseized
ALERT
Flash Code 4
(Yellow LED)
Locked Rotor
• Runcapacitorhasfailed
• Lowlinevoltage(contactutitlityifvoltageatdisconnectislow)
• Checkwiringconnections
• Excessiveliquidrefrigerantincompressor
• Compressorbearingsareseized
• Measurecompressoroillevel
ALERT
Flash Code 5
(Yellow LED)
Open Circuit
• Outdoorunitpowerdisconnectisopen
• Compressorcircuitbreakerorfuse(s)isopen
• Compressorcontactorhasfailedopen
— Check compressor contactor wiring and connectors
— Check for compressor contactor failure (burned, pitted or open)
— Check wiring and connectors between supply and compressor
— Check for low pilot voltage at compressor contactor coil
— High pressure switch is open and requires manual reset
• Opencircuitincompressorsupplywiringorconnections
• Unusuallylongcompressorprotectorresettimeduetoextremeambienttemperature
• Compressorwindingsaredamaged
— Check compressor motor winding resistance
ALERT
Flash Code 6
(Yellow LED)
Open Start Circuit
Current only in run circuit
• Runcapacitorhasfailed
• Opencircuitincompressorstartwiringorconnections
Check wiring and connectors between supply and the compressor S terminal
• Compressorstartwindingisdamaged
— Check compressor motor winding resistance
ALERT
Flash Code 7
(Yellow LED)
Open run circuit
Current only in start circuit
• Opencircuitincompressorrunwiringorconnections
Check wiring and connectors between supply and the compressor R terminal
• Compressorrunwindingisdamaged
— Check compressor motor winding resistance
ALERT
Flash Code 8
(Yellow LED)
Welded Contactor
Compressor always runs
• Compressorcontactorhasfailedclosed
• Thermostatdemandsignalnotconnectedtomodule
ALERT
Flash Code 9
(Yellow LED)
Low Voltage
Control circuit < 17VAC
• Controlcircuittransformerisoverloaded
• Lowlinevoltage(contactutilityifvoltageatdisconnectislow)
• Checkwiringconnections
* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. Trip and
alert LED’s flashing at same time means control circuit voltage is too low for operation.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Unbranded JT4BF Installation guide

Category
Heat pumps
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI