,TPOI +
A__ CONDmONING INC.
ELECTRIC HEAT
D)zeoh.i='
....U I+Publications
Litho U.S.A.
503,025M
2/96
Supersedes 1/96
ES180/ES240 SERIES HEATERS
INSTALLATION INSTRUCTIONS FOR ES180/ES240 SERIES ELECTRIC HEATERS FOR USE
WITH AHV180/AHV240 AND AHH180/AHH240 SERIES UNITS
Package 1 or 1 contains:
1- Electric element/harness!control box assembly
4- Bolts
4- Washers
4- Lockwashers
1- Plastic bushing
1- Strain relief bushing
1- Snap hole plug
Insulation strips
Inspect package upon recewing. If any damage is
found, contact last carrier immediately.
Installation of these electric heaters must conform
with standards in National Fire Protection
Association (NFPA) "Standard for Installation of Air
Conditioning and Ventilation Systems NFPA No.
90A," "Standard for the Installation of Residence
Type Warm Air Heating and Air Conditioning Systems
NFPA No. 90B," manufacturer's installation
instructions and local municipal building codes.
Heaters are approved for clearance to combustible
materials as listed on heater rating plate. Accessibility
and service clearances must take precedence over
fire protection clearances. All wiring must conform
with local codes and the National Electric Code (NEC)
ANSI-C1.
ES180/240 series heaters are used as primary heaters
for AHV and AHH series units. These heaters may be
installed in either upflow or horizontal application
and are designed for indoor use only.
ES180 heaters are used with AHV180/AHH180 units.
ES240 heaters are used with AHV240iAHH240 units.
1-Remove duct work from supply air side of
blower/coil unit (if unit has been previously
installed).
2- Remove blower access panel.
3-Apply provided insulation strips around the
adjoining cabinet surfaces. See figures 1 and 2.
4- Remove 3" knockout in corner of AHV/AHH unit.
5-Align heater unit with blower/coil unit; four
mounting holes in blower coil cabinet line up with
four spot nuts in ES unit and pipe nipple on ES
unit lines up with knockout just removed. Refer to
figures 1 and 2.
6- Bolt the two cabinets together using bolts and
washers provided.
7-Install bushing provided with ES on wiring
conduit nipple.
HORIZONTAL APPLICATION
INSTALL BOLT, LOCKWASHER,
BUSHING WASHER, SPOTNUT
PROVIDED
INSULATION
STRIPS
ALIGN WIRING CONDUIT NIPPLE
WITH KNOCKOUT IN BLOWER/COIL UNIT
ALIGN THE FOUR HOLES IN BLOWER COIL CABINET
WITH THE FOUR SPOTNUTS IN ES CABINET.
FIGURE 1
Page1