1300 552 976
1st October
CAUTION !! You may need to use 3 spanners to support & lock home
the couplers to avoid twisting the copper pipe either side of the
coupler.
Remove the connection cover on the side of the heat pump (remove 1
screw & push the cover downwards).
There are two brass hexagonal endcaps on the ends of the 2 spigots
protruding from the heat pump. (The frig pipes go into the side of the
spigots).
Remove the 2 endcaps.
Put a 5mm Allen key into the now exposed socket & rotate the key
anticlockwise until resistance is felt. (3 < 5 turns).
Replace the endcaps & the lower tank cover.
The refrigeration connection is now complete. Allow 10 minutes for the
charge to balance before turning the heat-pump on.
CHECK FOR REFRIGERANT LEAKS BEFORE CONTINUING.
NOTE: ONCE THE COUPLERS HAVE BEEN JOINED, THE USE-ONCE SEALS HAVE BEEN
BROKEN. DO NOT DISCONNECT THE REFRIGERANT LINES WITHOUT FIRST
PERFORMING A “PUMP-DOWN” PROCEDURE.
Electrical Connections:
In warmer climates, the heat-pump may be installed on the off-peak tariff if available. In colder
climates, if off-peak is not available, or if night-time noise is a consideration, the unit should be
installed on the day tariff. If installed on the day tariff, we recommend installing a DIN rail timer
and set the run time appropriately (to run during the warmest time of day – say from midday to
6pm – 9pm. The customer should be left the instructions for the timer, so it can be adjusted)
Remove the upper connection cover from the tank.
Take the supplied, conduit-sheathed lead & put the end with the gland through the hole in the
connection cover & secure it with the nut provided.
Push the 2 female blade terminals on the lead firmly onto the blades of the water thermostat
mounted on the side of the tank.
Secure the eyelet earth terminal to the thermostat mount post.
The bootlace pins on the other end of the lead go to terminal 1 & 2 on the heat pump connection
block & the forked earth lug goes under the earth screw.
Pull any excess lead back into the tank cover & secure it by winding a cable tie 2 or 3 times
around the lead, at the gland, to stop it from sliding back out.
Power in (Active) goes to Terminal L on
the pump connection block.
Power in (Neutral) goes to Terminal N
Earth goes to the brass earth screw.
Replace both covers.
CAUTION DO NOT START the machine until the plumbing is complete & the
TANK is FULL of WATER
Forurgentassistancepleasecall:
SkylineEnergyInstallationSupport
on0411732122