Dell UPS 2700R User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
Dellt Line-Interactive Rack UPS
1000W, 1920/1500W, and 2700/2300W
User's Guide
H919N, J718N, K792N, H928N, K802N, H945N, J727N
J735N, K811N
w w w . d e l l . c o m | s u p p o r t . d e l l . c o m
Notes and Warnings
NOTE: A NOTE indicates important information that helps you make better use of your software.
DANGER: A DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING: A WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
injury.
CAUTION: A CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury or in property damage incidents.
DANGER: Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
Information in this document is subject to change without notice.
E 2009 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.; National Electrical Code and NEC are registered
trademarks of National Fire Protection Association, Inc.; Phillips is a registered trademark of Phillips Screw Company.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their
products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
September 2009 S 164201787 4
3
Table of Contents
|
Table of Contents
1 Introduction
Finding Information 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Safety Warnings
3 Installation
Inspecting the Equipment 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unpacking the Cabinet 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identifying the UPS Rear Panels 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identifying the UPS Front Panel 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Setup 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rackmount Setup 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tower Setup 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the EBM 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the UPS 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing Remote Emergency Power-off 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Initial Startup 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operation
UPS Startup and Shutdown 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS on Battery 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Shutdown 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel Functions 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the Language 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
|
Table of Contents
Display Functions 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Startup Screen 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Screen Locked 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Status 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Event Log 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measurements 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Screens 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identification 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Retrieving the Event Log 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Behavior on Overload 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Load Segments 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controlling Load Segments Through the Display 51. . . . . . . . . . . . . . . . . . . . .
Configuring Automatic Start Delay 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic on Battery Shutdown 53. . . . . . . . . . . . . . . . . . . . . . . .
Configuring Battery Settings 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the UPS for an EBM 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Running Automatic Battery Tests 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic Battery Tests 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic Restart 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Additional UPS Features
RS-232 and USB Communication Ports 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dell Network Management Card (Optional) 58. . . . . . . . . . . . . . . . . . . . . . . . .
Dell UPS Management Software 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Table of Contents
|
6 UPS Maintenance
UPS and Battery Care 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transporting the UPS 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing the UPS and Batteries 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When to Replace Batteries 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing Batteries 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Updating the UPS Firmware 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Specifications
8 Troubleshooting
Accessing Alarms and Conditions 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Status Menu 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Event Log Menu 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Alarms and Conditions 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Silencing the Alarm 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
|
Introduction
Introduction
The Dellt Line-Interactive Rack uninterruptible power system (UPS) protects your sensitive electronic
equipment from basic power problems such as power failures, power sags, power surges, brownouts, and
line noise.
Power outages can occur when you least expect them and power quality can be erratic. These power
problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage
hardware — causing hours of lost productivity and expensive repairs.
With the Dell Line-Interactive Rack UPS, you can safely eliminate the effects of power disturbances
and guard the integrity of your equipment. The UPS's flexibility to handle an array of network devices
makes it the perfect choice to protect your LANs, servers, workstations, and other electrical equipment.
Figure 1 shows the Dell Line-Interactive Rack UPS.
Figure 1. The Dell Line-Interactive Rack UPS
1
7
Introduction
|
Providing outstanding performance and reliability, the UPS's unique benefits include:
S Buck and Boost voltage regulation that ensures regulated voltage to your load by correcting voltage
fluctuations.
S Start‐on‐battery capability for powering up the UPS even if utility power is not available.
S Maintenance is simplified by allowing the safe replacement of batteries without powering down the
UPS.
S Extended runtime with an optional External Battery Module (EBM) for 1500–2700W UPS models.
S 2700/2300W 3U UPS models only. Two-in-one form factor using the UPS in a rackmount
configuration or as a standalone cabinet.
S Emergency shutdown control through the Remote Emergency Power-off (REPO) ports.
S Two standard communication ports (USB and DB-9 serial port).
S Optional Dell Network Management Card with enhanced communication capabilities for
increased power protection and control.
S Advanced power management with the Dell UPS Management Software for graceful shutdowns
and power monitoring.
S Sequential shutdown and load management through separate receptacle groups called load
segments.
S Firmware that is easily upgradable without a service call.
S Backed by worldwide agency approvals.
8
|
Introduction
Finding Information
CAUTION: The Safety, Environmental, and Regulatory Information document provides important safety and
regulatory information.
What are You Looking For?
Find It Here
S The user's guide for my UPS
S The user's guide for the Dell Network Management
Card
S Dell UPS Management Software
NOTE: Documentation and software updates can be
found at
support.dell.com.
Dell UPS Disc
S Specifications
S How to configure UPS settings
S How to troubleshoot and solve problems
S How to install REPO control
Dell UPS User's Guide
The user's guide is available on the Dell UPS disc and
on support.dell.com.
S Safety instructions
S Regulatory information
S Recycling information
Safety, Environmental, and Regulatory Information
S Warranty information
S Terms and Conditions (U.S. only)
S End User License Agreement
Dell Warranty and Support Information
S Support information Dell Support Website — support.dell.com
NOTE: Select your region or business segment to view
the appropriate support site.
9
Safety Warnings
|
Safety Warnings
CAUTION: Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your Safety, Environmental, and Regulatory Information document.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment and
save this manual for future reference.
DANGER:
Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE
PARTS inside the UPS.
WARNING:
Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, could result in death or injury:
S This UPS contains its own energy source (batteries). The output receptacles may carry live voltage
even when the UPS is not connected to an AC supply.
S Do not remove or unplug the input cord when the UPS is turned on. This removes the safety
ground from the UPS and the equipment connected to the UPS.
S To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection with an ampere rating in accordance with the National Electrical Code
®
(NEC
®
),
ANSI/NFPA 70 or your local electrical code:
UPS Output Power 120V 208V 230V
1000W 15A 15A
1500W (at 100V)
1920W
20A 15A
2300W (at 100V)
2700W
30A 20A 16A
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum).
2
10
|
Safety Warnings
S Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and
on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely
dry (hazard of electric shock).
S If the UPS requires any type of transportation, disconnect the internal UPS batteries before
transporting (see page 61).
CAUTION:
Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury or in property damage incidents:
S For PLUGABLE EQUIPMENT, the power outlet shall be installed near the equipment and shall
be easily accessible.
S Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use
tools with insulated handles; 3) Wear rubber gloves and boots; 4) Do not lay tools or metal parts on
top of batteries; 5) Disconnect the charging source prior to connecting or disconnecting battery
terminals.
S Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the utility
source from the ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance (applicable to equipment and remote battery supplies not having a grounded supply
circuit).
S ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
S Replace batteries with the same number and type of batteries as originally installed in the UPS.
S Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes and may be extremely toxic.
S The 1500–2700W UPS may be connected to a maximum of one External Battery Module (EBM).
11
Safety Warnings
|
WARNING: Additional instructions for Rack-Mounted Systems
S Your rack kit has been approved only for the rack cabinet provided. It is your responsibility to
ensure that installation of the equipment into any other rack complies with all applicable
standards. Dell disclaims all liability and warranties with respect to combinations of equipment
with any other rack.
S Before installing your equipment in a rack, install all front and side stabilizers. Failure to install
stabilizers can allow the rack to tip over.
S Always load from the bottom up, and load the heaviest items first.
S Do not overload the AC power supply branch circuit that provides power to the rack.
S Do not stand or step on any components in the rack.
WARNING:
Slide/rail mounted equipment is not to be used as a shelf or work space.
Do not add weight to slide/rail mounted equipment.
12
|
Installation
Installation
This chapter explains:
S Equipment inspection
S Unpacking the cabinet
S UPS rear panels
S UPS setup and installation, including the External Battery Module (EBM)
S Remote Emergency Power-off (REPO) installation
S Initial startup
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials
for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of
receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service
representative.
NOTE:
Check the battery recharge date on the shipping carton label. If the date has passed and the batteries
were never recharged, do not use the UPS. Contact your service representative.
3
13
Installation
|
Unpacking the Cabinet
CAUTION: Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and
on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely dry (hazard
of electric shock).
CAUTION: The cabinet is heavy (see page 65). Use caution to unpack and move the cabinet.
Use care when moving and opening the carton. Leave the components packaged until ready to install.
To unpack the system:
1 Open the outer carton and remove the accessories packaged with the cabinet (see Figure 2).
Figure 2. Unpacking the Cabinet
14
|
Installation
2 With one person on each side, carefully lift the cabinet out of the outer carton using the handles
on the cardboard and set it on a flat, stable surface (see Figure 3).
Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable
gas, and corrosion.
Figure 3. Lifting the Cabinet
3 Discard or recycle the packaging in a responsible manner, or store it for future use.
15
Installation
|
Identifying the UPS Rear Panels
This section shows the rear panels of the Dell Line-Interactive Rack models.
IN P U T 10 0 120V~
Four 5‐15 Receptacles
(Load Segment 1)
UPS Communication Bay
IEC-C14 Input
Connector
USB Port
Two IEC 320-C13 Receptacles
(Load Segment 2)
REPO Ports RS-232 Port
Ground Screw
Figure 4. 1000W, 100V/120V Rear Panel
UPS Communication Bay
IEC-C14 Input
Connector
USB Port
Two IEC 320-C13 Receptacles
(Load Segment 2)
RS-232 Port
Ground Screw
Two IEC 320-C13
Receptacles
(Load Segment 1)
REPO Ports
Figure 5. 1000W, 230V Rear Panel
16
|
Installation
UPS Communication Bay
IEC-C20 Input
Connector
USB Port
Two IEC 320-C13 Receptacles
(Load Segment 2)
REPO Ports
RS-232 Port
Ground Screw
Six 5-15/5-20 and Two
IEC 320-C19 Receptacles
(Load Segment 1)
EBM Connector Cover/Strain
Relief Bracket
Figure 6. 1920W/120V, 1500W/100V Rear Panel
UPS Communication Bay
IEC-C14 Input
Connector
USB Port
Two IEC 320-C19
Receptacles
(Load Segment 2)
REPO Ports
RS-232 Port
Ground Screw
EBM Connector Cover/Strain
Relief Bracket
Six IEC 320-C13
Receptacles
(Load Segment 2)
Two IEC 320-C13
Receptacles
(Load Segment 1)
Figure 7. 1920W, 230V Rear Panel
17
Installation
|
UPS
Communication
Bay
USB Port
Two IEC 320-C13
Receptacles
(Load Segment 2)
REPO Ports
RS-232 Port
Ground Screw
EBM Connector
Cover/Strain Relief
Bracket
2m, L5-30P Input Cord
One L5-20, Two 5-15/5-20, and
Two IEC 320-C19 Receptacles
(Load Segment 1)
Output Circuit Breakers
Figure 8. 2700W/120V, 2300W/100V Rear Panel
REPO Ports
IEC-C20 Input
Connector
Ground Screw
USB Port
RS-232 Port
UPS
Communication
Bay
Two IEC 320-C13
Receptacles
(Load Segment 2)
EBM Connector
Cover/Strain Relief
Bracket
Two L6-20 and
Two IEC 320-C19 Receptacles
(Load Segment 1)
Figure 9. 2700W, 208V Rear Panel
18
|
Installation
REPO Ports
IEC-C20 Input
Connector
Ground Screw
USB Port
RS-232 Port
UPS
Communication
Bay
Two IEC 320-C13
Receptacles
(Load Segment 2)
EBM Connector
Cover/Strain Relief
Bracket
Six IEC 320-C13 and
Two IEC 320-C19 Receptacles
(Load Segment 1)
Figure 10. 2700W, 230V Rear Panel
Identifying the UPS Front Panel
On/Off Button
LCD Panel
Scroll Button (Down or Forward)
Select Button
Scroll Button (Up or Back)
Figure 11. The Dell Line-Interactive Rack UPS Front Panel
19
Installation
|
UPS Setup
The Dell Line-Interactive Rack UPS can be installed in 19-inch racks and needs only 2U of valuable rack
space (3U for 2700/2300W UPS models).
NOTE:
No tools are needed to attach the rack rails to a round- or square-hole EIA rack.
The 2700/2300W UPS models are designed for flexible configurations and can be installed in a rack or
as a standalone cabinet.
If you are installing the UPS in a rack, continue to the following section, “Rackmount Setup.” To install
the 2700/2300W UPS as a standalone cabinet, continue to “Tower Setup” on page 24.
Rackmount Setup
CAUTION: The cabinet is heavy (see page 65): 1) Dell strongly recommends to remove the battery tray from the
UPS before lifting. 2) Lifting the cabinets into the rack requires a minimum of two people.
CAUTION: Removing the batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
CAUTION: If installing an optional EBM, install the EBM directly below the UPS.
NOTE: Mounting rails are required for each individual cabinet.
To install the UPS and optional EBM in a rack:
1 Remove the internal battery tray from the UPS:
Loosen the thumbscrew on the metal battery cover, slide the cover to the right, and open (see
Figure 12).
Figure 12. Opening the Metal Battery Cover
20
|
Installation
Unclip the right battery connector and move the connector out of the way.
Pull the battery tray out using the plastic tabs and remove the battery tray (see Figure 13).
Figure 13. Removing the Battery Tray
2 If installing additional UPSs, repeat Step 1 for each cabinet.
NOTE:
The instructions are the same for square-hole racks and unthreaded, round-hole racks. The rails fit both
rack styles. The square-hole rack is shown in the illustrations.
3 Select the proper holes in the rail for positioning the cabinet in the desired location in the rack.
The rails should be located at the bottom of the 2U (or 3U for 2700/2300W UPS models) space
allocated for the UPS or EBM.
4 Position the end of the left and right rails labeled FRONT facing inward.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73

Dell UPS 2700R User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI