LG LH247HV LH247HV Submittal

Type
LH247HV Submittal
Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
SingleZoneHighStaticDuct
LH247HV
Page1of3
SB_SZ_HS_Ducted_LH247HV_02_17
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
Performan ce:
Cooling(MinRatedMax,Btu/h)
9,700‐24,000‐26,700
SEER/EER
17.0
/
12.0
Cooling:
Heating:
Heating(MinRatedMax,Bt u/h)
10,900‐27,000‐30,000
HSPF
10.0
CoolingNominalTestConditions: HeatingNominalTestConditions:
Indoor:
80°FDB/67°FWB
Indoor:
70°FDB/60°FWB
Outdoor:
95°FDB/75°FWB
Outdoor:
47°FDB/43°FWB
Electrical:
MCA(A )
18.1
MOP(A)
30
FanMotor(A)
0.6
CoolingRatedAmps(A)
15.1
HeatingRatedAmps(A)
15.1
CoolingPowerInput(kW)
2.00
HeatingPowerInput(kW)
2.28
Piping:
LiquidLine(in,OD)
3/8
AdditionalRefrigerant(oz/ft)
0.43
MaxElevation(ft)
98
MaxPipeLength(ft)²
164
VaporLine(in,OD)
5/8
Features:
•ESPcontrol
•Hotstart
•Inverter(variable
speedfan)
•Internal
condensatepump
•Autorestart
•Controllock
OperatingRange:
OutdoorUnit:
IndoorUnit:
UnitData:
RefrigerantType/Control
R410A/E EV
RefrigerantCharge(lbs)
4.4
Fan:
Notes:
1.Acceptableoperangvoltage:187V253V.
2.Pipinglengthsareequivalent.
3.SoundPressurelevelsaretestedinananechoicchamberunderISOStandard1996.
4.Maximumstacpressuremayresultinreducedairow(CFM).
5.Allpower/communicationcabletobeminimum18Americanwir egage(AWG),4conductor,
stranded,shieldedorunshieldedwir
eandmustcomplywithapplicablelocalandnationalcode.
Ifshielded,thewiremustbegroundedtothec hassisattheoutdoorunitonly.
6.SeeEngineeringManualforsensibleandlatentcapacies.
7.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
8.Theindooruni
tcomeswithadryheliumcharge.
9.Thisdataisrated0abovesealevel,with25ofrefrigerantlineanda0leveldierence
betweenoutdoorandindoorunits.
10.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
11.Iftheoptionallowambientwindbaffle(ZL
ABGP04A) isused,onewindbaffleisrequiredfor
eachODUfan.
Motor/Drive
BrushlessDigitallyControlled/Direct
ODUNetWeight(lbs)
133
ODUShippingWeight(lbs)
146
IDUNetWeight(lbs)
73
IDUShi ppingWeight(lbs)
95
FanSpeeds(Fan/Cooling/Heating)
3/3/3
FanQuantity(ODU+IDU)
1+1
Heating(°FWB)
064
Cooling(°FWB)
5777
SEER‐SeasonalEnergyEfficiencyRating EER‐EnergyEfficiencyRating
HSPF‐HeatingSeasonalPerformanceFactor
MOP‐MaximumO vercurrentProtection MCA‐MinimumCircuitAmpacity
ACEz
‐PQCSZ250S0
LGMultiSITE™CRC1Controller‐PREMTBVC0
DryContactforThermostat‐PDRYCB300
O
p
tionalAccessories
(
soldse
p
aratel
y)
PQRCVCL0QW
IncludedAccessories:
•SimpleControllerwithMode(White)‐PQRCVCL0QW
Compressor(A)
13.5
DehumidificationRate(pts/hr)
7.0
ODUAirCirculation(CFM)
2048
IDUAirCirculationH/M/L(CFM)
688/618/530
DefaultExternalStaticPr essure(inwg)
0.39
Cooling(°FDB)
5118
Heating(°FDB)
5981
PowerSupply(V¹/Hz/Ø)
208230/60/1
ODUSoundPressureMax(Cool/Heat) ±3dB( A)³
48/52
IDUSoundPressure(H/M/L)±3dB( A) ³
38/36/35
PipeLength(noadd'lRefrigerant,ft)
25
IndoorUnit(IDU)‐LHN247HVOutdoorUnit(ODU)‐LUU247HV
•Groupcontrol
•Timer(on/o)
•Sleepmoden
HighEfficiencyFilterBoxforBRHSDChassis‐ZFBXBR01A
DynamicV82VLLowP rofileAirCleane r‐ZPL MV201A
DynamicV84VLLowP rofileAirCleane r‐ZPL MV402A
ODU/IDUFanType
Propeller/Sirocco
MinimumESP/FanSettingValue
0.01/82
MaximumESP/FanSettingValue
0.78/159
PI485‐PMNFP14A1
LowAmbientWindBaffle(coolingoperationto0°F)‐ZLABGP04A¹¹
JobName/Location:
Ta g#:
Date:
PONo.:
SingleZoneHighStaticDuct
Page2of3
SB_SZ_HS_Ducted_LH 247HV_02_17
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
©LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
OutdoorUnit
(
ODU
)
‐LUU247HV
JobName/Location:
Ta g#:
Date:
PONo.:
SingleZoneHighStaticDuct
Page3of3
SB_SZ_HS_Ducted_LH 247HV_02_17
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
IndoorUnit
(
IDU
)
‐LHN247HV
  • Page 1 1