10 IPB-99-7-EN-10-6-99
Performance
Data Cooling English Units
WCC030FD00B AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
59 29.3 23.6 25.4 27.2 29.1 30.0* 2.29
85 63 31.5 20.1 21.9 23.7 25.5 27.3 2.37
67 33.8 16.2 18.0 19.8 21.6 23.4 2.44
71 36.2 12.3 14.1 15.9 17.7 19.5 2.52
59 28.6 23.3 25.1 26.9 28.7* 29.4* 2.41
90 63 30.8 19.8 21.6 23.4 25.2 27.0 2.48
67 33.0 15.9 17.7 19.5 21.3 23.1 2.56
71 35.3 11.9 13.7 15.5 17.3 19.1 2.64
59 27.9 23.0 24.8 26.6 28.2* 28.8* 2.53
95 63 30.0 19.5 21.3 23.1 24.9 26.7 2.60
67 32.2 15.6 17.4 19.2 21.0 22.8 2.67
71 34.4 11.6 13.4 15.2 17.0 18.8 2.75
59 27.0 22.6 24.4 26.2 27.5* 28.1* 2.65
100 63 29.0 19.1 20.9 22.7 24.5 26.3 2.72
67 31.1 15.2 17.0 18.8 20.6 22.4 2.79
71 33.3 11.2 13.0 14.8 16.6 18.4 2.86
59 26.2 22.2 24.1 25.9 26.7* 27.4* 2.77
105 63 28.1 18.7 20.5 22.3 24.1 25.9 2.84
67 30.1 14.8 16.6 18.4 20.2 22.0 2.91
71 32.2 10.8 12.6 14.4 16.2 18.0 2.98
59 24.4 21.5 23.3 24.7* 25.3* 25.9* 3.02
115 63 26.2 17.9 19.7 21.5 23.3 25.1 3.08
67 28.1 14.0 15.8 17.6 19.4 21.2 3.14
71 30.0 10.0 11.8 13.6 15.4 17.2 3.20
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 875 1125
TOTAL CAP. X0.98 X1.02
SENS. CAP. X0.94 X1.05
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32200 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 2673 WATTS
I.D. FAN POWER = 340 WATTS
O.D. FAN POWER = 250 WATTS
E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8
SUCT. AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
WCC040FD00B AT 1325 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
59 37.1 30.9 33.4 35.9 37.7* 38.6* 2.60
85 63 40.0 25.9 28.5 31.0 33.5 36.1 2.68
67 42.9 20.5 23.1 25.6 28.1 30.7 2.75
71 46.0 15.0 17.6 20.1 22.6 25.1 2.84
59 36.5 30.6 33.1 35.7 37.2* 38.1* 2.73
90 63 39.3 25.7 28.2 30.7 33.3 35.8 2.81
67 42.2 20.3 22.8 25.3 27.9 30.4 2.89
71 45.2 14.8 17.3 19.8 22.4 24.9 2.97
59 35.9 30.4 32.9 35.4 36.7* 37.6* 2.87
95 63 38.6 25.4 28.0 30.5 33.0 35.5 2.95
67 41.5 20.0 22.5 25.1 27.6 30.1 3.02
71 44.5 14.5 17.0 19.6 22.1 24.6 3.10
59 34.9 29.9 32.5 35.0* 35.9* 36.8* 3.01
100 63 37.6 25.0 27.5 30.1 32.6 35.1 3.09
67 40.4 19.6 22.1 24.7 27.2 29.7 3.16
71 43.2 14.1 16.6 19.1 21.7 24.2 3.24
59 33.9 29.5 32.1 34.2* 35.1* 35.9* 3.16
105 63 36.5 24.6 27.1 29.6 32.2 34.7 3.23
67 39.2 19.2 21.7 24.2 26.8 29.3 3.30
71 42.0 13.7 16.2 18.7 21.3 23.8 3.37
59 32.0 28.7 31.3 32.6* 33.4* 34.2* 3.45
115 63 34.4 23.8 26.3 28.8 31.3 33.9 3.51
67 37.0 18.4 20.9 23.4 25.9 28.5 3.57
71 39.6 12.8 15.4 17.9 20.4 22.9 3.64
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1150 1500
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.94 X1.06
COMPR. KW X0.98 X1.02
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 41600 BTUH
AIRFLOW = 1325 CFM
COMPRESSOR POWER = 3022 WATTS
I.D. FAN POWER = 560 WATTS
O.D. FAN POWER = 500 WATTS
E.E.R. = 9.70 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8
SUCT. AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
WCC050FD00B AT 1675 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
59 47.9 40.4 43.6 46.9 48.7* 49.9* 4.22
85 63 51.3 34.0 37.3 40.5 43.7 47.0 4.35
67 55.0 27.0 30.3 33.5 36.8 40.0 4.48
71 58.8 19.9 23.2 26.4 29.6 32.9 4.61
59 47.3 40.2 43.4 46.7 48.3* 49.4* 4.17
90 63 50.8 33.8 37.1 40.3 43.5 46.8 4.29
67 54.5 26.8 30.1 33.3 36.5 39.8 4.41
71 58.2 19.7 23.0 26.2 29.4 32.7 4.54
59 46.9 40.0 43.2 46.4 47.9* 49.0* 4.11
95 63 50.3 33.6 36.9 40.1 43.3 46.6 4.22
67 53.9 26.6 29.9 33.1 36.3 39.6 4.34
71 57.7 19.5 22.8 26.0 29.2 32.5 4.46
59 45.1 39.2 42.4 45.3* 46.5* 47.6* 4.28
100 63 48.5 32.8 36.1 39.3 42.6 45.8 4.39
67 51.9 25.9 29.1 32.3 35.6 38.8 4.51
71 55.6 18.8 22.0 25.2 28.5 31.7 4.63
59 43.4 38.4 41.7 44.0* 45.0* 46.1* 4.46
105 63 46.6 32.1 35.3 38.6 41.8 45.0 4.57
67 50.0 25.1 28.4 31.6 34.8 38.1 4.68
71 53.5 18.0 21.3 24.5 27.7 31.0 4.80
59 39.9 36.9 40.0* 41.1* 42.1* 43.1* 4.82
115 63 42.9 30.6 33.8 37.1 40.3 43.1* 4.92
67 46.0 23.6 26.9 30.1 33.3 36.6 5.03
71 49.3 16.6 19.8 23.0 26.3 29.5 5.13
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1450 1900
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.94 X1.06
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 54000 BTUH
AIRFLOW = 1675 CFM
COMPRESSOR POWER = 4339 WATTS
I.D. FAN POWER = 680 WATTS
O.D. FAN POWER = 500 WATTS
E.E.R. = 9.35 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8
SUCT. AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY
FOR WET COIL
ALL TEMPERATURES IN DEGREES F.