Amerex 250 Owner's manual

Type
Owner's manual

This manual is also suitable for

PN 05607 04/2020
PART
NUMBER
TITLE DATE CREATED CREATED BY REV. CKD
05607 MANUAL OWNERS SERVICE FOAM 4-8-96 MS G
THIS DRAWING IS THE EXCLUSIVE AND CONFIDENTIAL PROPERTY OF AMEREX
CORPORATION. IT SHALL NOT BE DUPLICATED, USED OR DISCLOSED TO OTHERS
REV DRAWING CHANGE BY ECN# DATE
E UPDATE MANUAL FORMAT JH B000861 11-17-15
F REVISED PAGE 3, WARNING NOTE B, 25 PSI WAS 125 PSI MS B001233 12-02-16
G REFRESHED LAYOUT DESIGN CT B002026 4/29/20
COVER SHEET
DO NOT PRINT THIS PAGE FOR ACTUAL MANUAL. INTERNAL USE ONLY.
# NOTES
1 THIS COVERSHEET FOR INFORMATIONAL PURPOSES ONLY - DO NOT PRINT THIS PAGE IN MANUAL.
2 DESCRIPTION: MANUAL OWNERS SERVICE FOR FOAM PORTABLE EXTINGUISHERS
3 ACTUAL PRINTED MATERIAL TO CONSIST OF ATTACHED
4 OVERALL SIZE OF PRINTED DOCUMENT PAGES: 8-1/2” X 11” ON 20 LB PAPER
5 PRINTED MATERIAL TO MATCH ATTACHED IN SADDLE STITCHED BOOKLET FORM
6 PRINT MATERIAL IS TO BE HOLE PUNCHED 3 EACH 1/4HOLES DOWN LEFT SIDE FOR STD 3-RING BINDER
7 CURENT REVISION DATE: 4/20
PN 05607 04/2020
WARNING: DO NOT USE THESE EXTINGUISHERS ON FIRES INVOLVING ENERGIZED ELECTRICAL
EQUIPMENT (CLASS-C HAZARDS), FLAMMABLE METALS (CLASS-D HAZARDS), OR ANY
FLAMMABLE THAT WILL REACT WITH WATER. PROTECT FROM FREEZING!
All fire extinguishers shall be installed, inspected, and maintained in accordance with the National Fire
Protection Association standard titled "Portable Fire Extinguishers", NFPA 10, or the National Fire Code of
Canada and the requirements of local authorities having jurisdiction.
When maintenance is indicated it shall be performed by trained persons having proper equipment. Fire
extinguishers are pressure vessels and must be treated with respect and handled with care. They are
mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and
safely. Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained
professional – your local authorized Amerex Distributor.
Amerex Corporation makes original factory parts available to insure proper maintenance use of substitute
parts releases Amerex of its warranty obligations. Amerex parts have machined surfaces and threads that are
manufactured to exacting tolerances. O-rings, hoses, nozzles, horns and all metal parts meet precise
specifications and are subjected to multiple in-house inspections and tests for acceptability. There are
substitute parts available that are incorrectly labeled as UL component parts, some are advertised as Amerex
type. None of these meet UL requirements, and all of them void the Amerex extinguisher warranty and UL
listing. DO NOT SUBSTITUTE.
RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE
OWNERS SERVICE MANUAL
INSTALLATION, OPERATING & SERVICING INSTRUCTIONS
MANUAL PN 05607
FOAM EXTINGUISHERS
MODELS 250, 254
AMEREX CORPORATION DOES NOT SERVICE, MAINTAIN, OR RECHARGE FIRE
EXTINGUISHERS. THE MAINTENANCE AND RECHARGE PORTION OF THIS MANUAL IS
PUBLISHED AS A GUIDE TO ASSIST SERVICE PERSONNEL IN THE INSPECTION,
MAINTENANCE, AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY. NO
INSTRUCTION MANUAL CAN ANTICIPATE ALL POSSIBLE MALFUNCTIONS THAT MAY BE
ENCOUNTERED IN THE SERVICE OF FIRE EXTINGUISHERS. AMEREX ASSUMES NO
LIABILITY FOR SERVICE, MAINTENANCE, OR RECHARGE OF FIRE EXTINGUISHERS BY
PUBLISHING THIS MANUAL.
AMEREX CORPORATION P.O. BOX 81 – TRUSSVILLE, ALABAMA 35173-0081
Phone: 205/655-3271 Fax: 800/654-5980
e-mail: sales@amerex-fire.com Web Page: http://www.amerex-fire.com
REFERENCES IN THIS MAUNUAL:
NFPA 10 Portable Fire Extinguishers
JJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJJ
CGA C-1 Methods for Pressure Testing Compressed Gas
Cylinders
CGA C-6 Standard for Visual Inspection of Steel
Compressed Gas Cylinders.
National Fire Code of Canada
AVAILABLE FROM:
National Fire Protection Association, 1 Batterymarch Park,
Quincy, MA 02169-7471
Compressed Gas Association, 14501 George Carter Way,
Chantilly, VA 20151-2923
Compressed Gas Association, 14501 George Carter Way,
Chantilly, VA 20151-2923
National Research Council Canada, 1200 Montreal Road,
Building M-58Ottawa, ON K1A 0R6 Canada
PN 05607 04/2020
INSPECTING THE EXTINGUISHER
This extinguisher must be inspected at regular intervals (monthly or more often if circumstances require) to
insure that it is ready for use.
INSPECTION - A quick checkshall be made of the extinguisher for the following:
1. Located in designated place.
2. No obstructions to access or visibility.
3. Operating instructions on nameplate (label) and facing outward.
4. Tamper seal not broken or missing.
5. Determine fullness by weighing or "hefting".
6. Examine for obvious physical damage, corrosion, leakage, or clogged nozzle.
7. Pressure gauge reading in the operable area.
MAINTENANCE SERVICE PROCEDURE
At least once a year (or more frequently if indicated by an inspection), maintenance shall be performed.
Maintenance is a thorough checkof the extinguisher. It is intended to give maximum assurance that an
extinguisher will operate effectively and safely. It includes a thorough examination and any necessary repair
or replacement. It will normally reveal the need for hydrostatic testing.
1. Clean extinguisher to remove dirt, grease, or foreign material. Check to make sure that the instruction
nameplate is securely fastened and legible. Inspect the cylinder for corrosion, abrasion, dents, or weld
damage. If any of these conditions are found and you doubt the integrity of the cylinder, hydrostatically
test, using the proof-pressure method and a suitable cage, in accordance with CGA Pamphlet C-1 and
NFPA 10. NOTE: When cleaning avoid use of solvents around the pressure gauge. They could seriously
damage the plastic gauge face.
2. Inspect the extinguisher for damaged, missing, or substitute parts. Only factory-replacement parts are
approved for use on Amerex fire extinguishers.
3. Check the date when last recharged. The foam charge must be replaced every 3 years with the
proper Amerex charge (Model 502/504 AR-AFFF charge for models 250, 252 and 254). If the
extinguisher is to be hydrostatically tested, do not reuse the charge even if within a three-year cycle (the
foaming action will make it almost impossible to get complete charge back into the extinguisher).
4. Weigh extinguisher, and compare with weight printed on the Weigh Blocksection of the nameplate
(label). Recharge extinguisher if weight is not within the indicated allowable tolerances.
5. Check the date of manufacture on the extinguisher hanger loop or on the extinguisher nameplate.
Cylinder must be hydrostatically tested every 5 years to the test pressure indicated on the label.
6. Visually inspect the pressure gauge:
a. If bent, damaged, or improper gauge, depressurize and replace.
b. If pressure is low, check for leaks.
c. If over pressurized (overcharged), depressurize (discharge) and follow recharging instructions.
7. Inspect the footstand (base). If cracked or broken replace with proper footstand.
8. Inspect pull pin for freedom of movement by breaking the tamper seal and removing the pin. Replace the
pull pin if bent or if removal is difficult.
9. Inspect discharge lever for dirt or corrosion that might impair freedom of movement. Inspect carrying
handle for proper installation. If lever, handle, or rivets are damaged or distorted, replace with proper
Amerex part(s).
10. Remove hose assembly, inspect hose assembly for damage, and replace as necessary. Blow air through
hose assembly to insure passage is clear of foreign material.
PN 05607 04/2020
11. Inspect the valve assembly for corrosion or damage to hose thread connections. Replace valve assembly
or component parts as necessary following the proper depressurization and recharge procedures.
12. Install hose and nozzle assembly.
13. Install new tamper seal, and record service data on the extinguisher inspection tag.
14. Rehang the extinguisher on the wall hanger bracket making sure that it fits the hanger bracket properly
replace the bracket if necessary.
RECHARGE
RECHARGING is the replacement of the extinguishing agent and includes the expellant for this type of
extinguisher.
THE FIRE EXTINGUISHING AGENT IN THIS EXTINGUISHER MUST BE COMPLETELY REPLACED
EVERY 3 YEARS. Use only the Amerex Model 502/504 AR-AFFF charge to retain the UL approval and
manufacturers warranty. Substitute charges could make the extinguisher less effective.
WARNING:
a. Before attempting to recharge be sure this extinguisher is completely depressurized.
b. Use a regulated nitrogen pressurizing source. Set the regulator no more than 25 psi (172 kPa) higher
than the gauge operating pressure.
c. Check and calibrate regulator gauge at frequent intervals. The regulator gauge shall be used to
determine when the intended charging pressure has been reached. Do not use the extinguisher
gauge for this purpose.
d. Never leave an extinguisher connected to a regulator of a high-pressure source for an extended
period of time. A defective regulator could cause the cylinder to rupture due to excessive pressure.
RECHARGING PROCEDURE
1. Complete the Maintenance-Service Procedure”, items 1-11.
2. Discharge all remaining pressure and foam solution.
3. Remove the valve assembly and disassemble by removing downtube assembly, spring, and valve stem
from the valve assembly. Remove the collar o-ring from the valve assembly. Remove collar O-ring from
the valve and plastic fill tube from the cylinder.
4. Thoroughly rinse all parts with clean water and wipe dry with a soft cloth. Inspect the valve components,
and replace the collar O-ring and valve stem with new components. Lubricate the collar O-ring and small
O-ring on the valve stem with V-711 (do not lubricate the valve stem seal). Inspect the downtube. If it is
cracked or deformed replace with proper downtube (see Parts List). Inspect downtube O-ring, replace if
necessary.
5. Rinse the cylinder with clean, fresh water and inspect the interior following CGA Visual Inspection
Standard C-6.
6. Firmly replace the plastic fill tube.
7. Refill the extinguishers as follows:
a. Models 250 and 252 2½ gal. AR-AFFF Premix
1. Fill a clean bucket with 2.33 gallons (8.82 liters) [19.34 lbs. (8.77kg)]of clean tap or distilled water.
Continue with steps b2 through b4.
b. Model 254 6 Liter AR-AFFF Premix
1. Fill a clean bucket with 1.41 gallons. (5.34 liters) [11.70 lbs. (5.31 kg)] of clean tap or distilled
water.
PN 05607 04/2020
2. Add an Amerex 502/504 AR-AFFF charge to the water.
3. Mix water and foam charge slowly and thoroughly in the bucket (paint stirrer and electric drill work
well).
4. Pour the well-mixed foam charge into the cylinder using a long spout funnel, filling from the bottom
of the cylinder to reduce foaming.
Alternatively, on an accurate scale:
c. Models 250 and 252 2½ gal. AR-AFFF Premix
1. Fill cylinder with 2.33 gallons (8.82 liters) [19.34 lbs. (8.77kg)] of clean tap or distilled water.
Continue with steps d2 through d4.
d. Model 254 6 Liter AR-AFFF Premix
1. Fill cylinder with 1.41 gallons (5.34 liters) [11.70 lbs. (5.31 kg)] of clean tap or distilled water.
2. Slowly add an Amerex 502/504 AR-AFFF charge to the water. The liquid level shall now be close
to the bottom of the fill tube.
3. If necessary, add water very slowly to bring the liquid to this level.
4. Mix water and foam charge thoroughly in the cylinder (a mix-stirwine degasser tool and electric
drill work well).
8. Install a Verification of Servicecollar around neck of cylinder. Install valve assembly to the cylinder and
properly align. Shake the extinguisher to assure a thorough mix of the foam solution.
CAUTION: TIGHTEN VALVE COLLAR NUT BY HAND ONLY. DO NOT USE WRENCH.
9. Install a PN 02141 Fill (Pressurizing) Adapter on the valve outlet (where the hose assembly attaches) and
pressurize with nitrogen to 100 psi (690 kPa). The pressure regulator shall be set to no more than 125 psi
(862 kPa). Remove Fill Adapter.
10. Check the collar, gauge, cylinder welds, and valve orifice for leaks using a leak-detection fluid or a
solution of soapy water. Remove leak detection fluid from the valve assembly by blowing out with air, and
wipe exterior of the extinguisher dry.
11. Install hose assembly into the operating valve hand tight. Install in hose clip.
12. Install pull pin with ring facing front of the extinguisher. Install new tamper seal. Record recharge date and
attach new recharge tag.
13. Weigh assembled extinguisher, and confirm that the total weight is within the allowable tolerances
indicated in the Maintenance section on the extinguisher nameplate (label).
PN 05607 04/2020
TROUBLESHOOTING GUIDE
WARNING: Determine the source of a leak before the extinguisher is depressurized. THE EXTINGUISHER
MUST BE COMPLETELY DEPRESSURIZED BEFORE ANY ATTEMPT IS MADE TO
DEVALVE IT AND CORRECT ANY LEAKAGE PROBLEM. To depressurize hold the
extinguisher in an inverted position and slowly squeeze the discharge handle. Some liquid
remaining in the downtube will be discharged so care shall be taken in the area used for
depressurization. Thoroughly clean all valve parts after depressurization and valve removal.
PROBLEM CORRECTIVE ACTION
1. Leak at collar O-ring
Remove valve assembly, clean collar (knurled) nut thoroughly, and install
new O-ring. Lubricate the O-ring with V-711 (PN 06247).
2. Leak through valve
Install new valve stem assembly. Check valve seat for scratches or foreign
matter.
3.
Leak around gauge
threads
Remove gauge*, and reinstall using Teflon tape on the gauge threads.
4. Defective gauge
Remove defective gauge*, and install a new gauge using Teflon tape on
the gauge threads.
5. Leak in the cylinder
Contact Amerex if under warranty, otherwise mark "Rejected" and return to
owner.
6. Broken footstand Install new footstand
*
Pressure gauge threads are coated with a special epoxy at the factory. For easy removal soak the
valve assembly (minus the downtube assembly) in hot water (180°F/82°C) for two to four minutes.
Remove gauge with a 7/16” open-end wrench.
FOR REPLACEMENT PARTS SEE THE AMEREX PORTABLE AND WHEELED
PARTS BOOK PN 27277 AVAILABLE AT http://www.amerex-fire.com UNDER
MANUALS OF THE RESOURCE SELECTION.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Amerex 250 Owner's manual

Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI