Sanyo SAP-KRV126EHDS Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual

This manual is also suitable for

TECHNICAL & SERVICE MANUAL
SAP-KRV96EHDS + SAP-CRV96EHDS
SAP-KRV126EHDS + SAP-CRV126EHDS
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
Indoor Model No.
SAP-KRV96EHDS
SAP-KRV126EHDS
Indoor Unit
Product Code No.
1 852 340 69
1 852 340 70
FILE NO.
Destination: Europe
Outdoor Model No.
SAP-CRV96EHDS
SAP-CRV126EHDS
Product Code No.
1 852 340 73
1 852 340 74
Outdoor Unit
SAP-KRV96EHDS
SAP-KRV126EHDS
SAP-CRV96EHDS
SAP-CRV126EHDS
REFERENCE NO. SM700708
RoHS
WARNING
This product does not contain any hazardous substances prohibited by the RoHS Directive.
These air conditioners employ new refrigerant R410A.
Pay special attention when servicing the unit.
• You are requested to use RoHS compliant parts for maintenance or repair.
• You are requested to use lead-free solder.
A
IR
C
O
N
DITIONER
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
SPECIAL PRECAUTIONS
This symbol refers to a hazard
or unsafe practice which can
result in severe personal
injury or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
CAUTION
CAUTION
WARNING
WARNING
Important!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, it
is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
thin aluminum fins on the air conditioner can cut your
fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent
"sweating" that can cause dripping and water damage to
walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.
When Servicing
Tu rn the power off at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously toxic
gas.
Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other
heat source, it can produce dangerously toxic gas.
2
Table of Contents
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications
2-2. Major Component Specifications
2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Temperature Charts
5-2. Air Throw Distance Charts
6. ELECTRICAL DATA
6-1. Electrical Characteristics
6-2. Electric Wiring Diagrams
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection
7-2. Recommended Wire Length and Diameter
7-3. Remote Control Unit Installation Position
7-4. How to Test Run the Air Conditioner
7-5. Remove the Grille to Install the Indoor Unit
8. MAINTENANCE
8-1. Address Setting of the Remote Control Unit
8-2. Removing and Mounting the Drain Hose
8-3. Removing the Grill
8-4. Removing the Electrical Component Box
8-5. Removing the P.C.Board
8-6. Removing the Panel Motor
8-7. Removing and Mounting the UV antibacterial filtration unit
8-8. Removing the Drain Pan (Air Outlet Ass'y)
8-9. Removing and Mounting the Fan Motor
8-10. Removing the Fan
8-11. Disconnecting and Connecting Positive Connector for Outdoor Unit
9. FUNCTIONS
9-1. Operation Functions
9-2. Protective Functions
5
6
8
12
13
15
16
18
20
21
23
25
26
27
28
29
30
30
31
33
33
34
35
36
37
38
39
41
...................................................................................................................
.............................................................................................................
.......................................................................................
.......................................................................................
.....................................................................................................................
...................................................................................................
............................................................................................................
.................................................................................................
....................................................................................................
....................................................................................................
...................................................................................................
........................................................................
...........................................................................
...................................................................................
........................................................................
.......................................................................
............................................................................
...............................................................................................................
...........................................................................
.....................................................................................................
.................................................................................................
................................................
.........................................................................
..............................................................................
..............................................................................................................
.................................
...........................................................................................................
...........................................................................................................
Page
3
10. TROUBLESHOOTING
10-1. Precautions before Performing Inspection or Repair
10-2. Method of Self-Diagnostics
10-3. Checking the Indoor and Outdoor Units
10-4. Trouble Diagnosis of Fan Motor
10-5. Noise Malfunction and Electromagnetic Interference
10-6. Checking and Troubleshooting when the Front Panel fails to work
11. CHECKING ELECTRICAL COMPONENTS
11-1. Measurement of Insulation Resistance
11-2. Checking Continuity of Fuse on PCB Ass'y
12. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
12-1. Characteristics of New Refrigerant R410A
12-2. Checklist before Servicing
12-3. Tools Specifically for R410A
12-4. Tubing Installation Procedures
12-5. In Case of Compressor Malfunction
12-6. In Case Refrigerant is Leaking
12-7. Charging Additional Refrigerant
12-8. Retro-Fitting Existing Systems
APPENDIX INSTRUCTION MANUAL
43
43
45
48
50
51
53
54
55
55
57
57
59
60
61
61
62
...........................................................
.................................................................................................
..............................................................................
..........................................................................................
..........................................................
.....................................
...............................................................................
.........................................................................
.........................................................................
...................................................................................................
................................................................................................
............................................................................................
....................................................................................
............................................................................................
..........................................................................................
............................................................................................
............................................................................................
Page
4
1. OPERATING RANGE
Maximum
Minimum
Maximum
Minimum
32 °C D.B. / 23 °C W.B.
19 °C D.B. / 14 °C W.B.
27 °C D.B.
16 °C D.B.
43 °C D.B.
–15 °C D.B.
24 °C D.B. / 18 °C W.B.
_
D.B. / –15 °C W.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Heating
5
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit SAP-KRV96EHDS
Outdoor Unit SAP-CRV96EHDS
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo/Qt*
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant Control
( 0.9 to 4.9 )
( 3,100 to 16,700 )
3.26
630
( 1.29 to 5.38 )
( 250 to 1,040 )
4.03
835
( 1.21 to 6.76 )
( 250 to 1,400 )
2.65
9,000
3.60
11,900
( 0.9 to 3.6 )
( 3,100 to 12,200 )
Shipping Volume
Cooling Heating
480
1.6
Cooling Heating
Depth
Net
Shipping
Package Dimensions
Weight
Width
Depth
Height
Width
mm
kg
kg
m
3
mm
mm
mm
mm
230V
mm
500
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode)
Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High)
Moisture Removal (High)
WPower Input
V
A
Available Voltage Range
Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube
Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
0.21
38.0
325
9.5
367
36.0
11.5
0.06
619
931
789
180
790
265
239
862
Outdoor UnitIndoor Unit
265 565
6.35 (1/4)
9.52 (3/8)
mMax. allowable tubing length at shipment
Flare Type
7.5
41 / 35 / 28 / 2241 / 35 / 28 / 22
4645
R410A / 1,200
Electric Expansion Valve
Washable, Anti-Mold
DC Rotary (Inverter)
Manual
Auto
Timer
Indoor / Outdoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
C.O.P.
Compressor Locked Rotor Amperes
W/W
Optional / Air Clean Filter
kW
Performance
- 4.31
%Power Factor 84 90
A 8.5
Power Source
Voltage Rating
Liters/h
BTU/h
Capacity
m
3
/h
220 to 240V Single-Phase 50Hz
E.E.R. W/W 4.21 -
6
Indoor Unit SAP-KRV126EHDS
Outdoor Unit SAP-CRV126EHDS
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo/Qt*
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant Control
( 0.9 to 5.4 )
( 3,100 to 18,400 )
4.79
1,025
( 1.17 to 5.61 )
( 250 to 1,200 )
5.77
1,260
( 1.14 to 7.32 )
( 250 to 1,600 )
3.50
11,900
4.80
16,400
( 0.9 to 3.9 )
( 3,100 to 13,300 )
Shipping Volume
Cooling Heating
510
2.0
Cooling Heating
Depth
Net
Shipping
Package Dimensions
Weight
Width
Depth
Height
Width
mm
kg
kg
m
3
mm
mm
mm
mm
230V
mm
560
-
198 to 264
Dimensions & Weight
(*Qt = Quiet mode)
Refrigerant Tubing Connections
Unit Dimensions Height
Operation Sound
Electrical Rating
Air Circulation (High)
Moisture Removal (High)
WPower Input
V
A
Available Voltage Range
Running Amperes
Refrigerant Tube Kit / Accessories
Narrow tube
Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
0.21
38.0
325
9.5
367
36.0
11.5
0.06
619
931
789
180
790
265
239
862
Outdoor UnitIndoor Unit
265 565
6.35 (1/4)
9.52 (3/8)
mMax. allowable tubing length at shipment
Flare Type
7.5
42 / 36 / 29 / 2242 / 35 / 28 / 22
4847
R410A / 1,200
Electric Expansion Valve
Washable, Anti-Mold
DC Rotary (Inverter)
Manual
Auto
Timer
Indoor / Outdoor Fan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
C.O.P.
Compressor Locked Rotor Amperes
W/W
Optional / Air Clean Filter
kW
Performance
- 3.81
%Power Factor 93 95
A 8.5
Power Source
Voltage Rating
Liters/h
BTU/h
Capacity
m
3
/h
220 to 240V Single-Phase 50Hz
E.E.R. W/W 3.41 -
7
2-2. Major Component Specifications
2-2-1. Indoor Unit
Indoor Unit SAP-KRV96EHDS
(Ambient Temp. 25 °C)
MP24Z1
MP24Z1
Rating DC 5V
Coil Resistance Ohm Each Pair of Terminal : 70 +/- 7%
Panel Motor
Type Stepping Motor
Model MP24Z5
Flap Motor
Type Stepping Motor
Rating
Model
For Upper Flap
For Lower Flap
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 70 +/- 7%
DC 5V
Aluminum Plate Fin / Copper Tube
2
1.2
0.175 Face Area
Coil
Rows
Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KRV96EHDS
1 ... D85 / L551
RCS-6MHVPUSW4E
Cross-Flow
DC Motor
SIC-39CVL-D847-3-A ... 1
8
-
30
1,550 / 1,600
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output
Coil Resistance
Rough Measure RPM (Cool / Heat)
Type
Model ... Q'ty
No. of Poles
Safety Device
Type
Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
8
Indoor Unit SAP-KRV126EHDS
(Ambient Temp. 25 °C)
MP24Z1
MP24Z1
Rating DC 5V
Coil Resistance Ohm Each Pair of Terminal : 70 +/- 7%
Panel Motor
Type Stepping Motor
Model MP24Z5
Flap Motor
Type Stepping Motor
Rating
Model
For Upper Flap
For Lower Flap
Coil Resistance Ohm
(Ambient Temp. 25 °C)
Each Pair of Terminal : 70 +/- 7%
DC 5V
Aluminum Plate Fin / Copper Tube
2
1.2
0.175 Face Area
Coil
Rows
Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Over-Heat Protection
Yes
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3.15A
CB-KRV126EHDS
1 ... D85 / L551
RCS-6MHVPUSW4E
Cross-Flow
DC Motor
SIC-39CVL-D847-3-A ... 1
8
-
30
1,650 / 1,800
Internal Controller
Yes
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
mm
Fan Motor
Nominal Output
Coil Resistance
Rough Measure RPM (Cool / Heat)
Type
Model ... Q'ty
No. of Poles
Safety Device
Type
Over- Current Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
9
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 20A
CB-CRV96EHDS
2-2-2. Outdoor Unit
Outdoor Unit SAP-CRV96EHDS
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
CC
-
Micro F
VAC
External Finish Acrylic baked-on enamel finish
FV50S ... 350
-
Yes
-
Internal Controller
Yes
Aluminum Plate Fin / Copper Tube
2
1.4
Face Area
m
2
0.414
Coil
Rows
Fin Pitch mm
Heat Exchanger Coil
ARW35A8P60SY ... 1
Compressor Oil ... Amount
8
60
750 / 750
Ohm
DC Motor
Type
Compressor Model / Nominal Output
Compressor
Coil Resistance (Ambient Temp. 20 °C)
Ohm
DC Rotary (Hermetic)
C-1RVN68H0K / 675W
R - S : 0.632
S - T : 0.632
T - R : 0.632
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Safety Device
Micro F
VAC
Run Capacitor
Crankcase Heater
Yes
Yes
Yes
-
-
-
1 ... D400
Fan
Propeller
Q'ty ... Dia. mm
Type
Type
Over- Current Protection
Over- Heat Protection
(Ambient Temp. 20 °C)
Fan Motor
Nominal Output
Coil Resistance
Safety Device
Rough Measure RPM (Cool / Heat)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
10
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 20A
CB-CRV126EHDS
Outdoor Unit SAP-CRV126EHDS
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
CC
-
Micro F
VAC
External Finish Acrylic baked-on enamel finish
FV50S ... 350
-
-
Internal Controller
Aluminum Plate Fin / Copper Tube
2
1.4
Face Area
m
2
0.414
Coil
Rows
Fin Pitch mm
Heat Exchanger Coil
ARW35A8P60SY ... 1
Compressor Oil ... Amount
8
60
750 / 750
Ohm
DC Motor
Type
Compressor Model / Nominal Output
Compressor
Coil Resistance (Ambient Temp. 20 °C)
Ohm
DC Rotary (Hermetic)
C-1RVN68H0K / 675W
R - S : 0.632
S - T : 0.632
T - R : 0.632
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Safety Device
Micro F
VAC
Run Capacitor
Crankcase Heater
Yes
Yes
Yes
-
-
-
1 ... D400
Fan
Propeller
Q'ty ... Dia. mm
Type
Type
(Ambient Temp. 20 °C)
Fan Motor
Nominal Output
Coil Resistance
Safety Device
Rough Measure RPM (Cool / Heat)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
Yes
Yes
Over- Current Protection
Over- Heat Protection
11
2-3. Other Component Specifications
Indoor Unit SAP-KRV96EHDS
SAP-KRV126EHDS
Outdoor Unit SAP-CRV96EHDS
SAP-CRV126EHDS
0
0102030405060708090
40
60
80
100
120
140
160
180
200
20
10
1
2
3
4
5
6
7
8
9
10
15 20 25 30 35 40
• Indoor air temp sensor
(Model:DTN-TKS319Y TH1)
• Humidity sensor
(Model:C10-M52R-SY2)
• Indoor heat exchanger sensor
(Model:DTN-TKS319Y TH2)
• Compressor temp sensor
(Model:DTN-TKS335B)
Resistance (k ohm)Resistance (k ohm)
Resistance (k ohm)
Temperature (°C)
Temperature (°C)
• Outdoor air temp sensor
(Model:1FA4V2E034000)
• Outdoor heat exchanger sensor
(Model:DTN-TKS334B)
40
35
30
25
20
15
10
5
0
-
20
-
15
-
10
-
50 5101520
Temperature (°C)Relative Humidity (%RH)
Resistance (k ohm)
30 35 40 45 50 55 60 65 70 75 80 85 90
1
10
100
1000
25 C
12
3. DIMENSIONAL DATA
Indoor Unit SAP-KRV96EHDS
SAP-KRV126EHDS
Unit: mm
13
Outdoor Unit SAP-CRV96EHDS
SAP-CRV126EHDS
Unit: mm
790 72
Wide tube service valve
dia.9.52 (3/8")
ID:19
Narrow tube service valve
dia.6.35
(
1/4"
)
565
16
109 55
155
2
91
26525
46
290
315
608
309
12
5
3
14
Compressor
4-way
valve
Accumulator
Wide tube
service
valve
Wide tube
O.D.
9.52 mm
(3/8 ")
Narrow
tube
service
valve
Narrow tube
O.D.
6.35 mm
(1/4")
Heat exchanger
Heat exchanger
Muffler
Capillary
tube for
split flow
Cooling cycle
(Defrosting cycle)
Heating cycle
Indoor unit Outdoor unit
Electric
expansion
valve
Strainer
M
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Indoor Unit SAP-KRV96EHDS
SAP-KRV126EHDS
Outdoor Unit SAP-CRV96EHDS
SAP-CRV126EHDS
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
IMPORTANT
CAUTION
15
Indoor air temperature 20 °C D.B.
Outdoor air temperature 7 °C D.B. / 6 °C W.B.
Indoor air temperature 27 °C D.B. / 19 °C W.B.
Outdoor air temperature 35 °C D.B. / 24 °C W.B.
5. PERFORMANCE DATA
5-1. Temperature Charts
Indoor Unit SAP-KRV96EHDS
Outdoor Unit SAP-CRV96EHDS
Cooling Characteristics Heating Characteristics
Outdoor inlet air D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C) Outdoor inlet air D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C) Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Operating current (A)
Indoor discharge air temperature (°C)
Indoor discharge air temperature (°C)
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in
heating mode. (Refer to "9-2. Overload prevention during heating.")
:Points of rating condition
Black dots in above charts indicate the following rating conditions.
NOTE
Cooling: Heating:
30 35 40
1.2
(12.2)
1.4
(14.2)
1.0
(10.2)
0.8
(8.2)
25
Outdoor fan speed
HighLow
27
°C
24
°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30°C
25 30 35 40
4
5
3
2
Outdoor fan speed
HighLow
25 30 35 40
25
20
15
10
5
Outdoor fan speed
HighLow
-
50 510152025
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
-
50 510152025
2
5
4
3
-
50 510152025
55
50
45
40
35
30
25
20
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23
°C
24°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30°C
27
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23
°C
20
°C
27
°C
24°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30
°C
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23
°C
16
Indoor air temperature 20 °C D.B.
Outdoor air temperature 7 °C D.B. / 6 °C W.B.
Indoor air temperature 27 °C D.B. / 19 °C W.B.
Outdoor air temperature 35 °C D.B. / 24 °C W.B.
Indoor Unit SAP-KRV126EHDS
Outdoor Unit SAP-CRV126EHDS
Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in
heating mode. (Refer to "9-2. Overload prevention during heating.")
:Points of rating condition
Black dots in above charts indicate the following rating conditions.
Cooling Characteristics Heating Characteristics
NOTE
Cooling: Heating:
Outdoor inlet air D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C) Outdoor inlet air D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C) Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Operating current (A)
Indoor discharge air temperature (°C)
Indoor discharge air temperature (°C)
Outdoor inlet air D.B. temp. (°C)
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
30 35 40
1.2
(12.2)
1.4
(14.2)
1.0
(10.2)
0.8
(8.2)
25
Outdoor fan speed
HighLow
27
°C
24
°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30
°C
25 30 35 40
5
6
4
3
Outdoor fan speed
HighLow
25 30 35 40
25
20
15
10
5
Outdoor fan speed
HighLow
-
50 510152025
4.0
(40.8)
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
-
50 510152025
4
7
6
5
-
50 510152025
55
50
45
40
35
30
25
20
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23
°C
24
°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30
°C
27
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
27
°C
24
°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30
°C
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23
°C
17
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20 °C
Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27 °C
Fan speed : High
Cooling
: Flap angle 0° , : Axis air velocity 0°
: Flap angle 30°, : Axis air velocity 30°
: Flap angle 45
°
,
: Axis air velocity 45°
: Flap angle 60
°
,
: Axis air velocity 60°
5-2. Air Throw Distance Charts
Indoor Unit SAP-KRV96EHDS
0
1
2
3
4
0123456789
0
1
2
3
4
5
0123456789
18
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20 °C
Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27 °C
Fan speed : High
Cooling
: Flap angle 0°, : Axis air velocity 0°
: Flap angle 30°, : Axis air velocity 30°
: Flap angle 45°, : Axis air velocity 45°
: Flap angle 60°, : Axis air velocity 60°
Indoor Unit SAP-KRV126EHDS
0
1
2
3
4
0123456789
0
1
2
3
4
5
0123456789
19
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit SAP-KRV96EHDS
Outdoor Unit SAP-CRV96EHDS
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor + Compressor
Performance at 230V Single-phase 50Hz
Rating conditions Running amp. A 0.34
Power input W 30
2.92
600
Rating conditions: Indoor air temperature: 27 °C D.B. / 19 °C W.B.
Outdoor air temperature: 35 °C D.B.
Rating conditions: Indoor air temperature 20 °C D.B.
Outdoor air temperature 7 °C D.B. / 6 °C W.B.
Rating conditions: Indoor air temperature: 27 °C D.B. / 19 °C W.B.
Outdoor air temperature: 35 °C D.B.
Rating conditions: Indoor air temperature: 20 °C D.B.
Outdoor air temperature: 7 °C D.B. / 6 °C W.B.
Heating
Cooling
3.26
630
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor + Compressor
Performance at 230V Single-phase 50Hz
Rating conditions Running amp. A 0.35
Power input W 32
3.68
803
4.03
835
Indoor Unit SAP-KRV126EHDS
Outdoor Unit SAP-CRV126EHDS
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor + Compressor
Performance at 230V Single-phase 50Hz
Rating conditions Running amp. A 0.36
Power input W 33
4.43
992
Heating
Cooling
4.79
1,025
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor + Compressor
Performance at 230V Single-phase 50Hz
Rating conditions Running amp. A 0.40
Power input W 39
5.37
1,221
5.77
1,260
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77