NXA-PDU-1508-8 DATA SHEET
Control System Accessories
NXA-PDU-1508-8
Power Distribution Unit
The innovative Power Distribution Unit (PDU) now allows you to control the rack as well as control the
room. This PDU adds a basic level of control by allowing remote reset of devices via a power cycle,
reducing the need to send staff to a customer site. By managing power delivery, the PDU monitors energy
consumption of each connected component and restricts power to any or all devices when not in use. With
8 individually monitored and controlled AC outlets, built-in 12 Volt power supply, 2 sets of 4 AxLink Bus
Strips, and power monitoring for each outlet, the PDU is flexible and can reduce wasteful standby power
usage. Native NetLinx control over AxLink integrates the PDU with AMX Control systems and Resource
Management Suite (RMS).
COMMON APPLICATION
Ideal for commercial and residential installations wanting to reduce energy usage costs, minimize their carbon footprint and
protect valuable electronics. With AC and AxLink power, current sensing, and available temperature monitoring, this all-in-
one easily adds both convenience and a Green element to installations.
FEATURES
• IndividuallyControlledOutlets-Allowsaremoterebootfordevicesintherackreducingon-siteservicecalls
• PowerManagementofConnectedDevices-Reducesstandbyenergyusage(vampirepower/phantomload)
• Built-inPowerCurrentSensingonEachACOutlet-Makesiteasytotellifadeviceispoweredonoroff
• SwitchedandMonitoredAxLinkBusStrips-AllowspowerandswitchingofAxLinkor12Vpowereddevices
(inbanksoffour)
• NativeNetLinxDevice-Simpliesintegration
• U.S.andInternationalvoltagessupportedutilizingIECplugreceptaclesandadaptercables
• PDUincludes12Voltpowersupplyand2setsof4AxLinkBusStripswithpowerdistributionsavingcostsoverbuying
these devices separately
• Frontmountedresetbuttonforeasyaccesswheninstalledinanequipmentrack
• Compactdesignonlytakesuponerackunit
• Optionalaccessorycablesprovideconvenientcablingeitherdirecttodeviceor120VoltNEMAadapters.
• LocalizedPowerMonitoring–Allowsenduserstotrackpowerusageofeachcomponentformanagement,
troubleshooting or showcasing Green initiatives.
NXA-PDU-1508-8 DATA SHEET
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 800.222.0193 469.624.8000 +1.469.624.7400 469.624.7153 fax www.amx.com
DIMENSIONS (HWD)
1 3/16” x 17” x 9 11/16 (3.0 cm x 43.2 cm x 9.7 cm)
RU: 1
POWER
Powered via 100-240VAC, 50-60Hz mains power on an IEC-320 C-14 connector
Required voltage = 100 to 240 VAC, 47-63 Hz
AC Current
- Input: 12 AMPS @ 110V-120V
- Input: 10 AMPS @ 220V-240V
- Outputs: 10 AMPS Single Outlet @ 110 VAC, 12 AMPS Max Unit Output @
110 VAC
- Outputs: 8 AMPS Single Outlet @ 110 VAC, 12 AMPS Max Unit Output @
220 VAC
FRONT PANEL COMPONENTS
MASTER RESET PUSHBUTTON
The Master Reset pushbutton is a momentary breaker reset switch for the AMX
Master power connection
Trippage of the reset switch causes a 0.5 second toggle on the AMX Master
AxLink power line
AXLINK STATUS LED:
Green LED lights to indicate AxLink communication activity
ON - power, no master connection
OFF - no power
Blink - powered, communicating with master
AXLINK BUS STATUS LEDs:
2 red LEDs light to indicate status (on/off) for AxLink Bus Strips 1-2. These LEDs
illuminate when the associated AxLink Bus Strip (#1) or (#2) on the PDU is in use.
AxLink Bus Strip 1 contains AxLink connectors 1 - 4
AxLink Bus Strip 2 contains AxLink connectors 5 - 8
OUTLET STATUS LEDs
8 green LEDs illuminate when the associated Power Outlet (#1 - #8) is in use.
REAR PANEL COMPONENTS
INTERNATIONAL POWER INLET (1)
100-240VAC 50/60 Hz
Connector Type: IEC C-14, 15A@120 VAC / 10A@240VAC
Intended for use with the included power cord (US Version Only)
INTERNATIONAL POWER OUTLETS (8)
100-240VAC 50/60 Hz
Connector Type: IEC C-13, 10A
Maximum load per outlet = 10A@120 VAC, 8A@240 VAC
Maximum load per unit = 15A@120VAC, 10A@240 VAC
Provides switching of mains power to each of the eight power outlets.
Measures current on each AC power outlet, as well as the total current draw of
the entire PDU.
AXLINK MASTER CONNECTOR
3.5mm Phoenix (4-pin) AxLink connector provides
connectivity to the NetLinx Master (always on)
AXLINK DEVICE CONNECTORS (8):
3.5mm Phoenix (4 pin) AxLink connectors provide connectivity to up to eight
AxLink devices Two switched banks of four outputs each:
Bank 1 contains AxLink connectors 1-4
Bank 2 contains AxLink connectors 5-8
A 13.5VDC, 6.5A power supply is provided for the AxLink bus strip. The PDU
measures current draw of the AxLink power supply.
REMOTE TEMPERATURE SENSOR (RTS) INPUT
3.5mm Phoenix (2 pin) connector provides connection to an (included) Remote
Temperature Sensor (RTS). The NXA-PDU-1508-8 is compatible with the
ENV-VST-TSF Flush Mount Indoor Temperature Sensor, and the ENV-VST-TSO
Outdoor Temperature sensor.
AXLINK ADDRESS DIP SWITCH
8-position DIP switch sets the AxLink device address for the unit.
ENCLOSURE
Steel, black powder coated finish
ENVIRONMENTAL
Operating Temperature: 0°C to 40°C (32°F to 104°F)
Operating Humidity: 5% to 85%, non-condensing
Storage Temperature: -10°C to 60°C (14°F - 140°F)
INCLUDED ACCESSORIES
NV-VST-TSO Outdoor Temperature Sensor (FG2050-22)
EC-320 C-13 to NEMA 5-15P cable
Removable rack ears
OTHER AMX EQUIPMENT
ENV-VST-TSF Indoor Temperature sensor (FG2050-21)
C13 to C14 Power Cable (FG10-673-01)
NEMA to C14 Power Cable (FG10-673-02)
NXA-PDU-1508-8 Power Distribution Unit (110V/220V) (FG673-01)
NXA-PDU-1508-8 DATA SHEET
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 800.222.0193 469.624.8000 +1.469.624.7400 469.624.7153 fax www.amx.com
NXA-PDU-1508-8
(Front View)
NXA-PDU-1508-8
(Left View)
NXA-PDU-1508-8
(Back View)
NXA-PDU-1508-8
(Top View)
17
(43.2 cm)
9 11/16
(9.7 cm)
1 3/16
(3.0 cm)