Frick Quantum Control Panel Installation guide

Type
Installation guide

Below you will find brief information for Quantum 3.5x/4.0x. This service manual provides setup and communication information for the Frick Quantum Control Panel. It covers communication protocols, including Frick's "#" and "$" protocols, as well as Allen-Bradley and Modbus communication. The manual includes checklists for setting up communication, details on wiring diagrams for RS-485 and RS-422 connections, and troubleshooting tips. It also features data tables for Allen-Bradley and Modbus communication. The document also includes information about main board communications jumpers and data access information.

Below you will find brief information for Quantum 3.5x/4.0x. This service manual provides setup and communication information for the Frick Quantum Control Panel. It covers communication protocols, including Frick's "#" and "$" protocols, as well as Allen-Bradley and Modbus communication. The manual includes checklists for setting up communication, details on wiring diagrams for RS-485 and RS-422 connections, and troubleshooting tips. It also features data tables for Allen-Bradley and Modbus communication. The document also includes information about main board communications jumpers and data access information.

COMMUNICATIONS SETUP
FRICK QUANTUM
CONTROL PANEL
VERSION 3.5x/4.0x
S90-010 CS/OCT 2000
File: SERVICE MANUAL - Section 90
Replaces: S90-010 CS/OCT 99
Dist: 3, 3a, 3b, 3c
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 2
The Quantum has the capability of being modified by the user/owner in order to obtain different performance characteristics.
Any modification to the standard default settings may have a severe negative impact on the operation and performance of
the equipment. Any modification to these control settings is the sole responsibility of the user/owner and Frick disclaims any
liability for the consequences of these modifications. It is possible that the modification of these settings may cause im-
proper operation and performance that results in property damage, personal injury or death. It is the responsibility of the
user/owner to evaluate and assess the consequences of their actions prior to modifying the controls for this unit.
QUANTUM PUBLICATIONS
S90-010 O Frick Quantum Control Panel OPERATION
S90-010 M Frick Quantum Control Panel MAINTENANCE
Contents
SETTING UP THE QUANTUM FOR COMMUNICATION..............................................................................................................3
CHECKLIST FOR SETTING UP COMMUNICATION ...................................................................................................................3
FRICK PROTOCOLS ....................................................................................................................................................................4
FRICK’S “#” PROTOCOL SPECIFICATIONS ........................................................................................................................4
QUANTUM’S PROTOCOL SPECIFICATIONS ......................................................................................................................8
ALLEN-BRADLEY COMMUNICATION ......................................................................................................................................15
SLC500 SUGGESTED SETUP .................................................................................................................................................16
CHANNEL CONFIGURATION.............................................................................................................................................16
READ MESSAGE SETUP EXAMPLE .................................................................................................................................16
WRITE MESSAGE SETUP EXAMPLE ................................................................................................................................16
PLC-5/30 - SUGGESTED SETUP ..............................................................................................................................................16
CHANNEL CONFIGURATION.............................................................................................................................................16
READ MESSAGE SETUP EXAMPLE .................................................................................................................................17
MODBUS COMMUNICATION ....................................................................................................................................................17
PORT CONFIGURATION OF THE LEADER: .............................................................................................................................17
HYPERTERMINAL SETUP ........................................................................................................................................................17
CONVERTING AN RS-232 SERIAL PORT TO RS-422 OR RS-485 .........................................................................................17
QUANTUM DATA TABLE ............................................................................................................................................................18
ALLEN-BRADLEY AND MODBUS DATA ACCESS............................................................................................................18
YORK ISN DATA ACCESS .........................................................................................................................................................35
ALARMS/SHUTDOWNS MESSAGE CODES ............................................................................................................................37
QUANTUM 1 & 2 MAIN BOARD.................................................................................................................................................39
HISTORY AND IDENTIFICATION........................................................................................................................................39
MAIN BOARD COMMUNICATIONS - COM-2 JUMPERS ..........................................................................................................40
WIRING DIAGRAMS
QUANTUM 1 & 2 TO CUSTOMER REMOTE COMPUTER/DCS - RS-485 COMMUNICATIONS ......................................40
QUANTUM 1 & 2 TO CUSTOMER REMOTE COMPUTER/DCS - RS-422 COMMUNICATIONS ......................................40
QUANTUM 1 & 2 MULTICOMPRESSOR SEQUENCING (LEAD-LAG) RS-485 COMMUNICATIONS..............................41
QUANTUM 1 & 2 MULTICOMPRESSOR SEQUENCING (LEAD-LAG) RS-422 COMMUNICATIONS..............................41
QUANTUM 3 MAIN BOARD .......................................................................................................................................................42
HISTORY AND IDENTIFICATION........................................................................................................................................42
MAIN BOARD
COM-2 JUMPERS ...............................................................................................................................................................43
LINKS (JUMPERS)..............................................................................................................................................................44
WIRING DIAGRAMS
QUANTUM 3 TO CUSTOMER REMOTE COMPUTER/DCS - RS-485 COMMUNICATIONS ............................................45
QUANTUM 3 TO CUSTOMER REMOTE COMPUTER/DCS - RS-422 COMMUNICATIONS ............................................45
QUANTUM 3 MULTICOMPRESSOR SEQUENCING (LEAD-LAG) RS-485 COMMUNICATION ......................................45
QUANTUM 3/RWB II/RDB/RXF MULTICOMPRESSOR SEQUENCING (LEAD-LAG) RS-422 COMMUNICATION .........45
OVERVIEW OF ALLEN-BRADLEY AND MODBUS CONNECTIONS .......................................................................................46
CONNECTIONS .........................................................................................................................................................................47
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 3
SETTING UP THE QUANTUM
FOR COMMUNICATION
Data communication to and from the Quantum can be through
a modem, remote data communications terminal, program-
mable controller, or leader computer via either RS-422,
RS-232, or RS-485 connections to the Quantum’s Com-2
port. Reference the “Main Board Communications - Com-2
Jump-ers” section for the correct jumpering of RS-422,
RS-232, or RS-485. Also reference the drawing of the
“Quantum Main Processor Board” (in publication S90-010
M) to identify wir-ing and jumpering locations for Comm2.
Following are the RS-422, RS-485, and RS-232 pin descrip-
tions for communications port 2 (also referred to as Com-2
or Comm2):
Quantum Panel Quantum Panel
Com-2 Com-2
RS-422 Pinout RS-485 Pinout
1 - RX (Receive) 1 -RX / - TX (Transmit)
2 + RX (Receive) 2 +RX / + TX (Transmit)
3 - TX (Transmit)
4 + TX (Transmit)
Quantum Panel Com-2, RS-232 Pinout
1 Data Communication Device (DCD)
2 Data Set Ready (DSR)
3 Received Data (RXD)
4 Request to Send (RTS)
5 Transmit Data (TXD)
6 Clear to Send (CTS)
7 Data Terminal Ready (DTR)
8 Ring Indicator (RI)
9 Ground (COM)
10 Not Used
Reference the drawing of the main processor board for the
location and positioning of the 10-Pin RS-232 connector.
Following is the pin connections showing how to wire a stan-
dard 9-Pin RS-232 connector directly to the 10-Pin RS-232
connector on the Quantum:
NOTE: The TX2 and RX2 are I/O communication activity
lamps on the Quantum Main Processor Board that can
be monitored to see if the Com-2 port is receiving (RX2)
and transmitting (TX2) data.
The use of communication protocols permit data transmis-
sion between devices. Protocol determines how contact is
established and how the query and response takes place.
The information in a message command requires an identity
of the intended receiver, what the receiver is to do, data needed
to perform an action, and a means of checking for errors.
When using Comm2 for communication, check what com-
munication protocol; if any, has been selected from the Panel
Setup – “Change Communications” display. For example:
“A-B Comm” should be selected when using Allen-Bradley’s
communication protocol. The baud rate of Comm2 and the
panel ID number are also changed from this display and
should coincide with the setup of the other device.
NOTE: The data communication protocols are continu-
ously being expanded and improved. Therefore, you
should consult Frick Company for the exact details on
your particular unit(s) before developing system soft-
ware to interface with the panel.
CHECKLIST FOR SETTING UP
COMMUNICATION
1. Decide which Quantum protocol you can communicate
with and want to use.
2. Setup your device’s communication port for the
Quantum‘s protocol and select a baud rate.
3. Next, setup the Quantum for the desired communica-
tion protocol. Select the protocol from the Panel Setup
– “Change Communications” display. For example:
“A-B Comm” should be selected when using Allen-
Bradley’s communication protocol.
4. Setup the baud rate of Comm2 to coincide with the setup
of the your device’s communication port.
5. Enter the Quantum’s ID. This will be used to identify
commands that are sent to it.
6. Wire to the first panel via RS-232, RS-422, or RS-485
connections to the Quantum’s Com-2 port.
If you are communicating to more than one panel
then you will not be able to use RS-232. You can
however convert RS-232 to either RS-422 or RS-
485 with an adaptor card. Reference the “Convert-
ing an RS-232 Serial Port to RS-422 or RS-485”
section for information about an adapter card.
Reference the drawing of the “Quantum Main Pro-
cessor Board”(in publication S90-010 M) to iden-
tify wiring and jumpering locations for Comm2.
Reference the “Main Board Communications -
Com-2 Jumpers” section in this manual for the cor-
rect jumpering of RS-232, RS-422, or RS-485.
7. Send a single command to read data from this Quan-
tum using it’s ID.
8. Check if you received a data response at your device.
9. Troubleshooting when you don’t receive a data re-
sponse:
Check if Comm2 on the “Operating Status” display
is showing “ACTIVE” or “OFF”.
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 4
“ACTIVE” is shown only when the Quantum
understands it is receiving a properly com-
posed message to itself.
Check that the RX2 I/O communication activity lamp
on the Quantum Main Processor Board is blinking
as it receives the instruction from your device.
A steady lit RX2 LED or one that isn’t lighting
are signs of improper wiring.
If the RX2 LED is properly blinking, then check if
the TX2 LED is blinking in response.
If the TX2 is not blinking then check the com-
munication protocol setup at the panel, the
panel’s ID and the Comm2 baud rate setting.
If the TX2 is blinking, then check that the
Comm2 communication jumpers are correct.
If you are sure that the wiring and Quantum
setup is correct, then select the [Show Comms]
key from the “Service Screen” display to see
what is being received and transmitted from
Comm2.
Note: A useful tool for troubleshooting is Windows
“HyperTerminal”. Using “HyperTerminal” can help you
figure out if you are wired OK. Reference the
“HyperTerminal Setup” section in this manual.
10. If you properly receive data and you need to communi-
cate to more than one panel, then setup and wire to
another panel. Reference the wiring diagram drawings
in the back of this manual. Send a single command to
read data from this Quantum using it’s ID and trouble-
shoot as above, if necessary.
11. To prevent noise feedback which is possible when com-
municating over a long distance, only the last panel
should be jumpered for long distance communication.
J68, J89, and J90 on the main board should be jumpered
for RS-422/485 communication lines. J91 and J92
should be jumpered for RS-422 communication lines.
FRICK PROTOCOLS
All commands for Frick protocols must be in ASCII to be recog-
nized. The data should be setup as an 8 bit Word with either
no Parity or even Parity, and a Stop Bit. The commands can be
in upper or lower case letters. A compressor with an ID code of
[00] is considered disabled. ID codes from [01] through [99]
are valid and recognized by the microprocessor.
FRICK’S “#” PROTOCOL SPECIFICATIONS
Frick’s “#” protocol consists of commands that are available
for most other existing models of Frick control panels. It is
better to use Frick’s Quantum (“$”) protocol when only com-
municating to Quantum panels.
When there is more than one panel, a Quantum can be wired
from it’s Com-2 to another Quantum’s Com-2 or a Quantum
can be wired from it’s Com-2 to Port 1 of a RWB, RDB, RXB
or RXF panel.
Frick RWB, RDB, RXB, or RXF Panel
Frick “#” Communications
Port #1, RS-422 Pinout
9 - TX (Transmit)
8 + TX (Transmit)
5 - RX (Receive)
4 + RX (Receive)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 5
The following is a complete list of available “#” commands:
COMMAND CODE and DESCRIPTION
I = Returns compressor status information.
R = Compressor start command.
S = Compressor stop command.
V = Slide valve/slide stop command.
P = Return Pressures information.
A = Return full load amps information.
T = Return Temperatures information.
Q = Query setpoints data.
C = Enter Change setpoints mode.
MC= Change compressor mode.
MV= Change slide valve mode.
KF = Clear Failures.
KR = Clear remaining recycle delay time.
X = Return digital I/O status.
F = Return Failures.
All data are returned as integer values. If decimal positions
are assumed, then divide the data by the proper multiple of
10 to get the actual value.
“Temperature” data, except for suction temperature, is re-
turned in the current temperature units as 3 characters with
no decimal position (i.e. 032 would represent 32 degree
Fahrenheit if the Quantum’s temperature units are in Fahr-
enheit or it would represent 32 degree Celsius if the
Quantum’s temperature units are in Celsius). Suction tem-
perature is returned as 4 characters with a “+” or “-” as the
leading character (i.e. -010 would represent -10 degrees).
“Pressure” data is usually returned in the current pressure
units. However, the Filter differential reading is always re-
turned in PSIA. When in PSIG or in PSIA, the pressure data
is returned as 3 characters with no decimal position. How-
ever; in order to show the full transducer range, the #IDPS
command returns 4 characters with one decimal position
assumed. The #IDI and #IDPA commands return 3 charac-
ters that assume one decimal position; therefore, 99.9 is the
highest value that can be returned. When in PSIG, suction
pressure is returned in PSIA. When in Bar and BarA, the
pressure data is returned as 4 characters with two decimal
positions assumed. When in KpaA, the pressure data is
returned as 4 characters with no decimal position.
The following is a detailed description of each command:
RETURN COMPRESSOR STATUS INFORMATION: #01I
# Start of command sequence.
01 Compressor ID code.
I Return Status information command.
RETURNED ANSWER, ie: 090RRRN340
Character Description
Position of returned data
1,2,3 Slide valve position.
4Remote, Auto, Manual (slide valve)
5Delay-recycle, Running, Off, Slide Valve too high,
Permissive Start not enabled, d(I)fferential
Pressure too high, s(T)opping
6Rem, M Keypad, Auto (Compressor mode)
7Cutout (Shutdown), Alarm, Normal
8,9,10 Suction in PSIA.
(Carriage return, line feed.)
NOTE: The following control commands are for remote control
of a compressor. A compressor should be in both remote
compressor mode and remote slide valve or capacity mode
for remote control.
COMPRESSOR START CONTROL: #01R01
# Start command sequence.
01 Compressor ID code.
R Start compressor command.
01 ID code repeated for verification.
NOTE: The compressor must be in the remote start mode
for this command to be executed.
RETURNED ANSWER: A01
Character Description
Position of returned data
1 Acknowledge of command sent.
2,3 ID code of compressor.
(Carriage return, line feed.)
COMPRESSOR STOP CONTROL: #01S01
returned in the current temperature units as 3 characters
with no decimal position (i.e. 032 would represent 32
# Start command sequence.
01 Compressor ID code.
S Stop compressor command.
01 ID code repeated for verification.
NOTE: The compressor must be in the remote
start mode for this command to be executed.
RETURNED ANSWER: A01
Character Description
Position of returned data
1 Acknowledge of command sent.
2,3 ID code of compressor.
(Carriage return, line feed.)
SLIDE VALVE CONTROL COMMANDS: #01VLXX
#01VUXX
#01VS
# Start command sequence.
01 Compressor ID code.
V Slide Valve/Slide Stop command.
L Load Slide valve command.
U Unload slide valve command.
XX = 00 Turns selected output off.
XX = 01 to 15 Turns selected output on
for XX seconds.
S Return slide valve position value.
If the command was #01VL00, then the load slide valve
output on compressor #1 would be turned off. If the
command was #01VL05, then the load slide valve output on
compressor #1 would be turned on for 5 seconds, and would
then automatically turn off. NOTE: the slide valve must be
in the remote mode for this command to be executed.
RETURNED ANSWER (for L or U commands): A01
Character Description
Position of returned data
1 Acknowledge of command sent.
2,3 ID code of compressor.
(Carriage return, line feed.)
RETURNED ANSWER (for S command), i.e. 090
1,2,3 Slide valve position.
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 6
RETURN SLIDE STOP POSITION COMMAND: #01VP
# Start command sequence.
01 Compressor ID code.
V Slide Valve/Slide Stop command.
P Return slide stop position value.
RETURNED ANSWER:
Character Description
Position of returned data
1 Acknowledge of command sent.
2,3 ID code of compressor.
4,5,6 Slide stop position, i.e. 025=2.5.
(Carriage return, line feed.)
RETURN PRESSURES COMMAND: #01PX
# Start command sequence.
01 Compressor ID code.
P Return pressures command.
X = S Return suction pressure (PSIA).
X = D Return discharge pressure (g/hg).
X = O Return oil pressure (g).
X = F Return filter differential pressure.
X = A Return all pressures.
If the command was #01PS, then the microprocessor
would dump the suction pressure.
Note: Don’t send CR or LF
RETURNED ANSWER
XXX = 3 characters followed by a carriage return, line feed.
If using the “A” command, then the returned data would be:
XXXXXXXXXXXX = 12 characters followed by a
carriage return, line feed.
RETURN FULL LOAD AMPS COMMAND: #01A
# Start command sequence.
01 Compressor ID code.
A Return full load amps command.
If the command was #01A, then the microprocessor
would dump the full load amps value
RETURNED ANSWER:
XXX = 3 characters followed by a carriage return, line feed.
RETURN TEMPERATURES COMMAND: #01TX
# Start command sequence.
01 Compressor ID code.
T Return temperature command.
X = S Return suction temperature.
X = D Return discharge temperature.
X = O Return oil temperature.
X = P Return separator temperature.
X = A Return all temperatures as a string
of data.
If the command was #01TS, then the microprocessor
would dump the suction temperature.
Note: Don’t send CR or LF
RETURNED ANSWER:
XXX = 3 characters followed by a carriage
return, line feed.
If using the “A” command, then the returned
data would be:
XXXXXXXXXXXX = 12 characters followed by a
carriage return, line feed.
NOTE: The “S” command will return four (4) characters: a “+”
or “-” and “xxx”, followed by a carriage return and a line feed.
QUERY SETPOINTS DATA #IDQ1 will return
Pos # Byte(s) Setpoint (Name/Comment)
1 1 Always “0”
2,3,4,5 4 Ccsp. 3 chars followed by g or h
14,15 2 Prop band
16,17 2 Dead band
18,19 2 Cycle time
20,21,22,23 4 Future
24,25,26,27 4 Future
28,29,30,31 4 Future
32,33 2 Future
34,35 2 Future
36,37 2 Future
38,39,40,41 4 High Disch. Press. Shutdown
42,43,44,45 4 High Disch. Press. Alarm
46 1 ID (tenths position byte)
47 1 ID (ones position byte)
48 1 ID Checksum of all data
(pos. 1 to 47)
49 1 CR code 13
50 1 LF code 10
51 1 0 null terminator char.
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 7
QUERY SETPOINTS DATA #IDQ2 will return
Pos # Byte(s) Setpoint (Name/Comment)
1,2,3 3 Future
4,5,6 3 Future
7,8,9 3 MLC amps stop load
10,11,12 3 MLC amps force unload
13,14,15 3 CT factor
16,17 2 Recycle delay (setpoint, not
time left)
18 1 Aux 1 0=alarm, 1=shutdown
19 1 Aux 1 0=NO, 1=NC
20 1 Aux 2 0=alarm, 1=shutdown
21 1 Aux 2 0=NO, 1=NC
22 1 Future
23,24 2 Future
25 1 Future
26 1 Future
27,28 2 Future
29 1 Future
30 1 ID (tenths position byte)
31 1 ID (ones position byte)
32 1 ID Checksum of all data
(pos. 1 to 47)
33 1 CR code 13
34 1 LF code 10
35 1 0 null terminator char.
QUERY SETPOINTS DATA #IDQ3 will return
Pos # Byte(s) Setpoint (Name/Comment)
1,2,3,4 4 Spaces
5,6,7,8 4 Future
9 1 Setback active 1=yes, 0=no
10,11,12,13 4 Auto. cycling comp. start
14,15,16,17 4 Auto. cycling comp. stop
18,19 2 Future
20,21 2 Future
22,23 2 Autocycle min. slide valve
24 1 Autocycle active 0=no 1=yes
25,26,27,28 4 Future
29,30,31,32 4 Future
33,34 2 Future
35,36 2 Future
37,38 2 Future
39 1 Future
40 1 ID (tenths position byte)
41 1 ID (ones position byte)
42 1 ID Checksum of all data
(pos. 1 to 47)
43 1 CR code 13
44 1 LF code 10
45 1 0 null terminator char.
CHANGE SETPOINTS COMMAND: #01C
# Start command sequence.
01 Compressor ID code.
C Change setpoint command.
xx Which setpoint
xxx New value
y g or h for gauge or inches
The following is the complete list of the setpoints that may
be changed while in the change setpoints command:
01xxxy Capacity Control Setpoint
(“y” deleted for KpaA & BarA ver.)
02xxxy Change Low Suction Shutdown Setpoint
(“y” deleted for KpaA & BarA ver.)
03xxxy Capacity Low Suction Alarm Setpoint
(“y” deleted for KpaA & BarA ver.)
04xxx Change High Press. Shutdown Setpoint
(“xxxx” is used for KpaA & BarA ver.)
05xxx Change High Press. Alarm Setpoint
(“xxxx” is used for KpaA & BarA ver.)
06xxx Change MLC Stop Load Setpoint
07xxx Change MLC Force Unload Setpoint
08xx Change Recycle Delay Setpoint
09xxx Change CTF Setpoint
10xx Proportional Band
11xx Dead Band
12xx Cycle Time
01 Compressor ID code
RETURNED ANSWER:
Axxxx The new setpoint which was sent followed by a
carriage return, line feed.
“BAD” followed by the “ID”, “CR”, ”LF”
if unsuccessful.
If the command was sent #01C01300g01, the capacity
control setpoint would be changed to 30.0g and the
returned answer is A300g followed by a carriage return,
line feed. If the command was sent #01C0711001, the MLC
force unload setpoint would be changed to 110% and the
returned answer is A110 followed by a carriage return, line
feed. If the command sent was #01C0520002, the returned
answer is “BAD” followed by the ID number and a carriage
return, line feed.
CHANGE COMPRESSOR MODE COMMAND:
#IDMCmID Change mode to m.
O=off A=autocycle R=remote
Return message - “A” followed by the “ID”,
CR”, “LF” if successful.
CHANGE SLIDE VALVE MODE COMMAND:
#IDMVmID Change Slide Valve mode.
to m. A=auto R=remote
Return message - “A” followed by the “ID”,
“CR”, “LF” if successful.
CLEAR FAILURE COMMAND:
#IDKFID Clear Fails
Return message - “A” followed by the “ID”,
“CR”, “LF” if successful.
CLEAR ANTIRECYCLE COMMAND:
#IDKRID Clear Recycle Delay
Return message - “A” followed by the “ID”,
“CR”, “LF” if successful.
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 8
RETURN DIGITAL IO STATUS COMMAND:
#IDX Returns Digital Inputs and Outputs Status:
Returns a 24 char data string followed by ID,
CR, LF. The 1st data
element represents input #1, the last element
represents output #16.
1=energized or on, 0=deenergized or off.
RETURN FAILURE COMMAND:
#IDF Return Discrete Failure List Command:
Returns a 24 char data string followed by ID, CR, LF.
Pos Alarm Description
1 High Discharge Pressure Shutdown
2 High Discharge Pressure Alarm
3 Low Suction Pressure Shutdown
4 Low Suction Pressure Alarm
5 Low Oil Pressure Shutdown and/or
Differential Oil Pressure Shutdown
6 Low Oil Pressure Alarm
7 High Oil Temperature Shutdown
8 High Oil Temperature Alarm
9 Low Oil Temperature Shutdown
10 Low Oil Temperature Alarm
11 High Discharge Temperature Shutdown
12 High Discharge Temperature Alarm
13 Compressor Aux. Fail - Shutdown
14 Pump Aux. Fail - Shutdown
15 Oil Level Shutdown
16 Unused - “0”
17 High Oil Filter Pressure Alarm
18 Unused - “0”
19 Auxiliary 1 Alarm/Shutdown
20 Auxiliary 2 Alarm/Shutdown
21 Low Motor Current - Shutdown
22 Sensor Fault
23 Unused - “0”
24 Unused - “0”
0=safe 1=alarm/shutdown
QUANTUM’S PROTOCOL SPECIFICATIONS
Quantum’s (“$”) protocol commands have been added spe-
cifically for the Quantum. Unless otherwise shown, 9 charac-
ters are returned from the Quantum for a data value. The data
value includes two decimal fields and the first character posi-
tion is either; “-“ if the value is negative, or it is “+” if the value
is positive. For example, if the data’s value is 25.5; then the
value +00002550 is sent. All temperatures are in degree C
and all pressures are in PSIA. A mode such as slide valve
mode is returned as an integer value that represents the mode
it is in. For example, a +00000000 is sent if it is in manual, or
a +00000100 is sent if it is in automatic, or a +00000200 is
sent if it is in remote. The value zero +00000000 is used to
represent an “OFF” status and a “DISABLED” option. The value
one +00000100, which is received as a 1, is used to repre-
sent an “ON” status and an “ENABLED” option. Setpoints are
only changed if the value sent is within the acceptable range.
Reference the “Frick Quantum Control Panel Setpoints Data
Sheets” publication S90-010 SD for the setpoints default set-
tings and ranges. The checksum is the 2 byte hexadecimal
sum of the each character within the command or returned
answer excluding the command type identifier, ”$”. If the
command’s checksum is replaced with “??”,the Quantum re-
turns a response without using checksum error checking on
the received command. If the Quantum detects a checksum
error, a “N” (Not Acknowledged), the Compressor ID code,
“02”, Carriage return, and Linefeed are returned.
The following is a complete list of available “$” command
types:
COMMAND CODE and DESCRIPTION
D1 = Operating Status Display Page 1.
D2 = Operating Status Display Page 2.
D3 = Operating Status Display Page 3.
D4 = Operating Status Display Page 4.
s0 = Suct. Press. Capacity control Page 0.
s1 = Suct. Press. Capacity control Page 1.
s2 = Suct. Press. Capacity control Page 2.
p0 = Proc. Temp. Capacity Control Pg.0.
p1 = Proc. Temp. Capacity Control Pg.1.
p2 = Proc. Temp. Capacity Control Pg.2.
p3 = Proc. Temp. Capacity Control Pg.3.
d0 = Disch. Press. Capacity control Page 0.
d1 = Disch. Press. Capacity control Page 1.
d2 = Disch. Press. Capacity control Page 2.
d3 = Disch. Temp. Capacity control Page 3.
d4 = Disch. Temp. Capacity control Page 4.
d5 = Disch. Temp. Capacity control Page 5.
F1 = Alarms/Shutdowns Annunciation Page 1.
F2 = Alarms/Shutdowns Annunciation Page 2.
F3 = Alarms/Shutdowns Annunciation Page 3.
CT = Compressor start.
CP = Compressor stop.
CL = Compressor load.
CU = Compressor unload.
MM = Compressor mode - manual.
MA = Compressor mode - autocycle.
MR = Compressor mode - remote.
VA = Slide valve mode - automatic.
VR = Slide valve mode - remote.
S2 = Compressor sequence - activate.
S3 = Compressor sequence - deactivate.
T1 = Read a value from the Table.
CS = Change a setpoint in the Table.
The following is a detailed description of each command:
RETURN OPERATING STATUS Page 1 data: $01D1
$ Start of command sequence.
01 Compressor ID code.
D1 Operating Status – Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Suction Pressure
13 Suction Temperature
22 Discharge Pressure
31 Discharge Temperature
40 Oil Pressure
49 Oil Temperature
58 Filter Differential
67 Motor Current
76 FLA%
85 Kilowatts
94 Slide Valve
103 Slide Stop
112 Process Temperature
121 CS (Checksum followed by
Carriage return, Line feed.)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 9
RETURN OPERATING STATUS Page 2 data: $01D2
$ Start of command sequence.
01 Compressor ID code.
D2 Operating Status – Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Alarm Status
13 Shutdown Status
22 Running Status
31 Slide Valve Load
40 Slide Valve Unload
49 Slide Stop Increase
58 Slide Stop Decrease
67 Stop Load/Force Unload Code
76 Separator Temperature
85 Balance Piston Pressure
94 Process Variable
103 Compressor Mode
112 CS (Checksum followed by
Carriage return, Line feed.)
RETURN OPERATING STATUS Page 3 data: $01D3
$ Start of command sequence.
01 Compressor ID code.
D3 Operating Status – Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Communication Port 1 Code
13 Communication Port 2 Code
22 I/O Communication Port Code
31 Capacity Control Mode
40 Process Control
49 Oil Pump Mode
58 Oil Pump Code
67 Oil Heater Code
76 Process Setpoint
85 Slide Valve Mode
94 Slide Stop Mode
103 Runtime Hours
112 CS (Checksum followed by
Carriage return, Line feed.)
RETURN OPERATING STATUS Page 4 data: $01D4
$ Start of command sequence.
01 Compressor ID code.
D4 Operating Status – Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Date as 00/00/00
13 Time as hh:mm:ss
23 Remaining Recycle time as mm:ss
30 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Suction Pressure Capacity Control
Mode 1 & 2 setpoints – Page 0: $01s0
$ Start of command sequence.
01 Compressor ID code.
s0 Suct. Press. Cap. Control Page 0 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Suction Pressure Control Setpoint 1
13 Suct. Press. Upper Prop. Band 1
22 Suct. Press. Lower Prop. Band 1
31 Suct. Press. Upper Dead Band 1
40 Suct. Press. Lower Dead Band 1
49 Suct. Press. Upper Cycle Time 1
58 Suct. Press. Lower Cycle Time 1
67 Suct. Press. Auto Start Setpoint 1
76 Suct. Press. Auto Stop Setpoint 1
85 Suct. Press. Auto Start delay 1
94 Suct. Press. Auto Stop delay 1
103 CS (Checksum followed by
Carriage return, Line feed.)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 10
RETURN Suction Pressure Capacity Control
Mode 1 & 2 setpoints – Page 1: $01s1
$ Start of command sequence.
01 Compressor ID code.
s1 Suct. Press. Cap. Control Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Suction Pressure Control Setpoint 2
13 Suct. Press. Upper Prop. Band 2
22 Suct. Press. Lower Prop. Band 2
31 Suct. Press. Upper Dead Band 2
40 Suct. Press. Lower Dead Band 2
49 Suct. Press. Upper Cycle Time 2
58 Suct. Press. Lower Cycle Time 2
67 Suct. Press. Auto Start Setpoint 2
76 Suct. Press. Auto Stop Setpoint 2
85 Suct. Press. Auto Start delay 2
94 Suct. Press. Auto Stop delay 2
103 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Suction Pressure Capacity Control
Mode 1 & 2 setpoints – Page 2: $01s2
$ Start of command sequence.
01 Compressor ID code.
s2 Suct. Press. Cap. Control Page 2 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Suct. Press. Stop Load 1
13 Suct. Press. Force Unload 1
22 Suct. Press. Low Alarm 1
31 Suct. Press. Low Shutdown 1
40 Suct. Press. Low Alarm delay 1
49 Suct. Press. Low Shutdown delay 1
58 Suct. Press. Stop Load 2
67 Suct. Press. Force Unload 2
76 Suct. Press. Low Alarm 2
85 Suct. Press. Low Shutdown 2
94 Suct. Press. Low Alarm delay 2
103 Suct. Press. Low Shutdown delay 2
112 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Process Temperature Capacity Control
Mode 1 & 2 setpoints – Page 0: $01p0
$ Start of command sequence.
01 Compressor ID code.
p0 Proc. Temp. Cap. Control Page 0 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Process Temperature Control 1
13 Proc. Temp. Upper Prop. Band 1
22 Proc. Temp. Lower Prop. Band 1
31 Proc. Temp. Upper Dead Band 1
40 Proc. Temp. Lower Dead Band 1
49 Proc. Temp. Upper Cycle Time 1
58 Proc. Temp. Lower Cycle Time 1
67 Proc. Temp. Auto Start Setpoint 1
76 Proc. Temp. Auto Stop Setpoint 1
85 Proc. Temp. Auto Start delay 1
94 Proc. Temp. Auto Stop delay 1
103 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Process Temperature Capacity Control
Mode 1 & 2 setpoints – Page 1: $01p1
$ Start of command sequence.
01 Compressor ID code.
p1 Proc. Temp. Cap. Control Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Process Temperature Control 2
13 Proc. Temp. Upper Prop. Band 2
22 Proc. Temp. Lower Prop. Band 2
31 Proc. Temp. Upper Dead Band 2
40 Proc. Temp. Lower Dead Band 2
49 Proc. Temp. Upper Cycle Time 2
58 Proc. Temp. Lower Cycle Time 2
67 Proc. Temp. Auto Start Setpoint 2
76 Proc. Temp. Auto Stop Setpoint 2
85 Proc. Temp. Auto Start delay 2
94 Proc. Temp. Auto Stop delay 2
103 CS (Checksum followed by
Carriage return, Line feed.)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 11
RETURN Process Temperature Capacity Control
Mode 1 & 2 setpoints – Page 2: $01p2
$ Start of command sequence.
01 Compressor ID code.
p2 Proc. Temp. Cap. Control Page 2 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Proc. Temp. Stop Load 1
13 Proc. Temp. Force Unload 1
22 Proc. Temp. Low Alarm 1
31 Proc. Temp. Low Shutdown 1
40 Proc. Temp. Low Alarm delay 1
49 Proc. Temp. Low Shutdown delay 1
58 Proc. Temp. Stop Load 2
67 Proc. Temp. Force Unload 2
76 Proc. Temp. Low Alarm 2
85 Proc. Temp. Low Shutdown 2
94 Proc. Temp. Low Alarm delay 2
103 Proc. Temp. Low Shutdown delay 2
112 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Process Temperature Capacity Control
Mode 1 & 2 setpoints – Page 3: $01p3
$ Start of command sequence.
01 Compressor ID code.
p3 Proc. Temp. Cap. Control Page 3 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 ProcT. Low Suct. Stop Load 1
13 ProcT. Low Suct. Force Unload 1
22 ProcT. Low Suct. Alarm 1
31 ProcT. Low Suct. Shutdown 1
40 ProcT. Low Suct. Alarm delay 1
49 ProcT. Low Suct. Shutdown delay 1
58 ProcT. Low Suct. Stop Load 2
67 ProcT. Low Suct. Force Unload 2
76 ProcT. Low Suct. Alarm 2
85 ProcT. Low Suct. Shutdown 2
94 ProcT. Low Suct. Alarm delay 2
103 ProcT. Low Suct. Shutdown delay 2
112 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 0: $01d0
$ Start of command sequence.
01 Compressor ID code.
d0 Disch. Press. Cap. Control Page 0 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Discharge Pressure Control 1
13 Disch. Press. Upper Prop. Band 1
22 Disch. Press. Lower Prop. Band 1
31 Disch. Press. Upper Dead Band 1
40 Disch. Press. Lower Dead Band 1
49 Disch. Press. Upper Cycle Time 1
58 Disch. Press. Lower Cycle Time 1
67 Disch. Press. Auto Start Setpoint 1
76 Disch. Press. Auto Stop Setpoint 1
85 Disch. Press. Auto Start delay 1
94 Disch. Press. Auto Stop delay 1
103 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 1: $01d1
$ Start of command sequence.
01 Compressor ID code.
d1 Disch. Press. Cap. Control Page 1 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Discharge Pressure Control 2
13 Disch. Press. Upper Prop. Band 2
22 Disch. Press. Lower Prop. Band 2
31 Disch. Press. Upper Dead Band 2
40 Disch. Press. Lower Dead Band 2
49 Disch. Press. Upper Cycle Time 2
58 Disch. Press. Lower Cycle Time 2
67 Disch. Press. Auto Start Setpoint 2
76 Disch. Press. Auto Stop Setpoint 2
85 Disch. Press. Auto Start delay 2
94 Disch. Press. Auto Stop delay 2
103 CS (Checksum followed by
Carriage return, Line feed.)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 12
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 2: $01d2
$ Start of command sequence.
01 Compressor ID code.
d2 Disch. Press. Cap. Control Page 2 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Disch. Press. Stop Load 1
13 Disch. Press. Force Unload 1
22 Disch. Press. Low Alarm 1
31 Disch. Press. Low Shutdown 1
40 Disch. Press. Low Alarm delay 1
49 Disch. Press. Low Shutdown delay 1
58 Disch. Press. Stop Load 2
67 Disch. Press. Force Unload 2
76 Disch. Press. Low Alarm 2
85 Disch. Press. Low Shutdown 2
94 Disch. Press. Low Alarm delay 2
103 Disch. Press. Low Shutdown delay 2
112 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Discharge Temperature Capacity Control
Mode 1 & 2 setpoints – Page 3: $01d3
$ Start of command sequence.
01 Compressor ID code.
d3 Disch. Temp. Cap. Control Page 3 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Discharge Temperature Control 1
13 Disch. Temp. Upper Prop. Band 1
22 Disch. Temp. Lower Prop. Band 1
31 Disch. Temp. Upper Dead Band 1
40 Disch. Temp. Lower Dead Band 1
49 Disch. Temp. Upper Cycle Time 1
58 Disch. Temp. Lower Cycle Time 1
67 Disch. Temp. Auto Start Setpoint 1
76 Disch. Temp. Auto Stop Setpoint 1
85 Disch. Temp. Auto Start delay 1
94 Disch. Temp. Auto Stop delay 1
103 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Discharge Temperature Capacity Control
Mode 1 & 2 setpoints – Page 4: $01d4
$ Start of command sequence.
01 Compressor ID code.
d4 Disch. Temp. Cap. Control Page 4 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Discharge Temperature Control 2
13 Disch. Temp. Upper Prop. Band 2
22 Disch. Temp. Lower Prop. Band 2
31 Disch. Temp. Upper Dead Band 2
40 Disch. Temp. Lower Dead Band 2
49 Disch. Temp. Upper Cycle Time 2
58 Disch. Temp. Lower Cycle Time 2
67 Disch. Temp. Auto Start Setpoint 2
76 Disch. Temp. Auto Stop Setpoint 2
85 Disch. Temp. Auto Start delay 2
94 Disch. Temp. Auto Stop delay 2
103 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 5: $01d5
$ Start of command sequence.
01 Compressor ID code.
d5 Disch. Temp. Cap. Control Page 5 command.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Disch. Temp. Stop Load 1
13 Disch. Temp. Force Unload 1
22 Disch. Temp. Low Alarm 1
31 Disch. Temp. Low Shutdown 1
40 Disch. Temp. Low Alarm delay 1
49 Disch. Temp. Low Shutdown delay 1
58 Disch. Temp. Stop Load 2
67 Disch. Temp. Force Unload 2
76 Disch. Temp. Low Alarm 2
85 Disch. Temp. Low Shutdown 2
94 Disch. Temp. Low Alarm delay 2
103 Disch. Temp. Low Shutdown delay 2
112 CS (Checksum followed by
Carriage return, Line feed.)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 13
RETURN Alarms & Shutdowns – Page 1 $01F1
$ Start of command sequence.
01 Compressor ID code.
F1 Failure Annunciation command Page 1.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Message Code 1
7 Date 1 as mm/dd/yy
15 Time 1 as hh:mm:ss
23 Space
24 Message Code 2
27 Date 2 as mm/dd/yy
35 Time 2 as hh:mm:ss
43 Space
44 Message Code 3
47 Date 3 as mm/dd/yy
55 Time 3 as hh:mm:ss
63 Space
64 Message Code 4
67 Date 4 as mm/dd/yy
75 Time 4 as hh:mm:ss
83 Space
84 Message Code 5
87 Date 5 as mm/dd/yy
95 Time 5 as hh:mm:ss
103 Space
104 Message Code 6
107 Date 6 as mm/dd/yy
115 Time 6 as hh:mm:ss
123 Space
124 CS (Checksum followed by
Carriage return, Line feed.)
RETURN Alarms & Shutdowns – Page 2 $01F2
$ Start of command sequence.
01 Compressor ID code.
F2 Failure Annunciation command Page 2.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Message Code 7
7 Date 7 as mm/dd/yy
15 Time 7 as hh:mm:ss
23 Space
24 Message Code 8
27 Date 8 as mm/dd/yy
35 Time 8 as hh:mm:ss
43 Space
44 Message Code 9
47 Date 9 as mm/dd/yy
55 Time 9 as hh:mm:ss
63 Space
64 Message Code 10
67 Date 10 as mm/dd/yy
75 Time 10 as hh:mm:ss
83 Space
84 Message Code 11
87 Date 11 as mm/dd/yy
95 Time 11 as hh:mm:ss
103 Space
104 Message Code 12
107 Date 12 as mm/dd/yy
115 Time 12 as hh:mm:ss
123 Space
124 CS (Checksum followed by
Carriage return, Line feed.)
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 14
RETURN Alarms & Shutdowns – Page 3 $01F3
$ Start of command sequence.
01 Compressor ID code.
F3 Failure Annunciation command Page 3.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Message Code 13
7 Date 13 as mm/dd/yy
15 Time 13 as hh:mm:ss
23 Space
24 Message Code 14
27 Date 14 as mm/dd/yy
35 Time 14 as hh:mm:ss
43 Space
44 Message Code 15
47 Date 15 as mm/dd/yy
55 Time 15 as hh:mm:ss
63 Space
64 Message Code 16
67 Date 16 as mm/dd/yy
75 Time 16 as hh:mm:ss
83 Space
84 Message Code 17
87 Date 17 as mm/dd/yy
95 Time 17 as hh:mm:ss
103 Space
104 Message Code 18
107 Date 18 as mm/dd/yy
115 Time 18 as hh:mm:ss
123 Space
124 CS (Checksum followed by
Carriage return, Line feed.)
RETURN DATA VALUE FROM TABLE $IDT1
$ Start of command sequence.
ID Compressor ID code.
T1 Return the value of a Table address.
0000 Frick Address(s) of data value in Table
up to 16 different addresses
can be requested
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character Description
Position of returned data
1 “A” Acknowledge
2 “01” Compressor ID code.
4 Value(s) of requested data.
CS (Checksum followed by
Carriage return, Line feed.)
CHANGE SETPOINT COMMAND: $IDCS
$ Start of command sequence.
ID Compressor ID code.
CS Change Table address’s setpoint value.
0000 Frick’s Table address of the setpoint.
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
CLEAR ALARMS COMMAND: $IDCA
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
NOTE: The following commands are for remote control of a
compressor. A compressor should be in both remote compres-
sor mode and remote slide valve or capacity mode for remote
control.
COMPRESSOR START COMMAND: $IDCT
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
COMPRESSOR STOP COMMAND: $IDCP
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
SLIDE VALVE CONTROL COMMANDS: $IDCLXX
$IDCUXX
$ Start command sequence.
ID Compressor ID code.
C Slide Valve/Slide Stop command.
L Load Slide valve command.
U Unload slide valve command.
XX = 00 Turns selected output off.
XX = 01 to 15 Turns selected output on
for XX seconds.
If the command was $01CL00, then the load slide valve
output on compressor #1 would be turned off. If the
command was $01CL05, then the load slide valve output on
compressor #1 would be turned on for 5 seconds, and would
then automatically turn off. NOTE: the slide valve must be
in the remote mode for this command to be executed.
RETURNED ANSWER (for L or U commands): A01
Character Description
Position of returned data
1 Acknowledge of command sent.
2,3 ID code of compressor.
(Carriage return, line feed.)
COMPRESSOR MODE MANUAL COMMAND: $IDMM
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 15
COMPRESSOR MODE AUTOCYCLE COMMAND: $IDMA
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
COMPRESSOR MODE REMOTE COMMAND: $IDMR
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
SLIDE VALVE MODE AUTOMATIC COMMAND: $IDVA
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
SLIDE VALVE MODE REMOTE COMMAND: $IDVR
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
COMPRESSOR SEQUENCE ACTIVATE COMMAND: $IDS2
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
COMPRESSOR SEQUENCE – DEACTIVATE COMMAND: $IDS3
followed by the “CS”,”CR”
RETURNED ANSWER: - “A” followed by the “ID”,
“CR”, “LF” if successful.
ALLEN-BRADLEY COMMUNICATION
To provide for the reading and writing of data to Quantum
panels using Allen-Bradley communication, the Quantum has
a Allen-Bradley DF1 communication driver that recognizes
both half-duplex and full duplex SLC 500 protected typed
logical read and write commands. This is a Leader /
Follower multi-drop communication method. The Quantum
talks Allen-Bradley SLC protocol and is setup to be a
Allen-Bradley SLC 500 follower station. The customer’s
PLC or DCS must be setup to initiate the reading and
writing of data to a Quan-tum. The Quantum’s ID number
is used as it’s station ad-dress and the target node. With
the AB PLC, the MSG (Mes-sage) instruction is used to
send read and write requests. A DCS (Distributed Control
System) will use a SLC 500 DF1 protocol driver to send
protected typed logical read and pro-tected typed logical
write requests to a Quantum. Fifty (50) data elements can
be read with one read. The most desired data (information
on the “Operating Status” display) exists in a fifty (50)
element data area. Setpoints are changed by sending a
write command to one element. Changing a set-point
causes the Quantum to save the new setpoint to
EPROM memory (nonvolatile memory). Be careful not to
continuously request a setpoint change. Keeping the Quan-
tum busy writing to EPROM memory will interfere with the
Quantum communicating to it’s I/O Boards. A communica-
tion failure to an I/O board will cause the compressor to
shutdown. Control commands such as starting the com-
pressor are also sent with a write command. For more detail
and a list of the data, reference the “Quantum Data Table”
section. For details about the actual protocol, reference the
AB publication 1770-6.5.16 “DF1 Protocol and Command
Set Reference Manual”.
The Quantum can be connected to the Data Highway (DH)
by wiring the Quantum’s serial port (Com-2) to a serial de-
vice on the DH such as an internal port of a PLC that sup-
ports the Data Highway protocol like the SLC 5/04.
Quantums can be on a multidrop link (wired to other
Quantums). If RS-422 or RS-485 is used as in a multidrop
link, an adapter card can be used to convert an RS-232 to
an RS-422 or RS-485 serial port.
Because overrun can occur and result in the Quantum peri-
odically missing characters, the baud rate and commands
should be set up to produce the more desired throughput.
The leader station should have the Stop Bit set to 1, Parity
set to none, Duplicate Detect disabled, and Error Detect set
for BCC.
When communication is between either your programming
software and a Quantum or an Allen-Bradley PLC and a
Quantum on a multidrop link, the devices depend on a DF1
Leader to give each of them polling permission to transmit
in a timely manner. As the number of Quantum followers
in-crease on the link, the time between when the Quantum
is polled also increases. This increase in time may
become larger if you are using low baud rates. As these time
periods grow the time-outs such as the message time-out,
poll time-out and reply time-out may need to be changed
to avoid loss of communication.
ACK Time-out - The amount of time in 20 milliseconds in-
crements that you want the processor to wait for an acknowl-
edgment to the message it has sent before the processor
retries the message or the message errors out.
Reply Message Wait Time - Define the amount of time in
20 millisecond increments that the leader station will wait
after receiving an ACK (to a leader-initiate message) be-
fore polling the remote station for a reply. Choose a time
that is, at minimum, equal to the longest time that a remote
station needs to format a reply packet. Some remote sta-
tions can format reply packets faster than others.
Message Time-out - Defines the amount of time in sec-
onds that the message will wait for a reply. If this time elapses
without a reply, the error bit is set, indicating that the instruc-
tion timed out. A time-out of 0 seconds means that there is
no timer and the message will wait indefinitely for a reply.
Valid range 0255 seconds.
NOTE: Make sure the Allen-Bradley PLC and the pro-
gramming software is the most recent software revision.
Some revisions have been made that affect doing the
SLC Typed Logical Read/Write Message Command.
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 16
SLC500 SUGGESTED SETUP
CHANNEL CONFIGURATION
Configure the communication channel – Channel 0:
Current Communication Mode: System
Communication Driver: DF1 Half-Duplex Leader or DF1 Full-
Duplex
Baud Rate: 4800 (suggested)
Stop Bits: 1
Duplicate Detect: Disabled
ACK Time-out (x20ms): 30
Message Retries: 3
Parity: None
Station Address (Source ID): 5 (Leader's DF1 selected ID#)
Error Detect: BCC
RTS off Delay (x20ms): 0
RTS Send Delay (x20ms): 0
PreSend Time Delay (x1 ms): 0
Control Line: No Handshaking
Polling Mode: Message Based (do not allow follower to
initiate messages)
Priority Polling Range - Low: 255, High: 0
Normal Polling Range - Low: 255, High: 0
Normal Poll Group Size: 0
Reply Message Wait Time (x20ms): 20
System Mode Driver: DF1 Half-Duplex Leader or DF1 Full-
Duplex
User Mode Driver: Generic ASCII
Write Protect: DISABLED
Mode Changes: DISABLED
Mode Attention Character: \0x1b (default)
System Mode Character: S (default)
User Mode Character: U (default)
Edit Resource/File Owner Time-out (Sec): 60
Passthru Link ID (decimal): 1
READ MESSAGE SETUP EXAMPLE
Read/Write Message
Type: Peer-To-Peer
Read/Write: Read
Target Device: 500 CPU
Local/Remote: Local
Control Block: N11:0
Control Block Length: 14
Channel: 0
Target Node: 2 (002) (this is Quantum’s Panel ID)
Local File Address: N12:0
Target File Address/Offset: N10:0
Message Length in Elements: 50
Message Time-out (seconds): 15
WRITE MESSAGE SETUP EXAMPLE
Read/Write Message
Type: Peer-To-Peer
Read/Write: Write
Target Device: 500 CPU
Local/Remote: Local
Control Block: N11:0
Control Block Length: 14
Channel: 0
Target Node: 2 (002) (this is Quantum’s Panel ID)
Local File Address: N12:0
Target File Address/Offset: N55:3
Message Length in Elements: 1
Message Time-out (seconds): 15
Enter 20 into N12:0 to send the command to set the com-
pressor in remote mode.
PLC-5/30 - SUGGESTED SETUP
Channel 0 - 25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible.
NOTE: Channel 0 is optically coupled (provides high
electrical noise immunity) and can be used with most
RS-422A equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to comply
with RS-423 requirements
The PLC-5’s switch 2 is used to select RS-232C, RS-422A,
or RS-423. Channel 0 can be wired for RS-422.
Following is the pin connections showing how to wire the
PLC-5 channel 0 connector to the Quantum for RS-422 com-
munication:
PLC-5 CH0 Quantum Com2
Pin 2 (TXD.OUT+) Pin 1 (-RX)
Pin 3 (RXD.IN+) Pin 3 (-TX)
Pin 14 (TXD.OUT-) Pin 2 (+RX)
Pin 16 (RXD.IN-) Pin 4 (+TX)
Channel 0 Setup:
Port Maximum Cable Length
RS-232C 15 m (50 ft)
RS-422A 61 m (200 ft)
RS-423 61 m (200 ft)
Important guidelines:
When channel 0 is configured for RS-422A compatibility,
do not use terminating resistors anywhere on the link.
When channel 0 is configured for RS-422A (compatible)
and RS-423, do not go beyond 61 m (200 ft). This dis-
tance restriction is independent from the transmission rate.
CHANNEL CONFIGURATION
Channel 0 = System (LEADER) for half-duplex or
System (Point-To-Point) for full-duplex
Remote Mode Change: DISABLED
Mode attention Char: \0x1b
System mode char: S
User mode char: U
Baud rate: 4800
Stop bits: 1
Parity: None
Station address: 5 (Leader's DF1 ID#)
Control line: No Handshaking
Reply Msg Wait (20ms):
ACK time-out (20ms):
DF1 retries: 3
Msg appl time-out (30 secs):2
Error detect: BCC
RTS send delay (20ms): 0
RTS off delay (20ms): 0
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 17
Polling mode: Message Based (Do Not Allow Follower to
initiate messages)
Leader Message Transmit: Between Station Polls
System (Point-To-Point) additional setup: Duplicate Detect:
OFF
NAK Receive:0
DF1 ENQS:0
READ MESSAGE SETUP EXAMPLE
Instruction Entry for Message Block MG14:0:
Communication Command: SLC Typed Logical Read
PLC-5 Data Table Address: N9:3
Size in Elements: 20
Local/Remote: Local
Local Node Address: 004 (Quantum Panel’s ID)
Destination Data Table Address: N10:1
Port Number: 0
MODBUS COMMUNICATION
The Quantum provides the capability to interface with other
devices that support serial data communications using the
Modbus ASCII protocol. This is a Leader / Follower
multidrop communication method. The Quantum is setup to be
a Modbus ASCII Follower. The customer’s PLC or DCS must
be setup as a Modbus ASCII Leader. The Leader initiates
the reading and writing of data to a Quantum. The
Quantum’s ID number is used as the Modbus Follower
address. The Leader uses Function Code 3 (Read Holding
Registers) to send a request to read data from the Quantum
and Function Code 6 (Load Register) to request to change a
setpoint or to send a command such as starting the
compressor. Fifty (50) data elements can be read with one
read request. The most desired data (information on the
“Operating Status” display) exists in a fifty (50) element
data area. The address references are numbered relative to
the Frick addresses in the Quantum Data Table. For example,
to reference Frick’s data address 128 enter the decimal value
128 for the Modbus Follower Address. The Quantum only
ac-cepts one value with a Load Register request.
Changing a setpoint causes the Quantum to save the
new setpoint to EPROM memory (nonvolatile memory). Be
careful not to con-tinuously request a setpoint change.
Keeping the Quantum busy writing to EPROM memory will
interfere with the Quan-tum communicating to it’s I/O Boards.
A communication failure to an I/O board will cause the
compressor to shutdown. For more detail and a list of the
data, reference the “Quantum Data Table” section. For details
about the actual protocol, reference the Gould publication
PO-MBUS-300 Gould odbus Protocol Reference Manual”.
PORT CONFIGURATION OF THE LEADER:
7 Bits per Character
No Parity
1 Stop Bit
No Handshake
HYPERTERMINAL SETUP
A modem or direct connection from a Comm port of a computer
running Windows 9x/NT can be used to connect to Com-2 of the
Quantum. From the HyperTerminal setup, select the type of con-
nection (i.e. Standard Modem, Direct to Com-1, etc.)
Setup the port settings to coincide with the Quantum’s Com-2
port settings:
Bits per second: (User changeable at Quantum)
Data Bits: 8
Parity: None
Stop bits: 1
Flow Control: None
Set up the function, arrow, and ctrl keys to act as: Terminal
Keys. And select ANSII emulation. If using the Frick “$” pro-
tocol, the check box to send line ends with line feeds should
not be checked. Check that the ID code used in a command
string coincides with the panel’s ID.
CONVERTING AN RS-232 SERIAL PORT TO
RS-422 OR RS-485
An adapter card can be used to convert an RS-232 serial
port to an RS-422 or RS-485 serial port. With RS-422 or
RS-485, the cable length can be extended to 5000 feet and
several Quantums can be multidropped. We have used both
an Opto 22 AC7A/B and an Opto 22 AC422 adapter card.
They can be wired to use either RS-422 or RS-485.
Opto 22 AC7A/B
The AC7A/B card is installed external to a computer and
requires wiring to a power supply. For example, it can be
used in a standalone panel along with a Allen Bradley SLC
5/04 or maybe along with an external modem. Keeping the
jumpers installed the same way they are received from the
factory, it is easy to wire for either RS-422 or RS-485.
Following is the pin connections showing how to wire a DB9
connector on this adapter card to the Quantum for RS-422
communication:
Quantum
COMM2 DB9
15
24
39
48
Following is the pin connections showing how to wire for
RS-485 to the terminal connections on this adapter card
from the Quantum:
Quantum Terminal
1 (-RX/-TX) TO+
2 (+RX/+TX) FO-
The card can be connected RS-232 to another device. Fol-
lowing is the pin connections showing how to wire the 25-
pin RS-232 connector on this adapter card to a 9-Pin con-
nector of the SLC 5/04:
DB9 DB25
57
33
22
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 18
QUANTUM DATA TABLE
ALLEN-BRADLEY AND MODBUS DATA ACCESS
Data to and from the Quantum are integer values with one
decimal field assumed unless shown otherwise or the com-
mand is sent to select two decimal fields. For example, if the
data’s value is 25.5, then the value 255 is sent. All tempera-
tures are in degree C and all pressures are in PSIA unless
the command is sent to select the units of the panel. A mode
such as slide valve mode is sent as an integer value that
represents the mode it is in. For example, a zero 0 is sent if
it is in manual, or a 10 is sent if it is in automatic, or a 20 is
sent if it is in remote. The value zero (0) is used to represent
an “OFF” status and a “DISABLED” option. The value one
(1), which is received as a 10, is used to represent an “ON”
status and an “ENABLED” option. Only data values that are
designated as setpoints are modifiable. “Read Only” is used
to help identify what data is not modifiable. The setpoint
range is checked to see if it is an allowed setting. If it is not
allowed, the setting is not changed. Reference the “Frick
Quantum Control Panel Setpoints Data Sheets” publication
S90-010 SD for the setpoints default settings and ranges.
Reference the “Quantum Data Table” for the address listing
and description of data. NOTE: The Frick address is used
to reference the Modbus data.
A command has been provided that selects whether data to
and from the Quantum will be integer values with either one
or two decimal fields assumed. Another command has been
provided that selects whether data to and from the Quan-
tum will be returned in the units that are the default (pres-
sure in PSIA and temperature in Degree C) or in the units
that are selected to display at the panel.
Digital Board 1 (Read Only):
Frick AB Module
Address Address Description of Data Type Value Codes
0 N50:0 Compressor Start Output 0=Off, 1=On
1 N50:1 Compressor Auxiliary Input 0=Off, 1=On
2 N50:2 Oil Pump #1 Start/Run Output 0=Off, 1=On
3 N50:3 Oil Pump #1 Auxiliary Input 0=Off, 1=On
4 N50:4 Slide Valve Load Output 0=Off, 1=On, 2=Off
5 N50:5 Slide Valve Unload Output 0=Off, 1=On, 2=Off
6 N50:6 Slide Stop Increase Output 0=Off, 1=On, 2=Off
7 N50:7 Slide Stop Decrease Output 0=Off, 1=On, 2=Off
8 N50:8 Liquid Injection Output 0=Off, 1=On
9 N50:9 HiVi Liquid Injection Output 0=Off, 1=On
10 N50:10 Economizer Output 0=Off, 1=On
11 N50:11 Balance Piston Output 0=Off, 1=On
12 N50:12 Oil Level Input 0=Off, 1=On
13 N50:13 High Liquid Level from System Input 0=Off, 1=On
14 N50:14 Enclosure Heater Output 0=Off, 1=On
15 N50:15 Hot Gas Bypass Output 0=Off, 1=On
16 N50:16 Aux. #1 Input 0=Off, 1=On
17 N50:17 Aux. #2 Input 0=Off, 1=On
18 N50:18 Process Mode Select Input 0=1st Mode, 1=2nd Mode
19 N50:19 Capacity Control Setpoint #2 Input 0=Mode 1, 1=Mode 2
20 N50:20 Oil Heater Output 0=Off, 1=On
21 N50:21 Alarm Output 0=None, 1=Alarm
22 N50:22 Shutdown Output 0=Shutdown, 1=None
23 N50:23 Power Assist Output 0=Off, 1=On
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP S90-010 CS
Page 19
Digital Board 2 (Read Only):
Frick AB Module
Address Address Description of Data Type Value Codes
24 N50:24 Ready-To-Run Output 0=Off, 1=On
25 N50:25 Remote Enabled Output 0=Off, 1=On
26 N50:26 Remote Start/Run/Stop Input 0=Stop, 1=Start/Run
27 N50:27 Remote Load Input 0=Off, 1=On
28 N50:28 Remote Unload Input 0=Off, 1=On
29 N50:29 In Recycle Delay Output 0=Off, 1=On
30 N50:30 Slide Valve Setpoint #1 Output 0=Off, 1=On
31 N50:31 Slide Valve Setpoint #2 Output 0=Off, 1=On
32 N50:32 Aux. #3 Input 0=Off, 1=On
33 N50:33 Aux. #4 Input 0=Off, 1=On
34 N50:34 Aux. #5 Input 0=Off, 1=On
35 N50:35 Aux. #6 Input 0=Off, 1=On
36 N50:36 Aux. #7 Input 0=Off, 1=On
37 N50:37 Aux. #8 Input 0=Off, 1=On
38 N50:38 Oil Pump #2 Start Output 0=Off, 1=On
39 N50:39 Oil Pump #2 Auxiliary Input 0=Off, 1=On
40 N50:40 Permissive Start Input 0=Off, 1=On
41 N50:41 Main Oil Injection Disch. Temp. Output 0=Off, 1=On
42 N50:42 Dx Circuit #1 Output 0=1st Mode, 1=2nd Mode
43 N50:43 Dx Circuit #2 Output 0=Mode 1, 1=Mode 2
44 N50:44 Condenser Control #1 Output 0=Off, 1=On
45 N50:45 Condenser Control #2 Output 0=None, 1=Alarm
46 N50:46 Condenser Control #3 Output 0=None, 1=Shutdown
47 N50:47 Condenser Control #4 Output 0=Off, 1=On
FRICK QUANTUM CONTROL PANEL
COMMUNICATIONS SETUP
S90-010 CS
Page 20
CALCULATED/STATUS (READ ONLY):
Frick AB
Address Address Description of Data Value Codes
97 N10:1 Motor Full Load Amps %
99 N10:3 Filter Differential
102 N10:6 Process Setpoint (Actual)
103 N10:7 Process Control Mode 0 = Suction Pressure Control Mode 1
1 = Suction Pressure Control Mode 2
2 = Temperature Control Mode 1
3 = Temperature Control Mode 2
4 = Discharge Press. Control Mode 1
5 = Discharge Press. Control Mode 2
6 = Discharge Temp. Control Mode 1
7 = Discharge Temp. Control Mode 2
105 N10:9 Compressor Mode 0 = Manual
1 = Automatic cycling
2 = Remote start
106 N10:10 Alarm Status 0=Off, 1=On
107 N10:11 Shutdown Status 0=Off, 1=On
108 N10:12 Language 0=English
1=Danish
2=German
3=Spanish
4=French
109 N10:13 Temperature 0=Fahrenheit
1=Celsius
110 N10:14 Pressure 0=PSIA
1=PSIG
2=BarA
3=KPAA
4=Bar
111 N10:15 Compressor Running Status 0=Off, 1=Running, 2=Starting
113 N10:17 Compressor Model 0=RWBII
1=RXB
2=RXF
3=Other Compressor Manufacturer
4= GSV II
5=RDB 4-Step
6=RDB 3-Step
7=GST
9=GSB
10= Gram Other
11=SC
12=YLC
13=York-S7
14=RWF
114 N10:18 Pump Operation 0=No Pump
1=Prelube
2=Cycling
3=FullTime
4=Shaft Driven with Aux.
5=Shaft Driven
115 N10:19 Differential Pressure
116 N10:20 Slide Valve Mode 0 = Manual
1 = Automatic
2 = Remote
3 = Remote Control Setpoint
117 N10:21 Slide Stop Mode 0 = Manual
1 = Automatic
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Frick Quantum Control Panel Installation guide

Type
Installation guide

Below you will find brief information for Quantum 3.5x/4.0x. This service manual provides setup and communication information for the Frick Quantum Control Panel. It covers communication protocols, including Frick's "#" and "$" protocols, as well as Allen-Bradley and Modbus communication. The manual includes checklists for setting up communication, details on wiring diagrams for RS-485 and RS-422 connections, and troubleshooting tips. It also features data tables for Allen-Bradley and Modbus communication. The document also includes information about main board communications jumpers and data access information.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI