8830139 - REV E 9/19 PAGE 1 OF 5
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
Features
 6 Programmable Initiating Device Circuits
 System is expandable to 192 input circuits using the IDC-6
expansion module
 5.0 Amp Power Supply
 
 Strobe Synchronization for Gentex, AMSECO, System Sensor
and Cooper/Wheelock
 One programmable auxiliary output rated at 1.0 A
 4 x 20 LCD display with system LEDs for clear system status
 
 Built-in Ethernet Connection with listed IP Communicator
 
 Service Reminder E-mails
Dimensions 
Enclosure 18 gauge cold rolled steel with removable locked
door with Lexan viewing window
AC Mains 5.0 amp @ 120 VAC 60 Hz
2.0 amp @ 240 VAC 50 Hz
Battery 70 mA Standby

Temperature
and Humidity
Range


Standards NFPA 70, 72
Description
The PFC-4064 Conventional Fire Panel is a compact, expandable panel

the status to a monitoring station. The PFC-4064 panel is a listed and

with UL-864, NFPA-70, and NFPA-72. The panel is provided with


supply provides ample power to meet any jurisdictions requirements

panel has the Potter P-Link for connection to system accessories.
The panel also has a 1.0 Amp auxiliary power output for controlling

The control panel is in a metal cabinet with a key lock and lexan
window for viewing the system status. The printed circuit assembly is
mounted for quick removal and installation to allow the cabinet to be



The system status is clearly displayed and the panel includes a history
buffer for past events. The key pad allows navigation into the system
menu, limited programming and system control. The condition and
events on the panel are clearly displayed to allow the user and installer
to determine the system status.

Technical Specications
LISTED
firealarmresources.com
8830139 - REV E 9/19 PAGE 2 OF 5
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
2-Wire Smoke Detector Compatibility
Detector Model Identier Base Model Identier
SYSTEM SENSOR (Brk) (Max. No. Of Detectors Per Zone Is 20)
1400 A N/A N/A
2400 A N/A N/A
2400TH A N/A N/A
2W-B A N/A N/A
2WT-B A N/A N/A
DETECTION SYSTEM (Max. No. Of Detectors Per Zone Is 25)
DS250 A MB2W/MB2WL A
DS250TH A MB2W/MB2WL A
ESL (Max. No. Of Detectors Per Zone Is 25)
611U S10 601U S00
611UD S10 601U S00
611UT S10 601U S00
612U S10 601U S00
612UD S10 601U S00
 S10 601U S00
611UD S10 609U10 S00
612UD S10 609U10 S00
425C S10 N/A N/A
425CT S10 N/A N/A
HOCHIKI (Max. No. Of Detectors Per Zone Is 25)
SLR-24  HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
NS6-220 
SLR-24H  HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
SIJ-24  HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
firealarmresources.com
8830139 - REV E 9/19 
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
Detector Model Identier Base Model Identier
FENWAL (Max. No. Of Detectors Per Zone Is 25)
CPD-7051 I51FE1 2-WIRE FE51A
PSD-7155 P55FE1 2WRLT FE52A
PSD-7156 P56FE1 2WRB FE55A
All of the above Fenwal detectors and bases can be used in any combination.


POTTER (Max. No. Of Detectors Per Zone Is 25)
CPS-24  SB-46 
 
PS-24H  SB-46 

IS-24  SB-46 

NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.
firealarmresources.com
8830139 - REV E 9/19 PAGE 4 OF 5
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
User Interface
Ethernet/I.P. Connection
P-Link
The PFC-4064 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected


programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, Event History and detector status. An
e-mail may be sent to the panel and the panel will e-mail the event

authorized E-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the Ethernet connection is UL listed as an IP
communicator. The IP communicator is listed to report to the UL
listed Sur-Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of
connection and communication to the monitoring station.
The PFC-4064 has a proprietary communication protocol that


P-Link includes the communication terminals and regulated 24 VDC

following:
IDC-6 – Initiating device circuit expander, provides an additional six

RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) – 16 LED annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) – 10 amp, remote intelligent power supply with 6
NACs, 2 Inputs and a P-Link repeater.
CA-4064 – Class A convertor that converts the NACs and P-Link
connection.
UD-2000 – UL listed, Dual line telephone alarm communicator.
DRV-50 – LED driver expander, used to connect up to 50 LEDs in a
graphic display .
FCB-1000 – Fire communication bridge, provides remote mounting
of the Ethernet connection.
FIB-1000 – Fiber interface module, used to extend P-Link to multi-

RLY- 5
amps 24VDC/125AC.
SPG-1000 – Serial parallel gateway, allows for the connection to a
serial or parallel printer.

information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LEDs:
 AC Power - Green
 Alarm - Red
 Earth Fault - Amber
 Supervisory - Amber
 Silenced - Amber
 Trouble - Amber
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is
opened.
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three panels to share a
single reporting technology.
AE-2 – Two card expansion cabinet.
AE-8 – Eight card expansion cabinet.
AE-14 – Fourteen card expansion cabinet.
firealarmresources.com
8830139 - REV E 9/19 PAGE 5 OF 5
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PFC-4064
Conventional Fire Alarm Control Panel
BOTTOM
LEFT SIDE
TOP
18.60"
18.10"
DEPTH
4.63"
3.95"
14.48"
14.78"
RIGHT SIDE
Dimensions
Ordering Information
Model Description Stock No.
PFC-4064 Fire Alarm Control Panel 
Replacement Board 
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

Potter PFC-4064 Conventional Fire Alarm Control Panel User manual

Category
Fire protection
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI