Marantec FS 345 Owner's manual

Type
Owner's manual

This manual is also suitable for

Marantec FS 345: Control your door systems with mechanical limit switches or inductive proximity switches with ease. Ideal for use in fireproof hydraulic drives, this system provides reliable operation and safety features.

Marantec FS 345: Control your door systems with mechanical limit switches or inductive proximity switches with ease. Ideal for use in fireproof hydraulic drives, this system provides reliable operation and safety features.

EN
FS 345 HY Door Controls / Rev.B 0.0 – 1
Control FS 345 HY with FS 101 and
CS 300 FS HY
Assembly and operating instructions
01.2023
www.marantec.com
2 – FS 345 HY Door Controls / Rev. B 0.0
1. Contents
1. Contents 2
2. Information in this document 2
3. General safety instructions 3
4. Overview of products 4
5. Commissioning 5
6. Limit switches 16
7. Programming with the LCD monitor 16
8. Navigator (LCD monitor only) 18
9. Overview of functions 20
10. Rechargeable battery and battery charger 28
11. Technical data 30
12. Maintenance 30
13. EC Declaration of Incorporation 31
Original operating instructions
− Protectedbycopyright.
− Nopartoftheseinstructionsmaybereproducedwithout
our prior approval.
− Subjecttoalterationsintheinterestoftechnicalprogress.
− Alldimensionsaregiveninmillimetres.
− Theillustrationsarenottruetoscale.
Key to symbols
DANGER!
Safetynoticeindicatingadangerthatwilldirectlyresultin
deathorsevereinjury.
WARNING!
Safetynoticeindicatingadangerthatcouldresultindeath
orsevereinjury.
CAUTION!
Safetynoticeindicatingadangerthatcanresultinslightor
moderateinjuries.
NOTICE
Safetynoticeindicatingadangerthatcanresultindamage
to property or in irreparable damage to the product.
CHECK
Reference to a check that needs to be carried out.
REFERENCE
Reference to separate documents that must be observed.
Instruction requiring actionInstruction requiring action
− List,itemisation
ÔReference to other sections of this document
2. Information in this document
FS 345 HY Door Controls / Rev.B 0.0 – 3
EN
3. General safety instructions
DANGER!
Failure to comply with the documentation could
result in life-threatening danger!
Be sure to follow all the safety instructions in this docu-
Be sure to follow all the safety instructions in this docu-
ment.
ment.
Warranty
The function and safety of the equipment is only guaranteed if
the warning and safety instructions included in these operat-
ing instructions are adhered to.
Marantec Legden GmbH + Co. KG is not liable for personal
injuryordamagetopropertyiftheseoccurasaresultofthe
warnings and safety advice being disregarded.
Marantec Legden does not accept any liability or warranty
for damage due to the use of non-approved spare parts and
accessories.
Intended use
TheFS345HYcontrolsareintendedexclusivelyforcontrol-
ling door systems with mechanical limit switches or inductive
proximityswitches.
Target group
Onlyqualiedandtrainedelectriciansmayconnect,pro-
gramme and service the control.
Qualiedandtrainedelectriciansmustmeetthefollowing
requirements:
− Knowledgeofthegeneralandspecicsafetyandaccident
preventionregulations,
− Knowledgeoftherelevantelectricalregulations,
− Trainingintheuseandcareofappropriatesafetyequip-
ment,
− Capableofrecognisingthedangersassociatedwithelec-
tricity.
Instructions regarding installation and connection
− ThecontrolisdesignedwithXtypeterminals.
− Thecontrolmustbedisconnectedfromtheelectricity
supply before carrying out any electrical work. It must be
ensured that the electricity supply remains disconnected for
the duration of the work.
− Localprotectiveregulationsmustbecompliedwith.
Information concerning operation
− Unauthorisedpersons(particularlychildren)shouldnotbe
allowedtoplaywithpermanentlyinstalledadjustingor
control devices.
− Keepremotecontrolbeyondthereachofchildren.
4 – FS 345 HY Door Controls / Rev. B 0.0
General safety instructions
− Toenablefault-freeoperationtobeguaranteed,itis
imperative that the rechargeable battery be replaced after
every two years of operation. If this maintenance instruc-
tionisdisregarded,thefunctionalsafetyofthesystemand
thus also the safety of buildings and persons cannot be
guaranteed.
− Toensurethatthesystemalwaysfunctionsconsistently,the
realarmfunctionmustbecheckedonceeveryfourweeks.
In order to check at the same time that the rechargeable
batteryalsofunctionscorrectly,thecontrolmustbediscon-
nectedfromthemains.Inthisway,theemergencyfunction
can be checked to ensure that the door is closed automati-
callybytheauxiliarymotor.
− Emergencyoperationisnotpossibleifthereisafaultinthe
safety circuit of the door operator.
− Toavoidadeepdischargeoftherechargeablebattery,the
batteryshouldnotbeconnectedtotheFS101unituntil
thesystemisputintooperationforthersttime.Ifdeep
dischargeoccurs,thebatterycannotberechargedagain
and must be replaced immediately.
4. Overview of products
4.1 4.1 Product descriptionProduct description
TheFS345HYcontrolscanbeusedinconnectionwithre-
proof hydraulic drives.
TheFS345HYcontrolsconsistofanCS300FSHYdoorcon-
trolunit,anFS101auxiliarycircuitboardandarechargeable
battery as a backup supply for the circuit boards and solenoid
valves.
Inthecaseofreorpowercuts,theemergencyrechargeable
battery provides the energy required for the solenoid valves to
hold the door.
Theremodeistriggeredbyacontinuouscommandinthe
realarmcontactoristimeactivatedifthemainspowersup-
plyfails.Inthecaseofre,thedoorcloseswiththeclosing
edgesystemdeactivated,or,optionally,withtheclosingedge
activated.
4.2 4.2 Various optionsVarious options
ThefollowingmodelsoftheFS345HYcontrolscanbesup-
plied:
− FS345HYcontrolsfordeadmanoperation
− FS345HYcontrolsforautomaticoperation
− FS345HYcontrolsforautomaticoperationwiththeclosing
edgesystemactivatedinthecaseofre
The following housing models are available:
− HousingwithOPEN-STOP-CLOSEbuttons
− HousingwithON/OFFkeyswitch
− Housingwithmainswitch
− HousingwithemergencyOFFswitch
The operating instructions describe the connection options
andmodelsoftheFS345HYcontrols.
General safety instructions
FS 345 HY Door Controls / Rev.B 0.0 – 5
EN
4.3 4.3 Product drawing of CS 300 FS HY with FS Product drawing of CS 300 FS HY with FS
101101
K06
K04 K05 K06 K07 K08 K09
K10
K11
K12
circuit board
CS300FSHY
FS101circuit
board
Battery
5. Commissioning
5.1 5.1 GeneralGeneral
Toguaranteethattheequipmentfunctionsproperly,itmust
be ensured that:
− Thedoorisinstalledandoperational.
− Thehydraulicmotorisinstalledandreadyforoperation.
− Thecommandandsafetydevicesareinstalledandreadyfor
operation.
− ThecontrolhousingwiththeFS345HYcontrolisinstalled.
REFERENCE
The relevant manufacturers’ instructions must be adhered to
fortheinstallationofthedoor,thehydraulicmotor,andthe
command and safety devices.
5.2 5.2 Mains connection Mains connection
Preconditions
Toguaranteethatthecontrolfunctionproperly,thefollowing
points must be ensured:
- The mains voltage must correspond to the voltage stated on
the type plate.
- The mains voltage must be the same as the voltage of the
operator.
-Forathree-phasecurrent,aclockwiserotatingeldis
required.
-Forapermanentconnection,anall-polemainswitchmust
be used.
-Forathree-phaseconnection,only3-wayautomaticcircuit
breakers(10A)maybeused.
NOTICE
Malfunctions can occur as a result of incorrect
installation of the control!
Beforeswitchingonthecontrolforthersttime,acheck
must be carried out after completing the wiring to ensure
that all the motor connections at the motor and at the con-
trolissecurelyxed.Allcontrolvoltageinputsaregalvani-
cally isolated from the supply.
6 – FS 345 HY Door Controls / Rev. B 0.0
5.3 5.3 Initial operation FS 101 emergency op-Initial operation FS 101 emergency op-
eration circuit boarderation circuit board
General
TheFS101circuitboardincludesachargerfortherecharge-
able battery and a microprocessor for controlling the solenoid
valves.
ThecircuitboardisconnectedtotheCS300FSHYdoor
control unit in the factory and if it is purchased together with
adooroperator,thecorrectsettingsforthatoperatorarealso
preset in the factory.
Allthatremainstobeconnectedbeforeuseisarealarm,
andtherechargeablebatterymustbeconnectedtotheFS
101 circuit board with a plug.
-+
NOTICE
Malfunctions due to incorrect installation of the
battery!
Topreventdeepdischargeoftherechargeablebattery,
thebatteryshouldnotbeconnectedtotheFS101circuit
boarduntilthedoorisputintooperation.Topreventerrors,
thebatterymustbeconnectedtotheFS101circuitboard
before the connection is made to the mains power supply.
Battery
FS101circuit
board
Battery
5.4 5.4 Circuit diagram for mains connection and Circuit diagram for mains connection and
motormotor
CS 300 FS HY
L1 L2 L3 N
PE
PE
PE
~-
X1
T1
K2K1
U V W B1 B2X2
M
1
400V / 50Hz / 3 / N / PE
1 3 5
2 4 6
1 3 5
2 4 6
M
L1N
X12
Key:
K1: -
K2: OPEN contactor
M1: Motor
T1: Transformer
X1: Terminalblockformainsconnection
X2: Terminalblockformotor
Connection:
− Connectthecontroltothemainspowersupply.
− Connectthecontroltothemotor.
− Cablegroupsmustbesecuredclosetotheirrelevanttermi-
nals using a cable tie.
Initial operation
FS 345 HY Door Controls / Rev.B 0.0 – 7
EN
FS 101 - CS 300 FS HY (ready-wired)
FS101-P1-1
8 – FS 345 HY Door Controls / Rev. B 0.0
5.5 5.5 Mains power connection and motor Mains power connection and motor
230 V AC version230 V AC version
CS 300 FS HY 230 V AC, 3~
L1 L2 L3 N
PE
PE
PE
~-
X1
T1
K2K1
U V W B1 B2X2
M
1
230V / 50Hz / 3 / PE
1 3 5
2 4 6
1 3 5
2 4 6
M
L1N
X12
Key:
K1: -
K2: OPEN contactor
M1: Motor
T1: 230 V transformer
X1: Terminalblockformainsconnection
X2: Terminalblockformotor
Connection:
− Connectthecontroltothemainspowersupply.
− Connectthecontroltothemotor.
− Cablegroupsmustbesecuredclosetotheirrelevanttermi-
nals using a cable tie.
CS 300 FS HY 230 V AC, 1~
L1 N
PE
PE
PE
~-
X1
T1
K2K1
AUF ZU NB1 B2X2
M
1
230V / 50Hz / 1~ / PE
1 3 5
2 4 6
1 3 5
2 4 6
M
L1N
X12
Key:
K1: -
K2: OPEN contactor
M1: Motor
T1: 230 V transformer
X1: Terminalblockformainsconnection
X2: Terminalblockformotor
Connection:
− Connectthecontroltothemainspowersupply.
− Connectthecontroltothemotor.
− Cablegroupsmustbesecuredclosetotheirrelevanttermi-
nals using a cable tie.
Initial operation
FS 345 HY Door Controls / Rev.B 0.0 – 9
EN
5.6 5.6 Connection of command and safety devic-Connection of command and safety devic-
es for normal door operation X3/CS 300 es for normal door operation X3/CS 300
FS HYFS HY
Command and safety devices can be connected via terminals
X3andX4.
X3 / CS 300 FS HY
X6 / CS 300 FS HY
X7 / CS 300 FS HY
-CLOSEbutton
- Impulse button
- OPEN button
-STOPbutton
-Emergencyoff,slackropeswitch,
wicketdoorcontact,drawinprotection
-SocketsforinternalON-OFFswitch
-Socketsforinternal3-buttoninputunit
STOP
OPEN
CLOSE
10 – FS 345 HY Door Controls / Rev. B 0.0
5.7 5.7 Connection examples for command and Connection examples for command and
safety devices (terminal block X3/CS 300 safety devices (terminal block X3/CS 300
FS HY)FS HY)
OPEN / STOP / CLOSE buttons
(6-lead solution)
12345678910
OPEN / STOP / CLOSE buttons
(4-lead solution)
12345678910
Button
STOP
Button
OPEN
Button
CLOSE
Button
STOP
Button
OPEN
Button
CLOSE
OPEN / CLOSE key switch
12345678910
Impulse button key switch
(sequence control)
12345678910
Button
OPEN
Button
CLOSE
Button
IMP.INPUT
Initial operation
FS 345 HY Door Controls / Rev.B 0.0 – 11
EN
5.8 5.8 Connection examples for safety devices Connection examples for safety devices
X4/CS 300 FS HYX4/CS 300 FS HY
Terminal block X4
8.2 kOhm closing edge safety device
Terminal block X4
Optoelectronic closing edge safety system
+-
9
10
1
2
3
4
5
6
7
8
wt
gr
br
Gnd
Signal
+12V DC
24VDCforexternal
switching devices
Drive-through
photocell*
8.2 kOhm closing edge
safety device*
HALFOPENlimitswitch
24VDCforexternal
switching devices
Drive-through
photocell*
HALFOPENlimitswitch
Optoelectronic closing
edge safety system*
Terminal block X4
Pneumatic safety edge protection - pressure sensor test
8k2
Terminal block X4
Marantec-type leading photocell
+-
9
10
1
2
3
4
5
6
7
8
wt
gr
br
Gnd
Signal
+12V DC
1
2
3
4
5
6
7
8
8k2
A 24VDCforexternalswitchingdevices
B Drive-through photocell*
C Leading photocell
D HALFOPENlimitswitch
Adjustmentofthepre-limitswitchCLOSEfortheleading
photocell
− OntheCS300FSHY,setthemodeforrelay1to11(pre-
limitswitchCLOSE)
− Drivethedoorinthe“close”directionuntiltheleading
photocelljusttouchestheground.
− Intheinputmenu,setthepre-limitswitchCLOSEtothis
position
* effective in closing direction only
24VDCforexternal
switching devices
Drive-through
photocell*
HALFOPENlimitswitch
Closing edge safety
device
(pressure sensor test)*
A
B
C
D
X5 / CS 300 FS HY
X4 / CS 300 FS HY
Relay 1
MOD 11
12 – FS 345 HY Door Controls / Rev. B 0.0
5.9 5.9 Product drawing of FS 101 circuit board + Product drawing of FS 101 circuit board +
rechargeable batteryrechargeable battery
K04 K05 K06 K07 K08 K09
K10 K11 K12
FS101-P1-1
X01
X02
X03
X04
X05
X10
X06
X07
X08
X09
+ - AKKU
TEST
RESET
TIME2
TIME1
S303
F200
ON
Battery
FS 101 circuit board
Key to FS 101 circuit board
X01/X02 Powersupply230V/PE
X03  Limitswitchconnection
X04 Outputsfortheauxiliarymotor,brake, 
 auxiliaryrelay
X05  ActivationoftheCS300FSHYcircuitboard
X06  Firealarmconnection
X07  Potential-freeoutputforfaultindicator
X08  Potential-freeoutputforrealarm
X09  Potential-freeoutputforclosingedgesafety
  device(SKS)
X10  Input,external24V
+-BATT Terminalblockforbatterypack
Time 1 Time-controlled closing if mains power supply
fails
Time 2 Timing element for door seal function
S303  DIPswitch
Reset Button – switch off buzzer
Test Button for testing emergency operation
F200  3.15Afuseforbatterycharger
ON Button
K04  Notused(auxiliarymotorrelay)
K05  Solenoidvalverelay
K06  OPEN/CLOSEcommandrelay
K07  Upperswitchrelay
K07 Lower switch relay
K09  Stoprelay
K10  Operation/errorrelay
K11 Emergency closing relay
K12  SKSrelay
Initial operation
FS 345 HY Door Controls / Rev.B 0.0 – 13
EN
5.10 5.10 DIP switches:DIP switches:
1ON OperatortypesHY(+FT)
1OFF (DooroperatortypesFDF+FTA)
2 ON Fire alarm as normally open contact
2 OFF Fire alarm as normally closed contact
3ON Emergencyclosingwith400VAC/24VDC
3 OFF Emergency closing with 24V DC
4ON WithSKSinemergencyoperation
4OFF WithoutSKSinemergencyoperation
5 ON Door closes if an error occurs
5 OFF Door remains open if an error occurs
6ON OperatortypeHY
6 OFF (Operator type FT)
WhenmakingchangestotheDIPswitchsettings,thefollow-
ing procedure must be observed:
1. Switchoffthemainsvoltage
2. Switchofftherechargeablebatteryvoltage
3. Change the DIP switch positions as required
4. Switchontherechargeablebatteryvoltage
5. Switchonthemainsvoltage
5.11 5.11 Types of door operatorTypes of door operator
TheFS345HYcontrolsarepresetasfollows.
FT operators
DIP 1 ON and DIP 6 ON
1.HYdooroperatorswith24VDCsolenoid
valve.
Inemergencymode,thedoorclosesunderits
own weight.
The weight of the door is held by the solenoid
valve,whichisstillsuppliedwithelectricity.
The power supply comes from the mains
adapterontheFS101circuitboard;ifthe
mainspowerisinterrupted,powerissupplied
from the rechargeable battery.
(DIP 6 OFF required for version FT)
14 – FS 345 HY Door Controls / Rev. B 0.0
5.12 5.12 FS 101 connectionsFS 101 connections
2
1
2
1
2
1
2
1
2
1
X09
X08
X07
X06
X10
X051 2 3 4 5 6X03
X04
+
-
SKS
Potential-free relay
(only in connection
with 8K2 closing edge)
EMERGENCYOPERATION
Potential-free relay
OPERATION/ERROR
Potential-free relay
INPUT
FIREALARM
24VDC/50mA
Potential-free relay
OPEN command
Solenoidvalve
Initial operation
FS 345 HY Door Controls / Rev.B 0.0 – 15
EN
5.13 5.13 Connection example for re alarm con-Connection example for re alarm con-
tacttact
Terminal strip X06
(potential-free continuous contact as normally closed contact)
2
1
X06/FS101 Dip 2 = OFF
1
2
3
4
ON OFF
5
6
2
X10/FS101 +
-
1
Terminal strip X06
(potential-free continuous contact as normally open contact)
Dip 2 = ON
1
2
3
4
ON OFF
5
6
2
1
X06/FS101
2
X10/FS101 +
-
1
5.14 5.14 MessagesMessages
Terminal strip X07
K10operation/errorrelay
X07/FS101
Innormaloperationcontactclosed,opensintheeventofan
error.
rechargeablebatteryfault/mainspowerfailure:switchesif
the battery is defective or if the battery voltage is less than
19V.
Fire alarm contact
Supplyvoltage
24VDC,max.50mA
Fire alarm contact
Supplyvoltage
24VDC,max.50mA
Terminal strip X08
K11 emergency closing relay
X08/FS101
Potential-free switching contact for emergency operation is
active.Switchesintheeventofemergencyclosing(contact
closed).
Terminal block X4
K06 operator command relay
X04/FS101
Potential-freeswitchingcontactforCLOSEorOPENcommand
depending on DIP switches 1 and 3.
(See12and13.1forwiringandfunction)
Terminal strip X09
K12relaySKS
X09/FS101
Potential-freeswitchingcontact,displaysstatusofSKS
16 – FS 345 HY Door Controls / Rev. B 0.0
6.1 6.1 Limit switchesLimit switches
Connectionarrangementforlimitswitches(CS300FSHY
terminalsX11,X10andFS101terminalsX03,X05)
1
2
3
4
5
6
7
8
X03/FS101
1
2
3
4
5
6
7
8
9
10
8
7
6
5
4
3
2
1
6
5
4
3
2
1
X05/FS101*
X11/CS300 FS
X10/CS300 FS*
braun
weiß
blau
1
braun
weiß
blau
2
1Proximitysensor,OPEN,PNPNCC
2Proximitysensor,CLOSE,PNPNCC
* ready wired
TheproximitysensorsareanalysedbytheFS101PCBandthe
valuesarepassedontotheCS300FSHYPCB.
6.2 6.2 Pre-limit switch CLOSEPre-limit switch CLOSE
If,forexample,apre-limitswitchCLOSEisrequiredforusing
aleadingphotocell,then the connection is made as follows:
braun
weiß
blau
6. Limit switches
7.1 7.1 Overview of the LCD monitorOverview of the LCD monitor
AUTOMATIC O
STANDBY
A
B
C D E
F
G
H
Key:
A: Modeofoperation/DIAGNOSISinfo
B: Parameters/DIAGNOSISinfo
C Button (+)
D: Button (-)
E Button (P)
F Value/status
G Value/status
H Jumper
7.2 7.2 LCD monitor, modes of operationLCD monitor, modes of operation
The control has four modes of operation with the LCD moni-
tor:
1.AUTOMATIC
2.ADJUSTMENT
3.INPUT
4.DIAGNOSIS
IfjumperHisremoved,the(+)button,the(-)buttonandthe
(P) button have no function.
The display still functions.
Afterswitchingthecontrolon,itisinINITIALISATIONmode.
ThedisplayshowsINITPHASEandthecontrolisnotyetready
foruse.Thisphaselastsapprox.5seconds.
7. Programming with the LCD monitor
FS 345 HY Door Controls / Rev.B 0.0 – 17
EN
ADJUSTMENT,INPUTandDIAGNOSISmodesareexitedau-
tomatically20secondsafterthelastbuttonwaspressed,and
thecontrolthengoesintoAUTOMATICmode.
Operating mode 1: AUTOMATIC
ThedoorsystemisoperatedinAUTOMATICoperatingmode.
Display:
− Displaystheactionbeingcarriedout
− Displaysanyerrors
Ifthe“PRESS/REL"parameterissettoMOD2orMOD3in
theinputmenu,thedisplaychangesfromAUTOMATICto
MANUAL.
Operating mode 2: ADJUSTMENT
InADJUSTMENTmode,theOPEN/CLOSEDendpositionsare
set.
NOTICE
Malfunctions can occur as a result of incorrect
operation of the control!
InADJUSTMENTmode,thedoorwillnotstopautomatically
when it reaches the travel limit position if electronic end
positions(AWG)areused.
The door can be damaged if driven beyond the end posi-
tion.
FineadjustmentscanbemadeintheINPUToperatingmode.
Display:
− Displaysthetravellimitvalue
Operating mode 3: INPUT
IntheINPUToperatingmode,thevaluesofvariousparam-
eters can be altered.
Display:
− Displaystheselectedparameter
− Displaysthecurrentvalueorstatus
Operating mode 4: DIAGNOSIS
IntheDIAGNOSISoperatingmode,door-speciccheckscan
be queried.
Display:
− Displaysthemonitoredfunction
− Displaysthestatusofthefunction
18 – FS 345 HY Door Controls / Rev. B 0.0
8. Navigator (LCD monitor only)
AUTOMATIC
STANDBY
P
> 1 second
ADJUSTMENT
STANDBY
+
->Position,DOOROPEN ADJUSTMENT
MAINUP Deadman operation
Deadman operation
-
->PositionDOORCLOSED ADJUSTMENT
MAINDOWN
P
> 1 second
INPUT
+
and
-
> 2 sec. INPUT
ENGLISH : Scrollupthroughmenu:
+
> 2 sec.
Scrolldownthroughmenu:
-
> 2 sec.
Selectvalue:
P
> 1 sec.
Increase value:
+
Decrease value:
-
Savevalue:
P
Return to INPUTmode:
+
and
-
> 1 sec
INPUT
RUNTIME : 60
P
> 1 second
INPUT
OPEN TIME : 0
INPUT
PREWARNING : 0
INPUT
REVERS.TIME : 3
INPUT
M1-3STAND.Mod : MOD1
INPUT
QUICKCLOSE : OFF
INPUT
RELAY1 : MOD6
INPUT
RELAY2 : MOD7
INPUT
RELAY3 : MOD1
INPUT
RELAY4 : MOD19
INPUT
DWTEST : OFF
INPUT
DELAYUP : OFF
INPUT
PRESS/REL : MOD1
INPUT
SU/WI : MOD1
INPUT
REVERS. : MOD1
DIAGNOSIS
Scrollupthroughmenu:
> 2 sec.
Scrolldownthroughmenu:
-
> 2 sec.
ReturntoAUTOMATICmode:
P
Only queries are possible.
UPPERSWITCH : ON
LOWERSWITCH : OFF
UPSWITCH : OFF
PARTUP : OFF
DOWNSWITCH : OFF
SKS : OFF
IMP.INPUT : OFF
SWITCHCLK : OFF
LIGHTBARR. : ON
STOPCIRCUIT : ON
S-POINT1 : ON
S-POINT2 : ON
CYCLE : XXXX
FS 345 HY Door Controls / Rev.B 0.0 – 19
EN
AUTOMATIC
STANDBY
P
> 1 second
ADJUSTMENT
STANDBY
+
->Position,DOOROPEN ADJUSTMENT
MAINUP Deadman operation
Deadman operation
-
->PositionDOORCLOSED ADJUSTMENT
MAINDOWN
P
> 1 second
INPUT
+
and
-
> 2 sec. INPUT
ENGLISH : Scrollupthroughmenu:
+
> 2 sec.
Scrolldownthroughmenu:
-
> 2 sec.
Selectvalue:
P
> 1 sec.
Increase value:
+
Decrease value:
-
Savevalue:
P
Return to INPUTmode:
+
and
-
> 1 sec
INPUT
RUNTIME : 60
P
> 1 second
INPUT
OPEN TIME : 0
INPUT
PREWARNING : 0
INPUT
REVERS.TIME : 3
INPUT
M1-3STAND.Mod : MOD1
INPUT
QUICKCLOSE : OFF
INPUT
RELAY1 : MOD6
INPUT
RELAY2 : MOD7
INPUT
RELAY3 : MOD1
INPUT
RELAY4 : MOD19
INPUT
DWTEST : OFF
INPUT
DELAYUP : OFF
INPUT
PRESS/REL : MOD1
INPUT
SU/WI : MOD1
INPUT
REVERS. : MOD1
DIAGNOSIS
Scrollupthroughmenu:
+
> 2 sec.
Scrolldownthroughmenu:
-
> 2 sec.
ReturntoAUTOMATICmode:
P
Only queries are possible.
UPPERSWITCH : ON
LOWERSWITCH : OFF
UPSWITCH : OFF
PARTUP : OFF
DOWNSWITCH : OFF
SKS : OFF
IMP.INPUT : OFF
SWITCHCLK : OFF
LIGHTBARR. : ON
STOPCIRCUIT : ON
S-POINT1 : ON
S-POINT2 : ON
CYCLE : XXXX
20 – FS 345 HY Door Controls / Rev. B 0.0
9. Overview of functions
9.1 Automatic operating mode
Display Description
AUTOMATIC
OPEN The door is driven to the OPEN end position
AUTOMATIC
CLOSE ThedoorisdriventotheCLOSEDendposition
AUTOMATIC
STANDBY The door stands between the end positions
AUTOMATIC O
STANDBY The door stands at the OPEN end position
AUTOMATIC o
STANDBY ThedoorstandsatthePARTOPENposition("before-endposition"OPEN)
AUTOMATIC U
STANDBY ThedoorstandsattheCLOSEDendposition
AUTOMATIC u
STANDBY ThedoorstandsatthePARTCLOSEDposition("before-endposition"CLOSED)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32