Tartarini V/31-2-E Series Pneumatic Switch Owner's manual

Type
Owner's manual
Instruction Manual
D104261X012
September 2018
V/31-2-AP-E Series
INTRODUCTION
Scope of the Manual
This manual provides installation, startup, maintenance,
troubleshooting, and spare parts for the switch for ow
partition system V/31-2-AP-E Series.
Product Description
In monitor-regulator systems the pneumatic switch
Type V/31-2-AP-E is installed on the motorization pressure
circuit, in order to obtain the capacity ow partition between
the pressure reducing lines.
This product has been designed to be used with fuel gases of
1st and 2nd family according to EN 437, and with other non
aggressive and non fuel gases. For any other gases, other
than natural gas, please contact your local Sales Ofce.
For special applications Types V/31-2 -AP-EF, V/31-2-AP-EM
and V/31-2-AP-EMF versions are available on request
(see Table 1).
V/31-2-AP-E Series Switch for Flow Partition System
Figure 1. Types V/31-2-AP-E and V/31-2-AP-EF
Switch for Flow Partition System
SUMMARY
Introduction ......................................................................... 1
Characteristics .................................................................... 2
Labelling ............................................................................. 2
Dimensions and Weight ...................................................... 2
Installation .......................................................................... 2
Startup ................................................................................ 5
SEP Statement ................................................................... 5
Field Inspection and Maintenance ......................................
5
Spare Parts......................................................................... 5
Troubleshooting .................................................................. 6
Parts List............................................................................. 6
Schematic Assemblies........................................................ 7
!
WARNING
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion and/or re
causing property damage and personal
injury or death.
Tartarini™ device must be installed, operated
and maintained in accordance with federal,
state and local codes, rules and regulations
and Emerson Process Management
Regulator Technologies, Inc. instructions.
If the device vents gas or a leak develops
in the system, service to the unit may be
required. Failure to correct trouble could
result in a hazardous condition.
Call a gas service person to service the
unit. Only a qualied person must install or
service the device.
2
V/31-2-AP-E Series
CHARACTERISTICS
Table 1. Technical Features
TYPE
ALLOWABLE
PRESSURE
PS (bar)
SETPOINT
TYPE
SET RANGE
W
d
(bar)
BODY AND
COVERS
MATERIAL
V/31-2-AP-E
100
Adjustable 0.5 - 2
Steel
V/31-2-AP-EM
V/31-2-AP-EF
Fixed 2
V/31-2-AP-EMF
1/4” NPT female threaded connections.
LABELLING
APPARECCHIO TIPO /DEVICE TYPE
Wau
DN2
DN1
MATRICOLA
bar
bar
SERIAL Nr.
°C
FLUIDO GRUPPO
FLUIDGROUP
ANNO
YEAR
HARMONIZED STD.
bar
NORME ARMONIZ.
LEAKAGECLASS
CLASSE DI PERDITA
FUNCTIONAL CLASS
CLASSE FUNZIONALE
bar
Wao
Wa
TS
bar
pao
Cg
PS
body
bar PT= xPSbar
PS
covers
EN
bar
pmax
xxxx
body
Notified
BOLOGNA ITALY
1.5Note 4Note 3
Note2
Note 1
1
-
Figure 2. Label for V/31-2-AP-E Series Pneumatic Switch
Note 1: See “Characteristics
Nota 2: Year of Manufacture
Nota 3: Class 1: -10°/60°C
Class 2: -20°/60°C
Note 4: See “Characteristics”
DIMENSIONS AND WEIGHT
107
Ø 75 Ø 75
202
Type V/31-2-AP-EF
Type V/31-2-AP-EMF
Type V/31-2-AP-E
Type V/31-2-AP-EM
TYPES V/31-2-AP-E and V/31-2-AP-EM WEIGHT: 3.5 kg
TYPES V/31-2-AP-EF and V/31-2-AP-EMF WEIGHT: 2.9 kg
Figure 3. Dimensions (mm) V/31-2-AP-E Series Pneumatic Switch
CAUTION
All interventions on the equipment should
only be performed by qualied and
trained personnel.
For further information, please contact our
local Sales Ofce or our Authorized Dealers.
INSTALLATION
!
WARNING
Personal injury or equipment damage, due
to bursting of pressure-containing parts
may result if this device is overpressured or
is installed where service conditions could
exceed the limits given in the Characteristics
section and on the appropriate nameplate or
where conditions exceed any rating of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices to prevent service conditions from
exceeding those limits.
Also, be sure the installation is in
compliance with all applicable codes
and regulations.
Additionally, physical damage to the
device can cause personal injury and
property damage due to bursting of
pressure-containing parts.
To avoid such injury and damage, install the
device in a safe location.
CAUTION
The device must be rated for the maximum
allowable operating pressure of the ow
partition system.
a. Check that data on the pilot’s plate are compatible with
actual working conditions.
b. Install in accordance with regulator instruction manual.
3
V/31-2-AP-E Series
Figure 4. Type V/31-2-AP-EF Switch for Flow Partition System Connection/Installation Schematic
NOTE: RECOMMENDED PIPING IS STAINLESS STEEL WITH 10 mm DIAMETER.
TO THE HEATING
2
1
VENT DOWNSTREAM OR TO A SAFE AREA
LEGEND:
INSTALLATION (continued)
4 X DN
6 X DN
MONITOR
2
R
S
M
R
S
M
REGULATOR
TYPE
PS/80
V
TYPE
PS/79
TYPE
PS/80
TYPE
PS/79
V
2
4 X DN
6 X DN
MONITOR
R
S
M
R
S
M
REGULATOR
V V
B
A
C
TYPE
V/31-2-AP-EF
1
ANY OTHER LINES
1
2
2
1
1
D
4
V/31-2-AP-E Series
Figure 5. Type V/31-2-AP-EM Switch for Flow Partition System Connection/Installation Schematic
NOTE: RECOMMENDED PIPING IS STAINLESS STEEL WITH 10 mm DIAMETER.
TO THE HEATING
2
1
VENT DOWNSTREAM OR TO A SAFE AREA
LEGEND:
INSTALLATION (continued)
4 X DN
6 X DN
4 X DN
6 X DN
2
2
TYPE
PS/80
TYPE
PS/79
TYPE
PS/80
TYPE
PS/79
2
2
MONITOR REGULATOR
MONITOR REGULATOR
TYPE
V/31-2-AP-EM
TYPE
V/31-2-AP
ANY OTHER LINES
1
1
1
1
R
SM
R
SM
V
V
R
S
M
R
S
M
V V
B
A
C
D
B
A
C
D
E
5
V/31-2-AP-E Series
STARTUP
CAUTION
Be sure to slowly introduce pressure into the
system to prevent downstream overpressure
due to potential rapid pressure increase.
Pressure gauges should always be used to
monitor downstream pressure
during Startup.
See the setup and pilot adjustment instructions applying to
the equipment where the switch for ow partition system
is tted.
SEP STATEMENT
Emerson declares this product conforms to Pressure
Equipment Directive PED 2014/68/UE Article 4 section 3 and
was designed and manufactured in accordance with sound
engineering practice SEP.
Per Article 4 section 3, this “SEP” product must not bear the
CE marking.
FIELD INSPECTION AND MAINTENANCE
The pneumatic switch parts are subject to normal wear and
must be inspected periodically and replaced if necessary.
The frequency of inspection/checks and replacement
depends upon the severity of service conditions and
according to applicable National or Industry codes,
standards and regulations/recommendations.
In accordance with applicable National or Industry codes,
standards and regulations/recommendations, all hazards
covered by specic tests after nal assembling before applying
the CE marking, shall be covered also after every subsequent
reassembly at installation site, in order to ensure that the
equipment will be functional throughout its intended life.
Before proceeding with any maintenance work, shutoff the
gas upstream and downstream from the regulator, also
ensure that there is no gas pressure inside the body by
loosening the upstream and downstream connections.
Upon completion, check for leaks using an appropriate leak
detection solution.
Replacing Seal Pad
a. Disconnect all ttings, remove valve from the line and
unscrew (key 4) in the lower part of the valve.
Remove the lower cover (key 2) and replace pad (key 7).
General Maintenance
CAUTION
Always remove spring (key 24) tension
before performing maintenance on this unit.
a. Disconnect all ttings, remove valve from the line, loosen
nut (key 19) and unscrew completely adjusting screw
(key 18) to remove spring tension.
b. Unscrew cap (key 20), remove spring holder (key 23) and
spring (key 24). Replace O-ring (keys 21 and 22).
c. Unscrew screws (key 4) and remove the lower cover
(key 2). Replace O-ring (keys 13 and 8).
d. Hold stem (key 9) using a wrench and unscrew nuts
(key 16).
e. Disassemble parts and replace diaphragm (key 12), pad
(key 7) and lip seals (key 10).
f. Unscrew seat (key 5) and replace O-ring (key 6).
Reassembly
Reassemble all parts by following in reverse order the assembly
as described above (see General Maintenance section).
As parts are assembled, make sure they move freely
causing no friction.
Make sure to:
a. O-rings and diaphragms should be lubricated by applying a
thin layer of grease Molykote 55 M or equivalent.
Pay attention not to damage them during reassembly.
All other pilot parts don’t require lubrication.
b. The cover clamping screws (key 4) should be tightened
evenly to ensure proper tightness.
c. Previously disassembled ttings must be connected. Check
for leaks by using suds.
SPARE PARTS
Spare parts storage shall be done by proper procedures
according to national standard/rules to avoid over aging of
rubber parts or any damage to critical part.
6
V/31-2-AP-E Series
PARTS LIST
V/31-2-AP-E Series Switch for Flow
Partition System
(See Figure 6)
Item Description
1 Body
2 Lower cover
3 Washer
4 Screw
5 Seat
6* O-ring
7* Pad
8* O-ring
9 Stem
10* Lip seal
11 Lower plate
12* Diaphragm
13* O-ring
14 Upper plate
15 Washer
16 Nut
17 Spring holder
18 Adjusting screw
19 Nut
20 Cap
21* O-ring
22* O-ring
23 Spring holder
24 Spring
25 Upper cover
26 Restrictor
27 Label
Rubber parts marked with (*) are supplied in the “spare parts
kit”, recommended as stock.
To order the kit it is necessary to communicate to us the
pneumatic switch serial number.
TROUBLESHOOTING
Table 2. Troubleshooting for V/31-2-AP-E Series Switch for Flow Partition System
SYMPTOMS CAUSE ACTIONS
The booster valve does not work Valve diaphragm is broken (key 12) Replace diaphragm
7
V/31-2-AP-E Series
D
C
B
A
18
19
20
21
22
23
24
25
27
6
7
4
1
2
3
5
8
9
10
11
12
13
14
15
16
17
Figure 6. V/31-2-AP-E Series Switch for Flow Partition System
SCHEMATIC ASSEMBLIES
V/31-2-AP-E Series
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Europe
Bologna 40013, Italy
T +39 051 419 0611
Asia Pacic
Singapore 128461, Singapore
T +65 6770 8337
Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
D104261X012 © 2018 Emerson Process Management Regulator
Technologies, Inc. All rights reserved. 09/18.
The Emerson logo is a trademark and service mark of Emerson Electric
Co. All other marks are the property of their prospective owners.
Tartarini™ is a mark of O.M.T. Ofcina Meccanica Tartarini s.r.l., a
business of Emerson Automation Solutions.
The contents of this publication are presented for information purposes
only, and while effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which
are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any
product. Responsibility for proper selection, use and maintenance of any
Emerson Process Management Regulator Technologies, Inc. product
remains solely with the purchaser.
O.M.T. Ofcina Meccanica Tartarini S.R.L., Via P. Fabbri 1, I-40013 Castel Maggiore (Bologna), Italy
R.E.A 184221 BO Cod. Fisc. 00623720372 Part. IVA 00519501209 N° IVA CEE IT 00519501209,
Cap. Soc. 1.548 000 Euro i.v. R.I. 00623720372 - M BO 020330
Francel SAS, 3 Avenue Victor Hugo,CS 80125, Chartres 28008, France
SIRET 552 068 637 00057 APE 2651B, N° TVA : FR84552068637, RCS Chartres B 552 068 637,
SAS capital 534 400 Euro
Emerson Automation Solutions
Tartarini-NaturalGas.com
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
Figure 6. V/31-2-AP-E Series Switch for Flow Partition System (continued)
D
25
TYPE EF
24
DE
TYPE EMF
26
24
25
DE
26
24
25
TYPE EM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Tartarini V/31-2-E Series Pneumatic Switch Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI