Danfoss Refrigerant R290 Propane in Small Hermetic Systems Installation guide

Type
Installation guide

Danfoss Refrigerant R290 Propane in Small Hermetic Systems provides an efficient and environmentally friendly cooling solution for your refrigeration needs. Its high energy efficiency and low global warming potential make it a sustainable choice. Designed for use in small hermetic systems like refrigerators and freezers, it offers reliable performance and safety features to ensure peace of mind. Choose Danfoss R290 Propane for a greener and more efficient cooling experience.

Danfoss Refrigerant R290 Propane in Small Hermetic Systems provides an efficient and environmentally friendly cooling solution for your refrigeration needs. Its high energy efficiency and low global warming potential make it a sustainable choice. Designed for use in small hermetic systems like refrigerators and freezers, it offers reliable performance and safety features to ensure peace of mind. Choose Danfoss R290 Propane for a greener and more efficient cooling experience.

Practical Application of Refrigerant
R290 Propane in Small Hermetic Systems
COMPRESSORS
Technical information
REFRIGERATION AND AIR CONDITIONING
2 CN.60.F1.02 November 2000
Refrigerant R 290, or propane, is a possible replacement for other refrigerants, which have
high impact on environment, in small hermetic systems, like factory made commercial re-
frigerators and freezers. It has zero ozone depletion potential ODP and a neglectible global
warming potential GWP. Furthermore it is a substance which is a part of petrol gases from
natural sources.
The refrigerant R 290 has been in use in refrigeration plants in the past, and is still used in
some industrial plants. In domestic heat pumps and air conditioners R 290 has been used
in Germany for some years, however, with different level of success. Because of the
availability of propane allover the world it has been discussed widely for CFC replacement.
Propane R 290 is a possible refrigerant for this application, with good energy efficiency, but
special care has to be taken to the flammability of propane.
This paper is partly similar to the R 600a paper CN.60.E .
The properties of R 290 differ from other refrigerants commonly used in small hermetic
systems, as shown in table 1. This leads to a different design of details in many cases.
Table 1: Refrigerant data comparison
tnaregirfeR092Ra431RA404R22Ra006R
emaNenaporP-2,1,1,1
-arteT
-oruolf
enahte
erutxiM
521R
a341R
a431R
-orolhC
-oroulfid
enahtem
enatubosI
alumroFC
3
H
8
FC
3
HC-
2
F4/25/44FHC
2
ICHC(
3
)
3
HC
erutarepmetlacitirC
C°ni
7.691015.271.69531
thgiewraluceloM
lomk/gkni
1.442016.795.681.85
tniopgnilioblamroN
C°ni
1.24-5.62-8.54-8.04-6.11-
erusserP
)etulosba(rabniC°52-ta
30.270.105.210.285.0
ytisneddiuqiL
l/gkniC°52-ta
65.073.142.163.106.0
ytisnedruopaV
tta
o
³m/gkniC°23+/52-
6.34.40.010.73.1
yticapaccirtemuloV
³m/JkniC°23/55/52-ta
461185643314421373
noitasiropavfoyplahtnE
gk/JkniC°52-ta
604612681322673
erusserP
)etulosba(rabniC°02+ta
4.87.50.111.90.3
1 Refrigerant
November 2000 CN.60.F1.02 3
A difference between R 290 and R 134a is found in the pressure level, which is closer to R
22 and R 404A, e.g. at -25 °C evaporation the pressure is roughly 190 % of R 134a, 81 %
of R 404A, 350% of R 600a or almost exactly that of R 22. In connection with this the
normal boiling point is close to R 22 also. Evaporators will thus have to be designed similar
as for R 22 or R 404A.
Figure 1: Vapour pressure of different refrigerants versus temperature
The pressure level and critical temperature are almost like R 22. However, the discharge
temperature is much lower. This gives the opportunity to work at higher pressure ratios,
means lower evaporating temperatures, or at higher suction gas temperatures.
1.1 Pressure
0
5
10
15
20
25
-50 -40 -30 -20 -10 0 10 20 30 40 50 60
Temperature in °C
Vapour pressure in bar
R290
R134a
R404A
R22
R600a
4 CN.60.F1.02 November 2000
R 290 has roughly 90 % of R 22 or 150 % of R 134a volumetric capacity at 45 °C condens-
ing temperature, as seen in figure 2. Because of this the necessary compressor swept
volume is close to R 22 also, and 10 % to 20 % larger than for R 404A.
The volumetric capacity is approx. 2.5 to 3 times that of R 600a. Thus the choice for either
R 290 or R 600a will lead to differences in system design because of very different neces-
sary volume flow for same refrigeration need.
The volumetric cooling capacity is a value calculated from suction gas density and en-
thalpy difference of evaporation.
Figure 2: Volumetric capacity of R 290, R 134a, R 404A and R 600a, relative to R 22, over
evaporation temperature, at 45 °C condensing and 32 °C suction gas temperature, no
subcooling
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
-40 -30 -20 -10 0
Evaporation temperature in °C
Volumetric capacity rel. to R22
R290
R134a
R404A
R22
R600a
1.2 Capacity
November 2000 CN.60.F1.02 5
If R 290 would be charged into an unchanged refrigeration system, charge amount counted
in grams would be much lower. However, calculated in cm³, the charge would be roughly
the same liquid volume in the system. This gives charges of approx. 40 % of R 22 or R
404A charge in grams, according to the data from table 1, which also corresponds with
empirical values.
Maximum charge according to safety regulations is 150 g for household refrigerators and
similar applications, which corresponds to approx. 360 g of R 22 or R 404A.
Refrigerant R 290 specification is not found in international standards. Some data are
enclosed in the German standard DIN 8960 of 1998, which is an extended version of ISO
916. The purity of the refrigerant has to be judged from chemical and stability side, for
compressor and system lifetime, and from thermodynamic side regarding refrigeration
system behaviour and controllability.
The specification in DIN 8960 is a safe general hydrocarbons refrigerant specification,
adopted from other refrigerants criteria catalogue and covering propane, isobutane, normal
butane, and others. Some points can possibly be accepted a little less narrow for specific
refrigerants and impurities combinations after extensive evaluation.
For the time being no refrigerant quality according to an official standard is on the market.
The specifications of possible qualities have to be checked with the supplier in details.
Liquified petrol gas LPG for fuel applications or technical grade 95 % purity is not sufficient
for hermetic refrigeration. Water, sulfur and reactive compounds contents has to be on a
lower level than guaranteed for those products. Technical grade 99.5 %, also called 2.5, is
widely used.
Table 2: Specification of R 290 according to DIN 8960 - 1998
1) This content is not explicitly stated in DIN 8960. Only the impurities are listed and
limited. The main content is the rest up to 100 %.
2) From compressor point of view a butane content up to approx. 1 % is acceptable
in the R 290.
3) This is a maximum value for every single substance of the multiple unsaturated
hydrocarbons.
4) This is a maximum value for every single aromatic compound.
5) This is a preliminary value, to be reviewed with growing experience.
noitacificepStinU
tnetnoctnaregirfeR
1
5.99ssamyb%
seitirupmicinagrO
2
5.0ssamyb%
eneidatuB-3,1
3
5ssamybmpp
enaxeHlamroN
05ssamybmpp
enezneB
4
1ecnatsbusrepmpp
rufluS
2ssamybmpp
.pavefoedilgerutarepmeT
5.0).llitsed%79ot5ta(K
sesagelbasnednocnoN
5.1esahpruopavfo.lov%
retaW
5
52ssamybmpp
tnetnocdicA
20.0noitazilartueNg/HOKgm
eudisernoitaropavE
05ssamybmpp
sdilos/selcitraPonkcehclausiV
1.3 Refrigerant charge
1.4 Purity
6 CN.60.F1.02 November 2000
Refrigerant R 290 is used with polyolester oil in Danfoss compressors, so material com-
patibility is almost identical to R 134a or R 404A situation from oil side. R 290 is chemically
inactive in refrigeration circuits, so no specific problems should occur there. Solubility with
ester oil is good. Direct material compatibility is less problematic. On some rubbers, plas-
tics and especially chlorinated plastics however, problems have been observed, but these
materials are normally not present in small hermetic systems. Some materials, on which
problems have been reported by different testers, are listed in the table 3. On critical
materials test have to be performed for the specified use.
Table 3: Material compatibility
For domestic refrigerators the common desiccant is a molecular sieve, a zeolithe. For R
290 a material with 3 Å pores is recommended, like for R 134a, e.g. UOP XH 7, XH 9 or XH
11, Grace 594, CECA Siliporite H3R. Pencil driers for R 134a can possibly be used for R
290, if they are tested according to IEC / EN 60 335 burst pressure demands.
See also note CN.86.A .
If hardcore driers are to be used, please ask the manufacturer for compatibility to R 290.
Danfoss type DU driers can be used.
lairetaMelbitapmoc
rebburcilytuBon
rebburlarutaNon
enelyhteyloPsnoitidnocnosdneped
PPon
CVPon
FDVPon
MDPEon
MSCon
2 Materials
2.1 Driers
November 2000 CN.60.F1.02 7
The main disadvantage discussed in connection with R 290 use is the risk based in its
flammability. This leads to necessity for very careful handling and safety precautions.
Table 4: Flammability of propane
Because of the flammability of propane in a wide concentration range safety precautions
are necessary, on the appliance itself and in the manufacturing factory. The risk assess-
ments behind these two situations are quite different. Main common starting point is, that
accidents need to have two essential preconditions. One is the flammable mixture of gas
and air and the other is the ignition source of a certain energy level or temperature.
These two have to be present together for combustions, so avoidance of this combination
has to be proven.
Figure 3: Yellow warning label
For safety testing of household refrigerators and similar applications a standard has been
established in Europe, IEC Technical Sheet TS 95006. It is also transferred to an amend-
ment to IEC / EN 60 335-2-24, which is the normal electrical safety standard. Approvals of
refrigerators using hydrocarbons as refrigerant are done according to the proceedures of
the TS in Europe since 1994. The methodology of TS and the amendments derived from
this are base for the following short description. Other applications have to take different
national standards and legislation into account, e.g. EN 378, DIN 7003, BS 4344, SN 253
130, which can have different demands.
All electrical elements switching during normal operation are taken to be possible igni
tion sources. This includes thermostat, door contacts for lighting, on/off and other
switches, like superfrost, compressor relays, external klixon, defrost timers and so on.
All refrigerant containing parts are taken to be possible refrigerant sources through
leaks. This includes evaporators, condensers, door heaters, tubings and the compressor
Maximum refrigerant charge is set to be 150 g. By keeping the charge to max. 25 % of
lower explosion level LEL, which is approx. 8 g/m
3
, for a standard kitchen, ignition
risk is very low, even if refrigerant distribution in case of leakage is uneven for some
time first
The main target of the safety precautions is to seperate rooms with refrigerant containing
parts from rooms with switching elements.
Danfoss Compressors for R 290 have in-ternal
protectors and PTC starters or special relays,
both preventing from sparks coming out near
the compressor, because it can not be guar-
anteed to hold surrounding air below LEL in
case of leaks close to the compressor.
They are equipped with a yellow label warn-
ing for flammable gas, like shown in figure 3.
8122-4
R290
3.1 Appliance
)LEL(timilnoisolpxerewoL%1.m/g93.xorppa
)LEU(timilnoisolpxereppU%5.m/g771.xorppa
erutarepmetnoitingimuminiMC°074
3 Flammability and
Safety
8 CN.60.F1.02 November 2000
Figure 4: Appliance design variants
In figure 4 three principal possibilities are shown. Option 1 has evaporator and thermostat/
door switch both located in the storage volume. This is critical for flammable refrigerants
and should not be used. Option 2 has evaporator inside and thermostat/door switch out-
side, on top. This normally gives a safe solution. Option 3 has thermostat/door switch
inside, but evaporator foamed in place behind the inner liner. This is a possible solution
used in many cases. Choosen option has to be designed and proven in leakage test accord-
ing to TS 95006 and IEC / EN 60335 demands.
On many refrigerator or freezer designs this separation is already the existing situation.
Large free standing bottle coolers and freezers often have all electrical switches in the
top panel.
Some refrigerators have the evaporators hidden behind the liner, in the foam, means not
in the cabinet space where thermostats and so on are allowed in this case.
Critical situation is given whenever it is not possible to avoid evaporator and thermostat or
switches being in the cabinet. In this case two possibilities are left.
Thermostats and switches have to be changed to sealed versions preventing gas from
penetrating them and thus reaching the switching contacts. Danfoss offers electronic
thermostats suitable for this application.
Fans inside the refrigerated compartment have to be safe and sparkfree even if blocked.
Electrical connectors and lamp holders have to be proven according to certain specifi-
ations.
Every R 290 appliance type has to be tested and approved according to the TS / IEC / EN
proceedures, by an independent institute, even if all above mentioned criteria are included
in the design. Please see the standards for details. Instructions for use should contain
some informations and warnings for careful handling, like not to defrost freezer compart-
ments with knives, and for installing in a room with at least 1 m³ of space per 8 g of charge,
the latter to be seen on the type label.
Systems using relays or other electrical components near the compressor must meet the
specifications. These are including
Fans at the condenser or compressor must be sparkfree even when blocked or over
loaded. Either they have to be designed not to need a thermal switch, or this switch has
to meet IEC 60079-15.
Relays have to meet IEC 60079-15 or being placed where a leakage can not produce a
flammable mixture with air, e.g. in a sealed box or at high altitude. The starting acces
sory of Danfoss SC compressors is delivered with a long cable for placing in a separate
electrical installation box.
1 32
Thermostat /
door switch
Evaporator
November 2000 CN.60.F1.02 9
The refrigerant containing system and the safety system design is to be approved and
controlled regularly by local authorities normally. Below the design principles for installa-
tions in Germany are given. In many details this is based on regulations for liquified gas
installations. Specialities are found around the charging stations, where gas connectors
are to be handled frequently and a charging of the appliances occurs.
The basic principles for safety are
Forced ventilation to avoid local accumulation of gas.
Standard electrical equipment except for the ventilation fans and safety systems.
Gas sensors continuously monitoring in possible leakage areas like around charging
stations, with alarm and doubling of ventilation at 15 % to 20 % of LEL and with discon-
nection of all non explosion proof electrics in the monitored area at 30 % to 35 % of
LEL, leaving the fans running at full speed.
Leakage test on appliances before charging to avoid charging of leaking systems.
Charging stations designed for flammable refrigerants and connected to the safety sys-
tems.
Safety system design can be supported by suppliers of charging stations and gas sensing
equipment in many cases.
For handling of R 290 in small containers, the rules are less strict in some countries.
In many cases of transition from non flammable refrigerants to R 290 the appliance cabinet
has to be modified for safety reasons as listed in section 3.1. But changes can additionally
be necessary for other reasons.
Refrigerant containing system parts have according to IEC / EN 60335 to withstand a
specified pressure without leaking. High pressure side has to withstand saturation over-
pressure of 70 °C times 3.5, low pressure side has to withstand saturation overpressure of
20 °C times 5. This gives the following for R 290:
87 bar overpressure High Pressure side
36.8 bar overpressure Low Pressure side
National standards could have different specifications, depending on the application.
The refrigeration system efficiency will normally not cause a need for changing evaporator
or condenser size, means outer surface can be left the same as with R 22 or R 404A.
Inside design of the evaporator possibly needs some modification, because the refrigerant
volume flow is different, according to the compressor swept volume. To keep the refriger-
ant flow speed within the recommended range of 3 to 5 m/s it may be necessary to adopt
the cross flow sections.
Rollbond evaporators can maybe not be used because of the high demands on burst
pressure.
Special care has to be taken when designing the accumulator in the system. When using
R 22 or R 134a the refrigerant is heavier than the oil used, while with R 290 the refrigerant
is less heavy, as can be seen in the data table 1. This can lead to oil accumulation if the
accumulator is too large, especially too high, and has a flow path which does not guaran-
tee emptying sufficiently during startup phase of the system. Evaporator design hints can
be found in note CN.82.A .
4 Refrigeration
system design
4.1 Heat exchangers
3.2 Factory
10 CN.60.F1.02 November 2000
For R 290 experience shows the need for a capillary flow rate almost similar to R 404A. At
least this is a good starting point for optimization.
As with R 134a, R 404A and R 600a the suction line heat exchanger is very important for
system energy efficiency of R 290, which it was not for R 22, see figure 5. The figure
shows increase of COP with superheat from few K up to +32 °C return gas temperature,
where a range from +20 °C to approx. +32 °C is usual for small hermetic systems. This
large increase in COP for R 290 is caused by a high vapour heat capacity. In combination
with the need for keeping the refrigerant charge close to maximum possible in the system,
thus giving no superheat at evaporator outlet, the suction line heat exchanger has to be
very efficient for preventing air humidity condensation on the suction tube. In many cases
an elongation of the suction line and capillary gives efficiency improvements. The capillary
itself has to be in good heat exchanging contact with the suction line for as long a part of
total length as possible.
Figure 5: Theoretical COP increase of different refrigerants versus suction temperature
with adiabatic compression, internal heat exchange, at -25 °C evaporation, 45 °C conden-
sation, no subcooling before internal heat exchanger
At high superheat, with good internal heat exchange, the theoretical COP of R 290, R 600a
and R 134a is higher than for R 22. At very low superheat the COP of R 290, R 600a and R
134a is lower than for R 22. The R 290 behaviour is similar to R 134a, with respect to
internal heat exchange.
2,0
2,2
2,4
2,6
2,8
3,0
-25 0 25
Suction gas temperature in °C
Isentropic COP
R290
R134a
R404A
R22
R600a
4.2 Capillary
November 2000 CN.60.F1.02 11
Generally the same rules for evacuation and processing are valid as for R 22, R 134a or
R 404A systems. The maximum allowable content of non condensable gases is 1 %.
Too high level of non condensables increases energy consumption because of higher
condensing temperature and a portion of the transported gas being inactive. It can addi-
tionally increase flow noise.
The specifications for cleanliness are generally comparable to R 22 or R 134a. The only
official standard on cleanliness of components for refrigeration use is the DIN 8964, which
also is used in several countries outside Germany. It specifies maximum contents of
soluble, insoluble and other residues. The methods for determining soluble and insoluble
contents are to be modified for the actual refrigerant R 290, but in principle the same limits
are useful.
Servicing and repair of R 290 systems is possible for skilled and well trained service
technicians. Please see note CN.73.C for details. Local laws and regulations have to be
taken into account also. It needs very careful handling because of the flammability of the
gas, which is a potential danger during work on the refrigeration system. A good ventilation
of the room is necessary and the discharge of the vacuum pump has to be lead to open air.
The equipment of the service technician has to meet the requirements of R 290 in terms of
evacuation quality and refrigerant charge accuracy. An electronic scales is recommended
to control refrigerant charge to within the needed accuracy.
Conversion of a R 22, R 502 or R 134a system to R 290 is not recommended by Danfoss,
because these systems are not approved for flammable refrigerant use, so electrical safety
is not proven to be according to the needed standards.
TS 95006
Refrigerators, food-freezers and ice-makers using
flammable refrigerants
, Safety Requirements,
Ammendment to IEC 60 335-2-24, CENELEC, July 1995
CN.86.A
Driers and Molecular Sieves Desiccants
CN.82.A
Evaporators for Refrigerators
CN.73.C
Service on Household Refrigerators and Freezers
with New Refrigerants
CN.60.E
Practical Application of Refrigerant R 600a Isobutane
in Domestic Refrigerator Systems
EN 60335-2-24
Safety of household and similar appliances Part 2:
Particular requirements for refrigerators,
food freezers and ice-makers
4.3 Evacuation
4.4 Cleanliness
of components
5 Service
References
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
CN.60.F1.02 Produced by Danfoss November 2000
The Danfoss product programme
for the refrigeration industry contains:
www.danfoss.com/compressors
Compressors for Refrigeration and Air Conditioning
A wide range of hermetic reciprocating compressors and scroll compressors
as well as aircooled condensing units. The product range is applied in air
conditioning units, water chillers and commercial refrigeration systems.
Appliance Controls
For the regulation of refrigeration appliances and freezers Danfoss supply a
CFC-free product range of electromechanical thermostats for refrigerators and
electromechanical thermostats for refrigerators and freezers produced according
to customer specification; Hermetic valves for refrigerator/freezer combina-
tions and for energy saving applications; Service thermostats – for all refrigerat-
ing and freezing appliances.
Refrigeration and Air Conditioning Controls
With our full product range we cover all the requirements for mechanical and
electronically controlled refrigeration systems. The functions cover: control, safety,
system protection and monitoring. Our products are applied for all commer-
cial- and industrial refrigeration applications as well as for air conditioning.
Compressors for Refrigerators and Freezers
Hermetic compressors and fan-cooled condensing units for household refrig-
eration units such as refrigerators and freezers, and for commercial installa-
tions such as sales counters and bottle coolers. Compressors for heating
pump systems. 12 and 24 V compressors for refrigerators and freezers in
commercial vehicles, buses, and boats.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Danfoss Refrigerant R290 Propane in Small Hermetic Systems Installation guide

Type
Installation guide

Danfoss Refrigerant R290 Propane in Small Hermetic Systems provides an efficient and environmentally friendly cooling solution for your refrigeration needs. Its high energy efficiency and low global warming potential make it a sustainable choice. Designed for use in small hermetic systems like refrigerators and freezers, it offers reliable performance and safety features to ensure peace of mind. Choose Danfoss R290 Propane for a greener and more efficient cooling experience.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI