Danfoss Information release 1.06 Operating instructions

Type
Operating instructions
NEW UPDATES RELEASE 1.06
Software update for DHP-R (1 / 1)
RELEASE 1.06 DHP-R
BOOTLOADER 3.11
FIRMWARE 2.39B
WEBPAGES 1.13B
APPSCRIPT 1.14
DISPLAY 1.25B
NEW UPDATES RELEASE 1.06
Broken outdoor temperature sensor halts the heatpump
As the break to outdoor sensor occurs, the outdoor temperature is shortly
interpreted as very high, placing the heat pump in ’Heat stop’, thus blocking it
from runnig until the deactivation time limit has run out. This issue has been
fixed.
Webpages on controller don’t automatically update.
The webpages on the controller didn’t automatically update. Webpages will
automatically update according to set time with this release.
New alarm; ’Master conflict’
If two or more heatpumps are connected as masters, a communication
problem arises between connected slaves, cooling and expansion modules.
Alarm ’Master conflict’ will indicate this problem.
Modbus
Communication protocol Modbus has been implemented in this release in
order to connect the DHP-R to supervisory control systems.
Modbus is connected to RS232-port on the WM HPC. A new menu, ‘Modbus’,
has been added to ‘SYSTEM SETTINGS’.
  • Page 1 1

Danfoss Information release 1.06 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI