MODELSCSMSTRSXANDCSMSTRGT‐EnhancedModularContr ollerSeries
Master
PROVIDES ENHANCED FEATURES FOR DATA ACQUISITION OR
MULTI-ZONE PID CONTROL APPLICATIONS
WEBSERVER PROVIDES WORLDWIDE ACCESS TO DATA LOGS
AND VIRTUAL HMI
VIRTUAL HMI OFFERS BUILT-IN PC-BASED SCADA
FUNCTIONALITY
PERFORMS HIERARCHICAL CONTROL OF OTHER MODULES IN
THE MODULAR CONTROLLER SERIES
STORES MODULE CONFIGURATION INFORMATION, AND
AUTOMATICALLY REPROGRAMS REPLACED MODULES
EXTENSIVE BUILT-IN DRIVER LIST ALLOWS EASY DATA
MAPPING TO PLCs, PCs, AND SCADA SYSTEMS
INDEPENDENT SERIAL PORTS PROVIDE VIRTUALLY
UNLIMITED INTEGRATION METHODS
10 BASE-T/100 BASE-TX ETHERNET CONNECTION PROVIDES
NETWORKING CAPABILITY
SUPPORTS UP TO 16 MODULAR CONTROLLER SERIES
MODULES
COMPACTFLASH
®
SLOT ALLOWS PROCESS DATA TO BE
LOGGED DIRECTLY TO CSV FILES
GENERALDESCRIPTION
The Model CSMSTR is a communications and control platform
designed for use with Modular Controller Series slave modules. The
CSMSTR uses a proprietary high speed serial protocol to communicate,
via backplane connection, with up to 16 slave modules. Through the
same connection, the Master also provides power to the modules.
When powered up, the CSMSTR automatically identifies and
addresses connected slave modules. By storing the configuration
information of all of the modules, the CSMSTR is able to automatically
configure modules if they are replaced.
The Master provides high-speed RS232/422/485 communication ports
and an Ethernet port for connection to PCs, PLCs, and SCADA systems.
An extensive list of master and slave protocol drivers are available to
allow the CSMSTR to share and exchange variable data with external
devices. The 10 Base-T/100 Base-TX Ethernet port can also be used to
connect and share data with other devices at high speeds. The virtual
HMI feature allows you to create and control an HMI from any networked
PC. An onboard CompactFlash slot provides storage for the Master’s
built-in data logger.
The design of the Modular Controller Series high density packaging
and DIN rail mounting saves time and panel space. The controller snaps
easily onto standard top hat (T) profile DIN rail.
SOFTWARE
The CSMSTR is programmed with Crimson
®
2.0 software for
Windows
®
2000 or later platforms. The software is an easy to use,
graphical interface which provides a means of communication
configuration, as well as commissioning and calibration of new systems.
CONTENTSOFPACKAGE
- CS Master
- Termination Plug
- Terminal block for connecting power
- Rubber End Cap
CompactFlash is a registered trademark of CompactFlash Association.
DIMENSIONSIninches(mm)
5.30
(134.7)
RS232
ETHERNET
CF
STS
USB/PG
RS485
RS232/PG
3.09 (78.5)
4.15 (105.4)
C
US LISTED
U
L
R
IND. CONT
. EQ.
34AD
C
US LISTED
U
L
R
3PWL
PROGRAMMABLE
CONTROLLERS
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
-2-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
1. POWER: 24 VDC ± 10%
400 mA min. (1 module)
3.5 Amps max. (16 modules + Expansion Card)
Must use NEC Class 2 or Limited Power Source (LPS) rated power
supply.
2. COMMUNICATIONS:
USB/PG Port: Adheres to USB specification 1.1. Device only using
Type B connection.
Serial Ports: Format and Baud Rates for each port are individually
software programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12
DH485 TXEN: Transmit enable; open collector, V
OH
= 15 VDC,
V
OL
= 0.5 V @ 25 mA max.
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
3. LEDs:
STS – Status LED indicates condition of master.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
CF – CompactFlash LED indicates card status and read/write activity
4. MEMORY:
On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM:
CSMSTRSX: 2 Mbytes
CSMSTRGT: 8 Mbytes
Memory Card: CompactFlash Type II slot for Type I and Type II cards.
5. REAL-TIME CLOCK: Typical accuracy is less than one minute per
month drift.
Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.
A “Battery Low” system variable is available so that the programmer
can choose specific action(s) to occur when the battery voltage
drops below its nominal voltage.
This unit is NOT field serviceable. All work must be done by a
qualified technician.
6. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -30 to +70 °C
Operating and Storage Humidity: 80% max relative humidity,
non-condensing, from 0 to 50 °C
Vibration to IEC 68-2-6: Operational 10 to 150 Hz, 1 g.
Shock to IEC 68-2-27: Operational 25 g.
Altitude: Up to 2000 meters
7. CONSTRUCTION: Case body is burgundy high impact plastic and
stainless steel. For indoor use only. Installation Category II, Pollution
Degree 2.
8. POWER CONNECTION: Removable wire clamp screw terminal block.
Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
9. MOUNTING: Snaps onto standard DIN style top hat (T) profile
mounting rails according to EN50022 -35 x 7.5 and -35 x 15.
10.CERTIFICATIONS AND COMPLIANCES:
Check each module’s specifications to determine system compliance.
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
Safety requirements for electrical equipment for measurement, control,
and laboratory use:
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and
Measuring Circuits
EN 61010-2-201: Particular Requirements for Control Equipment
RoHS Compliant
UL Listed: File #E302106
UL Hazardous: File #E317425
ABS Certificate #09-HS426719-B-4-PDA
11.WEIGHT: 15.1 oz (456.4 g)
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF
OR AREA IS KNOWN TO BE NON-HAZARDOUS.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF
OR AREA IS KNOWN TO BE NON-HAZARDOUS.
SPECIFICATIONS
HARDWAREINSTALLATION
DIN rail should be mounted horizontally so that the unit’s ventilation
holes are vertical in relation to cabinet orientation. A minimum clearance
of 1 inch (25.4 mm) should be maintained above and below the unit in
order to ensure proper thermal regulation.
The unit shall be installed inside a UL Listed Industrial Control Panel or
similar type of enclosure. A minimum 3.2 mm distance shall be
maintained between the hazardous live parts of the equipment and
accessible parts of the fire/electrical enclosure.
Figure 1 - Attach CSMSTR Master To DIN Rail and Remove Rubber
End Cap
1
2
REMOVE
SAFETYSUMMARY
All safety related regulations, local codes and instructions that appear
in the manual or on equipment must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment
connected to it. If equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other
actuators not equipped with safeguards. To do so can be potentially
harmful to persons or equipment in the event of a fault to the unit. An
independent and redundant temperature limit indicator with alarm outputs
is strongly recommended.
WARNING - EXPLOSION HAZARD - DO NOT D
EQUIPMENT UNLESS POWER HAS BEEN SW
OR AREA IS KNOWN TO BE NON-HAZARDOU
CAUTION: Risk of Danger.
Read complete instructions prior to installation
and operation of the unit.
-3-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
PROTOCOLCONVERSION
Mount the Master as shown under Hardware Installation Figure 1
above. Install the rubber end cap. The end cap protects the pins from
damage. Configure the Master for zero modules.
COMPACTFLASH®CARD
CompactFlash socket is a Type II socket that can accept either Type I
or II cards. Use cards with a minimum of 4 Mbytes and formatted to a
maximum of 2 Gbytes (see Note box) with the Master’s CompactFlash
socket. Cards are available at most computer and office supply retailers.
CompactFlash cards can be used for configuration transfers, data
logging, and trending.
Information stored on a CompactFlash card can be read by a card
reader attached to a PC. This information is stored in IBM (Windows
®
) PC
compatible FAT16 file format.
NOTE
For reliable operation of this and other Red Lion products, one of the
following brands of CompactFlash card must be used...
SimpleTech SMART
®
Modular swissbit
®
SanDisk
®
Silicon Systems
Not all of the above manufacturers offer CompactFlash cards recognized
to UL standards, which may be required for your application.
Although Red Lion Controls products limit use of CompactFlash card
memory to 2 GB, cards with a larger capacity can be used. They
MUST be formatted to 2 GB and use the FAT 16 file system. It is
recommended to format the CF card using the format utility from
within Crimson.
CompactFlash
(Top Side)
CompactFlash-
Insert Top Side
Towards Left
Note: Do not remove or insert
the CompactFlash card while
power is applied.
USB/PG
ETHERNET
RS232
CF
RS485
DIN RAIL
5
STS
RS232/PG
Figure 3 - Attach Termination Plug*
* Supplied with CSMSTR Master Module.
ETHERNET
RS232
CF
USB/PG
RS485
STS
RS232/PG
DIN RAIL
Figure 4 - Installation Complete
Figure 2 - Attach Slave Bases To DIN Rail
RS232
ETHERNET
CF
RS485
STS
RS232/PG
USB/PG
DIN RAIL
4
DEPRESS
3
4
1.00"
TOP
min. clearance
1.00"
BOTTOM
min. clearance
-4-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
POWER SUPPLY REQUIREMENTS
It is very important that the power supply is mounted correctly if the unit
is to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not
more than 6 feet (1.8 m) of cable between the supply and the
master. Ideally, the shortest length possible should be used.
– The wire used to connect the master’s power supply should be at
least 22-gage wire. If a longer cable run is used, a heavier gage wire
should be used. The routing of the cable should be kept away from
large contactors, inverters, and other devices which may generate
significant electrical noise.
– A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rating is to be used. This type of power supply provides
isolation to accessible circuits from hazardous voltage levels
generated by a mains power supply due to single faults. SELV is an
acronym for “safety extra-low voltage.” Safety extra-low voltage
circuits shall exhibit voltages safe to touch both under normal
operating conditions and after a single fault, such as a breakdown of
a layer of basic insulation or after the failure of a single component
has occurred.
Visit www.redlion.net for a complete list of our PSDR Series of NEC
Class 2 power supplies.
EMCINSTALLATIONGUIDELINES
Although Red Lion Controls products are designed with a high degree
of immunity to Electromagnetic Interference (EMI), proper installation and
wiring methods must be followed to ensure compatibility in each
application. The type of the electrical noise, source or coupling method
into a unit may be different for various installations. Cable length, routing,
and shield termination are very important and can mean the difference
between a successful or troublesome installation. Listed are some EMI
guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield
connection should be made as short as possible. The connection point
for the shield depends somewhat upon the application. Listed below
are the recommended methods of connecting the shield, in order of
their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end
where the unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually
when the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with
AC power lines, conductors, feeding motors, solenoids, SCR controls,
and heaters, etc. The cables should be run through metal conduit that
is properly grounded. This is especially useful in applications where
cable runs are long and portable two-way radios are used in close
proximity or if the installation is near a commercial radio transmitter.
Also, Signal or Control cables within an enclosure should be routed as
far away as possible from contactors, control relays, transformers, and
other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI
suppression devices such as Ferrite Suppression Cores for signal and
control cables is effective. The following EMI suppression devices (or
equivalent) are recommended:
Fair-Rite part number 0443167251 (Red Lion Controls #FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls #LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize
radiated and conducted noise (EMI), some type of contact protection
network is normally installed across the load, the contacts or both. The
most effective location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal
oxide varistor (MOV) across an AC inductive load is very effective at
reducing EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a
transistor switch, care must be taken not to exceed the breakdown
voltage of the transistor when the load is switched. One of the most
effective ways is to place a diode across the inductive load. Most
Red Lion products with solid state outputs have internal zener diode
protection. However external diode protection at the load is always a
good design practice to limit EMI. Although the use of a snubber or
varistor could be used.
Red Lion part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the
instrument. When a separate input and output common is provided,
they should not be mixed. Therefore a sensor common should NOT be
connected to an output common. This would cause EMI on the
sensitive input common, which could affect the instrument’s operation.
Visit www.redlion.net/emi for more information on EMI guidelines,
Safety and CE issues as they relate to Red Lion products.
WIRING
POWERCONNECTION
COMMON
+24 VDC
+24
N/C
COMM
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
WHILE CIRCUIT IS ALIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
INPUT AND OUTPUT (I/O) WIRING MUST BE IN ACCORDANCE
WITH CLASS I, DIV. 2 WIRING METHODS AND IN ACCOR-
DANCE WITH THE AUTHORITY HAVING JURISDICTION.
-5-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
COMMUNICATIONPORTS
Tx
RS232
RTS
COMM
COMM
CTS
Rx
RS232/PG
RS232
RS485
USB/PG
RS232/PG
ETHERNET
CF
STS
CBLxxxxx*
CHASSIS GND
OR
CBLPROG0
REM
SLC 5/03 CPU
RUN
BATT
FLT
RUN
RS232
DH485
FORCE
PROG
VDC
PWR OUT +24
PWR OUT COM
VAC NEUT
120/240 VAC
USER
POWER
POWER
ETHERNET
RS232
RS485
USB/PG
RS232/PG
CF
STS
CBLxxxxx*
REM
SLC 5/03 CPU
RUN
RUN
FLT
BATT
FORCE
PROG
DH485
RS232
120/240 VAC
VAC NEUT
CHASSIS GND
VDC
PWR OUT COM
PWR OUT +24
USER
POWER
POWER
CTS
Tx
COMM
Rx
RTS
COMM
RS232
RS232
* Use appropriate communications cable. See Ordering
Information for descriptions of the available cables.
WARNING: Do NOT use a standard DH-485
cable to connect this port to Allen Bradley
equipment.
TxB
RxB
RxA
TxA
TxB
COMM
TxEN
TxA
RS485
RS485
RS232
ETHERNET
RS485
USB/PG
RS232/PG
CF
STS
CBLxxxxx*
REM
SLC 5/03 CPU
RUN
RUN
FLT
BATT
FORCE
PROG
DH485
RS232
120/240 VAC
VAC NEUT
CHASSIS GND
VDC
PWR OUT COM
PWR OUT +24
USER
POWER
POWER
RS232
RTS
COMM
Tx
COMM
CTS
Rx
YELLOW LED
GREEN/AMBER LED
RS232/PG
USB/PG
ETHERNET
CBLPROG0
CBLUSB00
OR
Ethernet (Crossover)
OR
STS
CF
ETHERNET
RS485RS232
USB HOST
RS232/PG
PROGRAMMINGPORTS
-6-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
CONFIGURINGAMASTER
The Master is configured using Crimson 2.0 software. Crimson
software is available as a no charge download from Red Lion’s website.
Crimson updates for new features and drivers are posted on the website
as they become available. By configuring the Master using the latest
Crimson version, you are assured that your unit has the most up to date
feature set. Crimson software can configure the Master through the
RS232/PG port, USB/PG port, Ethernet or CompactFlash. The USB/PG
port is connected using a standard USB cable with a Type B connector.
The driver needed to use the USB port will be installed as part of
Crimson configuration. The RS232/PG port uses a programming cable
made by Red Lion to connect to the DB9 COM port of your computer. If
making your own cable, refer to the “Master Port Pin Outs” for wiring
information.
The CompactFlash can be used to program a Master by placing a
configuration file and firmware on the CompactFlash card. The card is
then inserted into the target Master and powered. Refer to the Crimson
2.0 literature for more information on the proper names and locations of
the files.
CABLESANDDRIVERS
Red Lion has a wide range of cables and drivers for use with many
different communication types. A list of these drivers and cables along
with pin outs is available from Red Lion’s website. New cables and
drivers are added on a regular basis. If making your own cable, refer to
the “Master Port Pin Outs” for wiring information.
USB,DATATRANSFERSFROMTHE
COMPACTFLASHCARD
In order to transfer data from the CompactFlash card via the USB port,
a driver must be installed on your computer. This driver is installed with
Crimson software and is located in the folder C:\Program Files\Red Lion
Controls\Crimson 2.0\Device\ after Crimson 2.0 is installed. This may
have already been accomplished if your Master was configured using the
USB port.
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
MASTERPORTPINOUTS
EXPANSION
24VDC ±10%
USB/PG
TxA (PIN 8)
GREEN/
YELLOW
LED
LED
AMBER
(NIC)
ETHERNET
RS232
PORT
COMMS
COMMS
PORT
COMM
CTS (PIN 1)
COMM
Rx
Tx
RTS (PIN 6) TxB
COMM
RxA
RxB
TxA
TxB (PIN 1)
TxEN
RS485
ETHERNET
RS232
RS485
CF
RS232/PG PORT
RTS (PIN 6)
CTS (PIN 1)
USB/PG
RS232
COMM
Tx
COMM
Rx
RS232/PG
STS
POWER
CONNECTOR
N/C
3
2
COMMON
1
PORT
TROUBLES HOOTING
If for any reason you have trouble operating, connecting, or
simply have questions concerning your new Master, contact
Red Lion’s technical support.
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
COMMUNICATINGWITHTHEMASTER
GREEN/AMBER LED
YELLOW LED
Standard Ethernet cable
ETHERNET
RS232
RS485
USB/PG
RS232/PG
CF
STS
PORT3‐ETHERNETCONNECTION
-7-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
Once the driver is installed, connect the Master to your PC with a USB
cable, and follow “Mounting the CompactFlash” instructions in the
Crimson 2.0 user manual.
Note that using the USB port for frequent data transfers is not
recommended. For frequent data transfers it is recommended that the
Ethernet connection be used. Through the Ethernet connection a web
page can be set up to view logged data. Refer to the Crimson 2.0 manual
for details.
Note: The USB port is for system set-up and diagnostics and is not
intended for permanent connection.
ETHERNETCOMMUNICATIONS
Ethernet communications can be established at either 10 BASE-T or
100 BASE-TX. The Master’s RJ45 jack is wired as a NIC (Network
Interface Card). For example, when wiring to a hub or switch use a
straight-through cable, but when connecting to another NIC use a
crossover cable.
Refer to the Crimson manual and Red Lion’s website for additional
information on Ethernet communications.
RS232PORTS
The Master has two RS232 ports. There is the RS232/PG port and the
COMMS port. Although only one of these ports can be used for
programming, both ports can be used for communications with a PLC.
The RS232/PG port can be used for either master or slave protocols.
RS422/485COMMSPORT
The Master has one RS422/485 port. This port can be configured to
act as either RS422 or RS485.
Note: All Red Lion devices connect A to A and B to B. Refer to
www.redlion.net for additional information.
DH485COMMUNICATIONS
The Master’s RS422/485 COMMS port can also be used for Allen
Bradley DH485 communications.
WARNING: DO NOT use a standard DH485 cable to connect this port
to Allen Bradley equipment. A cable and wiring diagram are available
from Red Lion.
LEDs
STSSTATUSLED
The green Status LED provides information regarding the state of the
Master, as well as the rest of the system. This includes indication of the
various stages of the start-up routine (power-up), and any errors that may
occur.
Startup Routine
Error States
CFLED
1. Do not turn off power to the unit while this light is flickering. The unit writes data in
two minute intervals. Later Microsoft operating systems will not lock the drive
unless they need to write data; Windows 98 may lock the drive any time it is
mounted, thereby interfering with logging. Refer to “Mounting the CompactFlash”
in the Crimson 2.0 User Manual.
USERCOMMUNICATIONPORTS‐TX/RXLEDS
Note: LEDs are not available on the Programming Port: RS232/PG.
ETHERNETLEDS
TX
5V
8
1
7
2
TxB
TxA
130K
130K
5
TxEN (OC)
RX
130K
5V
130K
RxB
4
RxA
3
COMM
6
RS422/485 4-WIRE
CONNECTIONS
RS485 2-WIRE
CONNECTIONS
TxEN (OC)
TX/RX
130K
5
TxA
2
8
130K
5V
7
1
TxB
6 COMM
INDICATION
Rapidly Flashing
Master is currently running the boot loader and/or
being flash upgraded by Crimson software.
Steady Master is operating properly.
LED INDICATION
1 blink, pause, repeat
One or more slave modules are missing from the
system. Master and installed modules will perform
normally in this state.
2 blinks, pause, repeat
Missing configuration, or configuration being updated
by Crimson program
3 blinks, pause, repeat
Quantity of module bases does not match
configuration file. Master will not communicate with the
modules until the error is corrected.
4 blinks, pause, repeat
Termination plug not installed, or one or more bases
are malfunctioning. Master will not communicate with
the modules until the plug is reinstalled, and power is
cycled.
LED INDICATION
Off No CompactFlash Card is present.
Steady Valid CompactFlash card is present.
Flashing Rapidly CompactFlash card is being checked.
Flickering
Unit is writing to the CompactFlash, either because it
is storing data, or because the PC connected via the
USB port has locked the drive.
1
Flashing Slowly Incorrectly formatted CompactFlash card present.
LED INDICATION
GREEN Transmitting
RED Receiving
LED INDICATION
YELLOW (Solid) Link Established
YELLOW (Flashing) Network Activity
GREEN 10 BASE-T Communications
AMBER
100 BASE-TX Communications
-8-
Released 2016-10-07 Bulletin No.CSMSTRSX-L
Drawing No. LP0610
ORDERINGINFORMATION
Note: Certain modules are not suitable for use in Hazardous locations. Check each module's specifications prior to installation.
1
Visit www.redlion.net for a complete list of PID modules, data acquisition modules, communications drivers and cables.
2
Use this part number to purchase Crimson on CD with a printed Modular Controller Manual, USB cable, and RS-232 cable. Otherwise,
download at no charge from www.redlion.net.
3
Antenna is NOT included with the card. Must be purchased separately if needed.
4
Industrial grade two million write cycles. SMART Modular Technologies model SG9CF (UL Listed Directory Category NWGQ)
.
TYPE MODEL NO. DESCRIPTION PART NUMBER
Master Module
CSMSTR
1
Modular Controller Master, Multi Comms ports and Ethernet CSMSTRV2
Modular Controller Master with multiple protocol converter, Ethernet and expansion slot CSMSTRLE
Modular Controller Master with multiple protocol converter, data logger, web server with Virtual HMI
up to QVGA (320 x 240) size and expansion slot
CSMSTRSX
Modular Controller Master with multiple protocol converter, data logger, web server with Virtual HMI
up to VGA (640 x 480) size and expansion slot with increased SDRAM
CSMSTRGT
Communications
Cables (10 feet)
CBL
RS232 Programming Cable CBLPROG0
USB Cable
CBLUSB00
Communications Cables
1
CBLxxxxx
Software SFCRM2
Crimson 2.0
2
, Modular Controller Manual, and Download Cable
SFCRM2MC
Power Supply PSDR
DIN Rail Mounted Power Supply PSDRxxxx
Accessories
XCCN
CANopen option card for Modular Controller or Data Station Plus
XCCN0000
XCDN
DeviceNet option card for Modular Controller or Data Station Plus XCDN0000
XCHSPA
GSM/HSPA+ Modem Option Card
3
for Modular Controller or Data Station Plus
XCHSPA00
XCPB
PROFIBUS option card for Modular Controller or Data Station Plus XCPBDP00
XCRS
RS232/485 option card for Modular Controller or Data Station Plus XCRS0000
G3CF
CompactFlash Card
4
G3CFxxxx
ANT
2G/3G 3" hinged antenna ANT-TG090113
2G/3G/4G LTE low profile direct permanent mount antenna, IP67 rated ANT-G30B108111
2G/3G 4.5" whip magnetic mount antenna, IP65 rated ANT-GA107201111
2G/3G low profile direct permanent mount antenna, IP65 rated ANT-G21B301111
Rail Stops (Qty 2) RSRSTP00
Replacement Base CSBASE00
Replacement Termination Plug CSTERM00
Replacement Rubber End Cap
CSBUNG00
LIMITED WARRANTY
(a) Red Lion Controls Inc., Sixnet Inc., N-Tron Corporation, or Blue Tree Wireless Data, Inc. (the “Company”)
warrants that all Products shall be free from defects in material and workmanship under normal use for the period of
time provided in “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the
Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO
WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF
MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY
AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY; WHETHER EXPRESS
OR IMPLIED BY LAW, COURSE OF DEALING, COURSE OF PERFORMANCE, USAGE OF TRADE OR
OTHERWISE. Customer shall be responsible for determining that a Product is suitable for Customer’s use and that
such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result
of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii) Customer
alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if
Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH
IN PARAGRAPH (a).