4.1 Operation of a condensing dehumidier:
Thebasisofanycondensingdehumidieris
aclosedcoolingcircuit,whichworksinaccor-
dance with the heat pump principle. A fan draws
inthehumidambientair.Theairrstpasses
throughaparticulatelterinstalledtoprotect
the heat exchangers before the air is carried
over the evaporator. As air is drawn over the
cold surface of the coil, it is cooled below its
dew point. A large proportion of the water va-
por contained within the air is condensed and
converted to condensate. The water that has
become condensate is contained in a conden-
sation tray installed under the evaporator and
thentransferreddirectlyintothedrainoutow
or collected in a corresponding container. Next,
the air stream which has now been dehumidi-
edpassesthroughthecondenser,whereitis
heated through the condensation heat of the
cooling circuit. The waste heat from the fan and
the compressor is also partly absorbed by the
airstreamtransferredviathedehumidier.Asa
result,thedehumidiedairintroducedintothe
area is always warmer than it was when it en-
teredthedehumidier.Theriseintemperature
can be in the order of 18 to 25 °F
4.2 Sizing a Dehumidier
Aftertherequireddehumidicationprocedure
forthespecicapplicationhasbeendetermined
on the basis of calculations (see chapter 6),
theappropriatedehumidiercanbeselected
through its corresponding performance dia-
gram. The performance and degree of effective-
nessofcondensingdehumidiersincreaseas
the temperature goes up, and decrease as tem-
peratures go down. In the technical documenta-
tion, with respect to performance, generally only
standard values at 86°F and 80%RH, some-
times also at 80°F and 60%RH are provided as
a performance guide.
In many cases, only the maximum possible de-
humidicationperformanceat95°Fand80%
RHisstated.Withrespecttothespecicappli-
cationconcerned,thesespecicationsareoften
insufcienttoenableanestimationofthese-
lected system’s capability to actually provide the
requireddehumidicationperformanceunder
the conditions for which it was designed. Most
manufacturers typically supply performance
diagramstofacilitateasufcientlyreasonable
determinationoftheactualdehumidication
capacity under the design conditions.
Example:acondensingdehumidierisstatedin
thedocumentationashavingadehumidication
performanceof88lbs/24hat86°Fand80%
RH.
Bycalculation,thedehumidiertobeselect-
ed should have a dehumidifying capacity of
44lbs/24hat68°Fand60%RH.Theactual
dehumidicationcapacityattherequiredcon-
ditions is shown in the manufacturer’s perfor-
mance diagram.
Result:Insteadoftherequireddehumidication
performanceof44lbs/24h,thesystemonly
hasacapacityof26lbs/24hunderthedesign
conditions.Therefore,itwouldbesignicantly
undersized. This example shows how important
it is to always determine the necessary perfor-
manceinrelationtotherequireddesigncondi-
tions. Nowadays, some manufacturers choose
not to Issue performance diagrams and instead
Dehumidier performance lbs/24h
Temperature in °F
41
0
33
66
99
59 7750
22
55
88
11
45
77
110
68 86 95
80%
70%
60%
50%
32
12
Figure 5: Dehumidier Performance