Contec CPS-RRY-4PCC Owner's manual

Type
Owner's manual

Contec CPS-RRY-4PCC is a module with a function of relay output interface for configurable controllers. It features four channels of relay outputs (Form C) with independent common, making it suitable for various applications such as industrial automation, building automation, and security systems. The product is easy to install and use, with clear instructions provided in the accompanying manual.

Contec CPS-RRY-4PCC is a module with a function of relay output interface for configurable controllers. It features four channels of relay outputs (Form C) with independent common, making it suitable for various applications such as industrial automation, building automation, and security systems. The product is easy to install and use, with clear instructions provided in the accompanying manual.

1 CPS-RRY-4PCC
CONPROSYS Series
CPS-RRY-4PCC Product Guide
CONTEC CO., LTD.
Thank you for purchasing this product. The product you have purchased consists of the following
items. Check, with the following list, that your package is complete. If you find any item either
missing or damaged, please contact the sales representative you purchased the product from.
Be sure to read the Reference Manual (Hardware) and either Reference Manual (Software) or
System Setup Guide (Software) thoroughly to use this product correctly.
About the Unit
This product is a module with a function of relay output interface to add to the configurable type of
our controller.It contains four channels of relay outputs (Form C) with independent common.
Product Configuration List
- Product [CPS-RRY-4PCC]…1
- Product Guide…1 - Warranty Certificate…1
- Serial Number Label…1 - 3-pin Connector4
About the manual
Read and check the details by downloading the manual from the CONTEC website
(https://www.contec.com/). (myCONTEC membership registration is required for downloading)
1. From the Contec website, expand Downloads located on the upper side, and click Technical guides.
2. Enter the model type you wish to search in the box and click Search. From the search results, click the check-mark in the
“Manual/Technical documents” of this product.
3. Download the appropriate manual from “Manual/Technical documents”.
Safety Precautions
Understand the following definitions and precautions to use the product safely.
The caution mark ”on the product requires users to read the manual and study the meaning of the
marks without fail.
Safety Information
This document provides safety information using the following symbols to prevent accidents resulting
in injury or death and the destruction of equipment and resources. Understand the meanings of these
labels to operate the equipment safely.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury or in property damage.
Product
Guide
Serial Number LabelProduct Warranty CertificateProduct Guide
Warranty
Certificate
3-pin Connector
DANGER
WARNING
CAUTION
CPS-RRY-4PCC Product guide
CPS-RRY-4PCC
2
Handling Precautions
- Do not use the product in locations exposed to a flammable or corrosive gas. It may cause explosion, fire, electrical
shock, or malfunction.
- Do not allow the device to come into contact with foreign substances (metal particles, flammable substances,
liquids, etc.) Otherwise, it can cause fire or electrical shock.
- Do not place the product in an unstable location or use incomplete mountings. Otherwise, it may cause the device to
fall.
- Be sure to connect the product to the stipulated power supply voltage. Connecting to a different voltage might cause
a fire or electrical shock.
- If the product is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
- The product is not intended for use in aerospace, space, nuclear power, medical equipment, or other applications
that require a very high level of reliability. Do not use the product in such applications.
- If using the product in applications where safety is critical such as in railways, automotive, or disaster prevention
or security systems, please contact your retailer.
- Be certain the following requirements are satisfied when using the product.
- Overvoltage category 2 - Indoor use - Altitude up to 2000m - Applicable POLLUTION DEGREE 2
When using the product at high altitudes, refer to the relational expression below to find an appropriate ambient
temperature. The heat dissipation decreases due to air pressure drop and could lead to damages or a shorter
product life.
- Ambient temperature = 60[°C] - 0.005 x altitude [m]
An Example) The product is used at 2000 meters 60°C - (0.005 x 2000m) = 50°C (Ambient temperature)
- Do not use or store the product in a location exposed to extremely high or low temperature that exceeds range of
specification or susceptible to rapid temperature changes.
e.g. - Exposure to direct sun - In the vicinity of a heat source
- Do not use the product in extremely humid or dusty locations. It is extremely dangerous to use the product with its
interior penetrated by water or any other fluid or conductive dust. If the product must be used in such an
environment, install it on a dust-proof control panel, for example.
- Avoid using or storing the product in locations subject to shock or vibration that exceeds range of specification.
- When transporting the product, take suitable measures to avoid applying shock or vibration directly to the product.
Impact resistance: 15G (11ms) below.
- Use the product in the specified operating condition (temperature, humidity, vibration and shock).
- Avoid installing in the place where ventilation of the product may compromise. Insufficient aeration could heat up
the product and lead to malfunctions or damages.
- Do not use the product in the vicinity of devices that generate strong magnetic force or noise. Such products will
cause the product to malfunction (stop, reboot).
- Do not use or store the product in the presence of chemicals.
- When removing connectors or cables, always unplug the power cables and confirm the LEDs are turned off.
- Do not modify the product. CONTEC will bear no responsibility for any problems, etc., resulting from modifying the
product.
- In the event of failure or abnormality (foul smells or excessive heat generation), unplug the power cables
immediately and contact your retailer.
- To connect with peripherals, use a grounded, shielded cable.
- To clean the product, wipe it gently with a soft cloth dampened with either water or mild detergent. Do not use
chemicals or a volatile solvent, such as benzene or thinner, to prevent the paint to be scraped or discolored.
- When connecting cables, first check the shapes of connectors, and then insert them in the correct orientation. After
they are connected, do not put too much load on the connected part. Doing so may result in poor contact or damage
to the product and the connected part.
- Do not touch metal parts or terminals with your hands when the product is in operation. Otherwise, the product
may malfunction, or cause failure.
- Do not touch the product or connectors with a wet hand to avoid electric shock.
- The specifications of the product are subject to change without notice for enhancement and quality improvement.
Even when using the product continuously, be sure to read the manual in the CONTEC’s website and understand
the contents.
- When the product is used in a place that is affected by overcurrent or overvoltage (lightning surge), select
appropriate surge protection device for all of the route (signal line etc.). Consult with the specialist regarding
selecting, purchasing, and setting the surge protection device.
- When disposing of the product, follow the disposal procedures stipulated under the relevant laws and municipal
ordinances.
DANGER
CAUTION
CPS-RRY-4PCC Product guide
3 CPS-MC341-ADSC1-111
- Regarding the power supply of the product and digital I/O. For UL-certified, connecting to both SELV and Limited
Energy Circuit is required. Note that Class 2 power supply can also be used in the U.S.
- Always attach the end cover while power is active (the cover comes with the configurable type controller).
- The product is an open-type device (a device designed to be housed inside other equipment) and must always be
mounted inside a mechanical enclosure having enough strength.
- The product can become extremely hot during the operation. When you intend to touch the product for the
maintenance work, turn off the power first, and leave it to cool off for 20 minutes, then start the works.
- About a caution mark on the product : Touching the product may cause a burn as the surface becomes extremely
hot during the operation.
- Regardless of the foregoing statements, CONTEC is not liable for any damages whatsoever
(Including damages for loss of business profits) arising out of the use or inability to use this CONTEC product or
the information contained herein.
Installation Requirements
Installation location
Use this product indoors. Always use the product
within the enclosure.
Installation orientation
You can position the product in the orientation shown below.
Other orientations could cause problems such as malfunction
due to inadequate heat dissipation.
-Vertical installation (Installation angle 0°)
Make sure to gain proper space between the product
and devices that generate heat or exhaust air so that
the ambient temperature stays in the range specified
in the environment requirement.
Recommended installation angle
Recommended installation angle is 0. Other angles
may not satisfy the temperature specification of the
product.
Ambient temperature
The ambient temperature is decided from the multiple
measurement points which are a 50mm-distance from
the case. During the operation, adjust the air current
to make certain that the temperatures measured in the
points stay within the specified temperature.
- Note that although the ambient temperature is within the
specified range, an operational failure may occur if there
is other device generating high heat nearby; the radiation
will influence the product to increase its temperature.
- Do not install the product into the fully-sealed space
except the case in which the internal temperature is
adjustable by equipment such as an air conditioner. Long-
term usage might increase the temperature and lead to a
malfunction or other troubles.
- When using the product in a high temperature
environment, its life time will be shorten. Perform the
forced air cooling to counteract.
Spaces between the product and surrounding objects (ambient
temperature exemplar)
Cab le Connection
Use the supplied connector plug when connecting the product
to an external device.For wiring, strip off approximately 10mm
of the covered part of a wire rod and then insert it to the
opening. After the insertion, secure the wire rod with screws.
Applicable wires are AWG 28 - 12.
- For wires, please use single wire or terminal crimp wire,
ferrules
- Removing the connector plug by grasping the cable can
break the wire.
Nomenclature of Components
(1) LED : Indicates the status of the product.
(2) Relay Output : Connector for relay output. Use the
3-pin connector, included in this package.
(3) Stack Bus : Used for the configurative module power
supply and communication
CAUTION
*
*
**
*
*: 50mm
CAUTION
STATUS
RRY-4PCC
0
1
2
3
0
1
2
3
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
CPS-RRY-4PCC Product guide
CONTEC CO., LTD. August 2019 Edition
3-9-31, Himesato, Nishiyodogawa-ku, Osaka 555-0025, Japan
https://www.contec.com/ NA05046 (LYUA454)
08232019_rev3 [06062016]
No part of this document may be copied or reproduced in any form by any means without prior written
consent of CONTEC CO., LTD.
Nomenclature of Functions
LED Indicator
LED
Ope rat io n
Mea ning
STATUS
(Green,
Red)
Green
It indicates the system runs
nor mally.
Red
It will light up when the error
occurs.
Green
Flashing
It will flash upon initializing.
OFF
Power is off. *1
0-3 (Green)
ON
It will li ght up when relay is o n.
OFF
It indicates relay is off.
*1 The module is inactive during the booting of the controller.
Power will be supplied from the controller after the completion
Relay outout connector (0, 1, 2, 3)
This product has 4 channels of relay output.
Use the 3-pin connector, included in this package.
Connector type : 2EDGKC-5.08-3P-13 (or equivalent)
Pin
No.
Signal
Name
Mea ning
1 NC
This indicates the output si gnals (Normally closed
[NC]). It connects the input signals from the other
devices.
2 NO
This indicates the output si gnals (Normally open
[NO]). It connects the input signals from the other
devices.
3 C
This is a common terminal for output signals (Normally
open [NO], normally closed [NC]).
Stack Bus
It is used for power supply and communication to the
configurative modules.
Function specifications
Item
CPS-RRY-4PCC
Output
Number of output signal
channels
4 (Independent common)
Output format
Relay co ntacts (Form C) output
LED
0 - 3 (Green)
Operate time (ON)
Within 20ms
Release time (OFF)
Within 20ms
Contact resistance
(Initial state)
125 Max.
Relay
contact
Spec.
*1*2
Rated load
240VAC 6A (resistive load), 24VDC 5 A
(resistive lo ad)
Maximu m
voltage
400VAC, 300VDC
Maximu m
current
6A (AC), 5A (DC)
Item
CPS-RRY-4PCC
Mechanical
life expectancy
10,000,000 operations min or more
(Switching times : 300 operations/min)
Electrical
lifetime
50,000 operations min. (Switching times :
10 operations/min, with rated load)
Connector
2 pieces 5.08mm pitch 3-pin terminal
Applicable wire
AWG28 - 12
LED
Status (Green, Red)
Suppl y voltage
24VDC (±10%)
Current consumption
0.1 A ( Max.)
Physical dimensions (mm)
25.2(W)×94.7(D)×124.8(H)
(No projection included)
Wei ght
250g
Installation method
Quick mounting on the 35mm DIN rail
*1 To meet CE's requirements, the rating should be up to 240VAC/3A
(Load resistor), 24VDC/5A (Load resistor). As for UL's requirements,
the rating should be up to 240VAC/6A (Load resistor), 24VDC/5A
(Load resistor). Use the product within the specified ratings to satisfy
these requirements.
*2 Refer to the maximum switching capacity listed in the Reference
Manual (Hardware) and use the product within the specified voltage
and current range.
The maximum number of configurative modules
operating along with the configurative type controllers
is 16, and the total current consumption of the modules
should be less than 3.3A.
Installation Environment Requirements
Item
CPS-RRY-4PCC
Operating ambient
temperature
-20 - +60°C
Operating ambient
humidity
10 - 85%RH (No condensation)
Non-operating ambient
temperature
-20 - +60°C
Non-operating ambient
humidity
10 - 85%RH (No condensation)
Floating dust particles
Not to be excessi ve
Corrosive gases
None
Line-noise
resistance
Line noise
Signal Line /±1kV (IEC61000-4-4 Level 3 ,
EN61000-4-4 Level 3)
Static
electricity
resistance
Touch /±4kV (IEC61000-4-2 Level 2,
EN61000-4-2 Level 2)
Air /±8kV (IEC61000-4-2 Level 3, EN61000-4-
2 Level 3)
Vibration
resistance
Sweep
resistance
10 - 57Hz *3 /semi-amplitude vibration
0.15mm, 57 - 150Hz/2.0G
40minutes each in X, Y, and Z directions (JIS
C60068-2-6-compliant, IEC60068-2-6-
compliant)
Shock resistance
15G half-sine shock for 11ms in X, Y, and Z
directions
(JIS C 60068-2-27 -compliant, IEC 60068-2-27
-compliant)
Standard
VCCI Class A, FCC Class A,
CE Marking (EMC Directive Class A, Low
Voltage Directive, RoHS Directive), UL
*3 When you use an optional power product: 10 - 55Hz (See the manual
of optional power product for details)
STATUS
0
1
2
3
123
C
AUTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Contec CPS-RRY-4PCC Owner's manual

Type
Owner's manual

Contec CPS-RRY-4PCC is a module with a function of relay output interface for configurable controllers. It features four channels of relay outputs (Form C) with independent common, making it suitable for various applications such as industrial automation, building automation, and security systems. The product is easy to install and use, with clear instructions provided in the accompanying manual.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI