Dwyer GFD User manual

Type
User manual

This manual is also suitable for

SPECIFICATIONS
Nominal Voltage: 208-600 VAC
±10%, Phase-to-Phase, 50/60 Hz.
Max Continuous Voltage: 660
VAC, Phase-to-Phase.
Wiring Error Protection: Yes.
Detection Threshold: 11.7 k Ω
±20% @ 50 Hz; 9.3 k Ω ±20% @
60 Hz; Single Phase-to-Ground.
Detector Induced Fault
Current: 50 Hz: 7.5 mA @ 600
VAC (1 Phase-to-Ground shorted);
60 Hz: 9 mA @ 600 VAC (1
Phase-to-Ground shorted).
Indicators: Normal: (3) Green
LEDs, 2 Flashes/sec; Fault: (3)
Red LEDs, 2 Flashes/sec.
Power Required: 50 Hz: 2.5 VA
@ 600 VAC; 60 Hz: 3 VA @ 600
VAC.
Temperature Rating: Operate:
32° to 131°F (0° to + 55°C).
Enclosure: 94V-0 Flame
Retardant Black ABS Plastic Panel
Mount with 1/4˝ Plastic Electrical
Conduit Adapter, Encapsulated for
Environmental Protection.
Electrical Connection: (4) 2 ft.,
18 AWG, 600V, 105°C PVC
Stranded Wire with Wire Pin
Terminations, Jacketed with 18˝
Slit Nylon Conrrugated Tubing
.556˝ O.D.
Weight: 3.52 oz (99.8 g).
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Specifications - Installation and Operating Instructions
Model GFD 3-Phase Ground Fault Display
©Copyright 2008 Dwyer Instruments, Inc. Printed in U.S.A. 9/08 FR# R1-443644-00
1
[25.4]
1-45/64
[43.26]
4
[101.6]
The GFD Model 3-Phase Ground Fault Display is intended for the use
on grounded systems to detect and indicate the phase of the first ground
fault condition. This enables corrective action to avoid the potential hazards
resulting from a second ground fault. With a nominal 3 phase line voltage
applied, a flashing normal green LED gives indication of a non-fault condition
and integrity of the wire connection to the corresponding phase. When there
is a phase-to-ground fault or a lost connection to the corresponding phase
occurs a flashing red LED gives positive fault indication.
INSTALLATION
BE SURE TO TURN THE POWER OFF PRIOR TO INSTALLING THIS
DEVICE
1. Follow all Local, State, and National Electrical Codes when installing this
equipment.
2. A 7/8” hole or 1/2” conduit knockout will have to be located on a visible
surface of the panel being monitored. When mounting on a hinged door,
place the hole location as close to the panel hinge as possible. This will
reduce the amount of cable slack required to properly open and close the
panel door. See Figure 1.
3. Remove the mounting hardware and insert the wiring harness and the
threaded nipple through the hole. Secure the unit in place by reinstalling
the locknut. Do not over torque.
4. Refer to Figure 2 for proper wiring connections.
NOTE: Matched color pairs must be kept linear from line to load side of the
fuse(s). Solid color to the line side, white striped to load side.
5. TURN POWER ON. All three green LEDs should flash independently at
a rate of 2 flashes/sec, indicating a normal operating condition.
6. If all three LEDs do not flash, TURN POWER OFF and check wiring con-
nections.
Figure 1
Figure 2
Bulletin TE-GFD
MAINTENANCE
Upon final installation, no routine maintenance is required. A periodic check
of the system is recommended. The GFD model is not field serviceable and
should be returned if repair is needed (field repair should not be attempted
and may void warranty). Be sure to include a brief description of the prob-
lem plus any relevant application notes. Contact customer service to
receive a return goods authorization number before shipping.