Unit: inch (mm
Service Space
Service Access Door 1*
Electrical Box
( 17-11/16 (450))
(100)
3-15/16
Service Access Door 3
(50)
1-15/16
Min. 11-13/16
(300)
Upper Side
Bottom Side
Min. A
Min. 3-15/16
(100)
Min.
19-11/16
(500)
Min. 3-15/16
(100)
4-Suspension Bolt
W3/8 or M10
(Field-Supplied)
Service Access Door 2
( 17-11/16 (450))
( 17-11/16 (450))
(50)
(100)
1-15/16
(100)
3-15/16
* Service access door 1 is required for models
COB08M264B22S and COB12M264B22S.
P5417012-rev.3
7
4.2 InitialCheck
● InstalltheChange-OverBoxwithaproper
clearancearounditformaintenanceworking
space,asshowninFigure4.1below.
Size
Model
A
COB04M132B22S Min.3-15/16 (100)
COB08M264B22S
Min.15-3/4 (400)
COB12M264B22S
PurposeofEachServiceAccessDoor
Name Purpose
ServiceAccess
Door1
Useduringinspectionofindoorunit
connectingside.
ServiceAccess
Door2
Useduringinspectionofindoorunit
connectingside.
ServiceAccess
Door3
Useduringinspectionofelectrical
componentsinsideelectricalbox.
Figure4.1ServiceSpace
● Checktoensurethattheceilingissuciently
strongtosustaintheChange-OverBox.Ifthe
ceilingisweak,abnormalsoundandvibration
mayoccur.
● Whentheelectronicexpansionvalveinthe
Change-OverBoxisactivated,soundsmaybe
producedfromtheChange-OverBox.Takethe
followingactiontominimizethesound.
(A) InstalltheChange-OverBoxinsidethe
ceiling.Asfortheceilingmaterial,selecta
materiallikeaplasterboardatleast1inch
(9mm),whichminimizesoperationsound.
(B) DonotinstalltheChange-OverBoxina
placenearbedroomsorhospitalrooms.
● Whentheoperationischangedtocooling/
heatingmode,achangeinthetypicalrefrigerant
owsoundsmaybeheardorperceivedfromthe
Change-OverBox.
Therefore,installtheChange-OverBoxinthe
ceilingofthecorridorsothattherefrigerant
owingsoundmaynotbeheardintheroom.
● DonotinstalltheChange-OverBoxinahot
orhumidplace,suchasakitchen,toprevent
condensationontheoutersurfaceofthe
Change-OverBox.
WheninstallingtheChange-OverBoxinsuch
places,applyadditionalinsulation.
● Payattentiontothefollowingpointswhenthe
Change-OverBoxisinstalledinahospitalor
otherfacilitywherethereareelectronicwaves
frommedicalequipment.
(A) DonotinstalltheChange-OverBoxwhere
theelectromagneticwaveisdirectlyradiated
totheelectricalboxorcommunicationcable.
(B) InstalltheChange-OverBoxand
componentsasfaraspracticableoratleast
10ft(3m)fromtheelectromagneticwave
radiator.
(C) Installanoiselterwhenthepowersupply
emitsharmfulnoises.
● Formoredetailsoftherefrigerantpipingand
heightlimitations,refertotheInstallationand
MaintenanceManualfortheOutdoorUnit.
● Ensuretheinstallationplaceisconvenient
fortherefrigerantpipingorelectricalwiring
connection.
● Donotdrill,ordrivescrewsintothecabinet.
Useonlymountingpointsprovided.
● IncasetheChange-OverBoxhastobereplaced
afterinstallation,providealargeenoughservice
doortoaccommodatetheunit.