Bryant 558F.36.1 User manual

  • Hello! I am an AI chatbot trained to assist you with the Bryant 558F.36.1 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Cancels: New WD 558F.36.1
11/15/00
DIAGRAM INDEX
LEGEND
UNIT LABEL DIAGRAM
Unit 558F Voltage-Phase-Hertz Type Label Diagram Figure No.
036,048
208/230-1-60 Schematic/Component Arrangement 50DK508524 1
208/230-3-60 Schematic/Component Arrangement 50DK508526 2
460-3-60 Schematic/Component Arrangement 50DK508529 3
575-3-60 Schematic/Component Arrangement 50DK508531 4
060
208/230-1-60 Schematic/Component Arrangement 50DK508525 5
208/230-3-60 Schematic/Component Arrangement 50DK508527 6
460-3-60 Schematic/Component Arrangement 50DK508530 7
575-3-60 Schematic/Component Arrangement 50DK508532 8
072
208/230-3-60, 460-3-60 Schematic/Component Arrangement 50DK508528 9
575-3-60 Schematic/Component Arrangement 50DK508533 10
090-150
208/230-3-60, 460-3-60 Schematic/Component Arrangement 50DK508793 11
575-3-60 Schematic/Component Arrangement 50DK508794 12
ACCESSORY WIRING
Description Unit Size Fig. No.
Motormaster® I Control 036-150 13
Motormaster II Control
036-072 14
090-150 15
Time Guard® II Device 036-150 16
Solid-State Enthalpy Control 036-150 17
Differential Enthalpy Control 036-150 18
EconoMi$er 036-072 19
EconoMi$er Sensor Wiring 036-150 20
Power Exhaust 036-072 21
wiring diagrams
SINGLE PACKAGE ROOFTOP
ELECTRIC COOLING
UNITS
558F
036-150
3 to 12
1
/
2
Tons
A
HA Adjustable Heat Anticipator
A
WG American Wire Gage
C
Contactor, Compressor
C
AP. Capacitor
C
B—Circuit Breaker
C
C—Cooling Compensator
C
OMP Compressor Motor
D—Diode
EC Enthalpy Control
ECON Economizer
EPS Emergency Power Supply
(Nine-Volt Battery)
EQUIP Equipment
ER Economizer Relay
FPT Freeze-Up Protection Thermostat
FU Fuse
G
ND Ground
HC Heater Contactor (Strip Heat)
HPS High-Pressure Switch
IFC Indoor-Fan Contactor
IFM Indoor-Fan Motor
IFMOVL— Indoor-Fan Motor Overload
TDR Time-Delay Relay
TH Thermostat, Heating
TRAN Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
IFR Indoor-Fan Relay
LPS Low-Pressure Switch
LSM Limit Switch (Manual Reset)
MTR Motor
OAT Outdoor-Air Thermostat
OFC Outdoor-Fan Contactor
OFM Outdoor-Fan Motor
OLR Overload Relay
P—Plug
PL Plug Assembly
QT Quadruple Terminal
R—Relay
SAT Supply-Air Thermostat
SEN Sensor
ST Start Thermistor
SW1 Switch Fully Open
SW2 Switch Fully Closed
SW3 Switch Minimum Vent Position
SW4 Switch Maximum Vent Position
TB Terminal Block
TC Thermostat, Cooling
2
NOTES FOR FIG. 1, 2, 5, 6, 9
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7. For 208/230-3-60 v units: TRAN is wired for 230-v unit. If unit is to be
run with 208-v power supply, disconnect BLK wire from 230-v tap
(RED) and connect to 208-v tap (BLU). Insulate end of 230-v tap.
NOTES FOR FIG. 3, 4, 7, 8, 10
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
NOTES FOR FIG. 11
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7. For 208/230-3-60 v units: TRAN is wired for 230-v unit. If unit is to be
run with 208-v power supply, disconnect BLK wire from 230-v tap
(RED) and connect to 208-v tap (BLU). Insulate end of 230-v tap.
8.
NOTES FOR FIG. 12
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7.
CIRCUIT
BREAKER
VOLTS MFG. PT. NO.
MUST
TRIP
AMPS
CB 24 V
Potter & Brumfield
3.2W2BX-1024-3.2
CB1 150 460-3-60
Heinemann Airpax
8.5CF3-Z228-4 219-3-2600-486
CIRCUIT
BREAKER
VOLTS MFG. PT. NO.
MUST
TRIP
AMPS
CB 24 V
Potter & Brumfield
3.2W2BX-1024-3.2
CB1 150 460-3-60
Heinemann Airpax
8.5CF3-Z228-4 219-3-2600-486
—3—
Fig. 1 — Schematic/Component Arrangement; 558F036,048; 208/230-1-60
—4—
Fig. 2 — Schematic/Component Arrangement; 558F036,048; 208/230-3-60
—5—
Fig. 3 — Schematic/Component Arrangement; 558F036,048; 460-3-60
—6—
Fig. 4 — Schematic/Component Arrangement; 558F036,048; 575-3-60
—7—
Fig. 5 — Schematic/Component Arrangement; 558F060; 208/230-1-60
—8—
Fig. 6 — Schematic/Component Arrangement; 558F060; 208/230-3-60
Fig. 7 — Schematic/Component Arrangement; 558F060; 460-3-60
—9—
Fig. 8 — Schematic/Component Arrangement; 558F060; 575-3-60
—10—
Fig. 9 — Schematic/Component Arrangement; 558F072; 208/230-3-60 and 460-3-60
—11—
—12—
Fig. 10 — Schematic/Component Arrangement; 558F072; 575-3-60
—13—
Fig. 11 — Schematic/Component Arrangement; 558F090-150; 208/230-3-60 and 460-3-60
—14—
Fig. 12 — Schematic/Component Arrangement; 558F090-150; 575-3-60
—15—
Fig. 13 — Motormaster® I Wiring Details
Fig. 14 — Motormaster II Wiring Schematic; 558F036-072
558F090-150
558F036-072
LEGEND
C — Contactor
LEGEND
NOTE: Motormaster II transformer is wired for 460-v supply; it must be rewired for 208/230-v application.
Be sure to insulate unused tap. Refer to color code.
C—Contactor
OFC Outdoor-Fan Contactor
TRAN Transformer
—16—
LEGEND
*The Motormaster II head pressure controller is equipped with an alternate operating mode. When
this mode is selected, the controller shifts the fan cycle sequence to effectively raise the average
condensing temperature approximately 20 F higher than the standard operating mode. In this
alternate mode, the outdoor fan begins cycling at higher outdoor ambient temperatures. This
mode should only be used if the evaporator coil shows signs of frosting at low outdoor ambient
temperatures.
To select the alternate operating mode, move the jumper wire on the Motormaster II control board
from reset T1 to reset T2.
NOTE: Motormaster® II transformer is wired for 460-v supply; it must be rewired for 208/230-v
application. Be sure to insulate unused tap. Refer to color code.
Fig. 15 — Motormaster II Wiring Schematic; 558F090-150
C—Contactor
OFC Outdoor-Fan Contactor
TRAN Transformer
—17—
620 ohm
JUMPER
}
24 VAC SUPPLY FROM
ECONOMIZER CONTROL
SECTION (RED TO TR,
BRN TO TR1)
TO SENSOR MOUNTED
ON BACK OF CONTROL
}
GRAY WIRE FROM
ECONOMIZER HARNESS
RED WIRE FROM
ECONOMIZER SWITCH 3
(NORMALLY CLOSED)
TR
TR1
SO +
+
SR
2
3
1
LED
A
B
C
D
LED
A
B
C
D
TR TR1
SO
SR
2
3
1
+
+
S
+
(HH57AC078
SENSOR)
24 VAC SUPPLY FROM
ECONOMIZER CONTROL
SECTION (RED TO TR,
BRN TO TR1)
TO SENSOR MOUNTED
ON BACK OF CONTROL
GRAY WIRE FROM
ECONOMIZER HARNESS
RED WIRE FROM
ECONOMIZER SWITCH 3
(NORMALLY CLOSED)
1
2
3
BRN
COMPRESSOR
SAFETIES
BRN
CLO
TIME GUARD I I DEVICE
C
OR
CR
T1
T3
T2
TIME GUARD I I DEVICE
C
OR
CR
BRN
T1
T3
T2
HIGH EFFICIENCY 3 TO 12
1
/
2
TON ROOFTOP UNITS
STANDARD EFFICIENCY 3 TO 12
1
/
2
TON ROOFTOP UNITS
LEGEND
Fig. 16 Time Guard® II Device; 558F036-150
C Contactor
CLO Compressor Lockout
CR Control Relay
NOTE: Switches shown in high enthalpy state. Terminals 2 and 3
close on enthalpy decrease.
Fig. 17 Wiring Connections for Solid-State
Enthalpy Control (HH57AC077)
NOTES:
1. Remove factory-installed jumper across SR and + before con-
necting wires from HH57AC078 sensor.
2. Switches shown in high outdoor-air enthalpy state. Terminals 2
and 3 close on low outdoor air enthalpy relative to indoor air
enthalpy.
Fig. 18 Wiring Connections for Differential
Enthalpy Control (HH57AC077 and HH57AC078)
—18—
OUTDOOR
AIR
SENSOR
TEMP
TEMP
COM
OUT
PWR
BROWN
VIOLET
WHITE
RED
BROWN
TEMP
TEMP
COM
OUT
PWR
RETURN
AIR
SENSOR
VIOLET
WHITE
RED
OAT
COM
OAH
-15 V
RAT
COM
RAH
+15 V
ECONOMI$ER
CONTROLLER
PINK
TEMP
TEMP
VIOLET
SUPPLY AIR
TEMPERATURE SENSOR
V+
24
COM VAC
SENSOR
CO
2
(+)
COM
DAT
COM
REM POT
COM
LED
COM
CO
2
CO
2
Fig. 20 EconoMi$er Sensor Wiring; 558F036-150
LEGEND
OAT Outdoor-Air Thermostat
Fig. 19 EconoMi$er Wiring
4-PIN
CONNECTOR
PLUG
L1
L2
GREEN
1
1
22
33
44
GND
230 VAC
1 PHASE
GREEN/
YELLOW
3
2
1
5
8
6
9
B
A
7
4
LT. BLUE
BLACK
BROWN
C1
BLUE
GREEN/
YELLOW
3
2
1
5
8
6
9
B
A
7
4
LT. BLUE
BLACK
BROWN
C1
BLUE
FAN 2
FAN 1
BLACK
BLACK
BLACK
R1
24 VAC
R2
24 VAC
BLACK
BLUE
1
2
3
BROWN
ORANGE
3-PIN
CONNECTOR
PLUG
YELLOW
RED YEL
H1
BLU
GRAY
H4
SECONDARY
230VAC
X4
X1
HT01AH850
(460 VAC)
RED
H1
GRAY
H2
SECONDARY
230VAC
X4
X1
HT01AH859
(575 VAC)
23
13
11 21
230VAC
OR
BLACK L1
BLUE L2
COMPRESSOR 1
CONTACTOR
FIELD SUPPLIED
WIRING
GREEN GND
2 x 4 IN.
HANDY BOX
X3
X2
H2
H3
X2
X3
TO FUSED
DISCONNECT
Fig. 21 — Wiring Diagram for Power Exhaust System
—19—
Copyright 2000 Bryant Heating & Cooling Systems CATALOG NO. 5355-810
/