KegLand KL01946 Operating instructions

Type
Operating instructions
NEMAProtectionRating
Housing IP20
NEMAProtectionRating
Display IP65
PowerSupply 250VAC50/60Hz(10amp)
FireProtectionRating V‐0
PowerConsumption <3W
DisplayRange ‐45to120C
Accuracy +/‐0.5C
Resolution 0.1C
WIRINGDIAGRAM
ICONLEGEND
ICON MODEFUNCTION
On CoolingRelayOn
Flashing CoolingRelayDelayedStart
On HeatingRelayOn
On Alarm
oCoF On TemperatureUnit
SETTINGTHESETPOINT
1. PushandimmediatelyreleasetheSETkey.Thedisplaywill
showthesetpointvalue.
2. Usetheupanddownarrowkeystochangethesetpoint.
3. Wait6secondstoreturntothehomescreen.
RESUMEFACTORYDEFAULTSETTING
Pushthedownkeyfor1second.Whileholdingdownthedown
keyalsopushtheupkeyatthesametime.Oncetheupand
downkeyarebothdepressedthenreleasethedownkeyand
keepholdingtheupkeyforafurther6seconds.
CHANGINGTHEADVANCEDSETTINGS
FormoreadvanceduserstheMKIItemperaturecontrollerhas
asignificantlyadvancedsettingsmenuthatcanbeaccessed.
Theadvancedsettingsallowfurtherinstructionstobegivento
thecontrollersuchasdifferentcoolingstartdelaytimes,
tightertemperaturehysteresissettings,distillationcontrolor
evensequentialtemperaturesettings.Someoftheadvanced
settingsareshowinthetablebelow:
FunctionSetting Range Default
E3 Temphysteresis 0.1 ~10C 1C
E4 CoolingStartdelayatpoweron 0~10min 00
E5 CoolingStartdelay 0~10min 02
E6 Calibrationoffsetsetting ‐20C~+20C 00
t1 Delaytimebetweenheatingand
coolingturningon
0~30min 05
H1 Hightempalarm H2~120C 120
H2 Lowtempalarm ‐45C~H1 ‐45
H5 Alarmstartdelayatpoweron 00~180min 00
H6 Alarmdelaytime 00~180min 00
C1 Temperatureunit 00=oC
01=oF
00
d1 Advancedfunctionmode
(EXPLAINEDINDETAILBELOW)
00=Normal
01=Sequential
02=Distillation
00
d2 TimeUnit 00=Second
01=Minute
02=Hour
03=Day
01
d3 Timeallocatedtoeachsequential
step
00~200 01
SEQUENCIALTEMPSETTINGSBELOWBECOMEVISABLEWHENYOUSET
“d1”to“01”
F1 Sequential Temp1 ‐40~+120oC20C
F2 SequentialTemp2 ‐40~+120oC 20C
F3 SequentialTemp3 ‐40~+120oC 20C
F4 SequentialTemp4 ‐40~+120oC 20C
F5 SequentialTemp5 ‐40~+120oC 20C
F6 SequentialTemp6 ‐40~+120oC 20C
F7 SequentialTemp7 ‐40~+120oC 20C
F8 SequentialTemp8 ‐40~+120oC 20C
F9 SequentialTemp9 ‐40~+120oC 20C
F10 SequentialTemp10 ‐40~+120oC 20C
F11 SequentialTemp11 ‐40~+120oC 20C
F12 Sequential Temp12 ‐40~+120oC20C
1. Toaccesstheadvancedsettings(above)pushtheSETkey
for6secondsuntilE3flashes.
2. Usethearrowkeystonavigatetotheadvancedsettingand
thenusesetkeytoselecttheadvancedsettingthenuse
thearrowkeytochangetheadvancedsetting.
3. Aftertheadvancedsettingshavebeensetusethesetkey
toreturntotheadvancedsettingdisplayorjustwait6
secondstoreturntothehomescreen.Alternativelyifyou
wouldliketoreturntothehomescreenquicklysimply
pressthe“X”buttontoinstantlyreturntothehome
screen.
d1ADVANCEDFUNCTIONMODE
Theadvancedfunctionmodehasthreedifferentsettings:
d1=00–Thisisjustnormaloperation
d1=01–SequentialMode
 Insequentialmodeaseriesofsettemperaturescanbe
setupsothetemperaturecontrolwillcyclethroughanumber
ofdifferentsettemperaturesbeforereturningtotheoriginal
settemp.Thiscanbeparticularlyusefulifyouwantedtoseta
fermentationtemperatureprofilesothatthetemperature
MKII Temp Controller
KL01946(7919)
wouldincreaseby2Cevery2daysthencrashchillanddropped
thetemperaturedownto0Cattheend.Tosetupsequential
mode:
1. Setd1to01
2. Navigatetod2andsetthetimeunittoeitherminutes,
seconds,hoursordays.
3. Navigatetod3andsetthetimeforeachsequential
step.Forexampleifd2hasbeensetto01(for
minutes)andyousetd3to15.Theneachsequential
settemperaturewilllastfor15minutesbeforemoving
tothenextsequentialsettemperature.
4. NavigatefromF1toF12andsetthetemperaturefor
eachsequentialstage.
5. Ifyoudonotwanttouseanyofthesequentialstages
simplysettheF1~F12settingto“no”.Thiscanbe
donebypressingthedownarrowuntilyougetto‐40C
thenpressthedownarrowagainanditwilldisplay
“no”.Inthe“no”settingthesequentialstepwillbe
skipped.IftheF1~F12settingissetto“no”the
controllerwilljumptothenextprogrammed
sequence.
6. Ifatanypointyouneedtore‐startthesequential
modefromF1simplypressthedownarrowandset
keyatthesametimefor6secondsandthesequential
modewillstartfromthebeginning.
7. OncethefinalF12settemperaturehasfinishedthe
controllerwill:
A)Soundanalarm
B)Turnoffsequentialmode
C)Returntotheoriginalsettemperaturebefore
sequentialmodewasselected
Ifyousimplypressanykeyonthedisplaythealarm
willturnoffandthecontrollerwillreturnbackto
normaloperation.
NOTE:Wileinsequentialmodethedisplaywillcyclebetween
theprobetemperatureandthe“F1~F12”sequentialstage.If
atanytimeyouwouldliketoseethesettemperatureforthat
sequentialstagesimplypressthe“X”keyandthesequential
settemperaturewillbedisplayed.
d1=02–DistillationMode
Whendistillingalcoholorotherliquidsitcantakeseveral
hours.Digitaltemperaturecontrollerssuchasthisonecan
helpautomatetheprocesssoyoudon’tneedtomonitorthe
stillsocloselyandthecontrollercanturnoffthestillandpump
whenthedistillationprocessisfinished.Whenindistillation
modetheMKIIcontrollerwillonlycycletheheatingrelayonce.
Soforinstanceifyousetthetemperatureto80Cthecontroller
willturnontheheatingrelayuntilthetemperaturegetsupto
80C.Onceitreaches80Citwillsoundthealarmandturnoff
theheatingrelayuntilitismanuallyreset.
Ifyoudidnotusedistillationmodethetemperaturecontroller
wouldturnontheboilerandthetemperaturewouldonlygo
upto80C.Howeveroncetheboilercoolsdownthecontroller
wouldturntheboilerbackonandthetemperaturewouldkeep
gettingpushedupto80Csotheboilerwouldkeepgetting
cycledonandoffrepeatedlythisissuehighlightstheneedfor
thedistillationmode.
INSTALLATIONANDMOUNTING
Thecontrollermountsintoaholethatis71mmwidex29mm
high.
Ensurethecontrollerismountedinaplacethatisfreeof
vibration,corrosivegassesandexcessivedirt.
PROBEFAULTCODE
Thecontrollercandisplayfaultcodesiftheproberesistanceis
outsideofnormaloperatingparameters.Ifthishappensthe
faultcodesbelowwillreadonthedisplay.
CODE REASON OPERATION
Er1 Probedisconnected/short‐circuit MaintainNormalOperation
Er2 ProbeTemperatureTooLow MaintainNormalOperation
Er3 ProbeTemperatureTooHigh OutputRelaysBotTurnOff