Sentera Controls SDP-E0US-DC Mounting Instruction

Type
Mounting Instruction
SDP-E0US-DC POTENTIOMETER WITH MIN
& MAX SETTINGS AND DRY
CONTACT
Mounting and operating instructions
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 2 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
Table of contents
SAFETY AND PRECAUTIONS 3
PRODUCT DESCRIPTION 4
ARTICLE CODES 4
INTENDED AREA OF USE 4
TECHNICAL DATA 4
STANDARDS 4
OPERATIONAL DIAGRAMS 5
WIRING AND CONNECTIONS 5
MOUNTING INSTRUCTIONS IN STEPS 5
SETTINGS 7
OPERATING INSTRUCTIONS 7
VERIFICATION OF INSTALLATION INSTRUCTIONS 7
TRANSPORT AND STORAGE 8
WARRANTY AND RESTRICTIONS 8
MAINTENANCE 8
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 3 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, Modbus map, mounting and operating
instructions and study the wiring and connection diagram before working with the
product. For personal and equipment safety, and for optimum product performance,
make sure you entirely understand the contents before installing, using, or maintaining
this product.
For safety and licensing (CE) reasons, unauthorised conversion and/ or modifications
of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. is product can only be installed by
an engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts. Always disconnect the power
supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 4 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
PRODUCT DESCRIPTION
ese potentiometers can control equipment that need a variable control signal. e
supply voltage is between 5 VDC and 24 VDC. e output is adjusted continuously
variable from minimum to maximum or from maximum to minimum via a rotary knob.
is version has a dry contact at the leftmost position to remotely switch ON/OFF
external equipment. e potentiometer is suitable for both inset (IP44) and surface
mounting (IP54).
ARTICLE CODES
Code Supply Output Remote ON/OFF
SDP-E0US-DC 5-24 VDC min - max/
max - min yes
INTENDED AREA OF USE
A variety of applications where a variable control signal is required
TECHNICAL DATA
Supply voltage: 5-24 VDC
Selectable analogue / modulating output:
0100% Us mode: min. load 50 kΩ (Rl ≥ 50 kΩ)
020 mA mode: max. load 500 Ω (RL ≤ 500 Ω)
PWM mode PWM frequency: 1 kHz, min. load 50 kΩ (RL ≥ 50 kΩ)
Enclosure:
ASA, white-ivory (RAL9010), IP54 (according to EN 60529)
Dry contact for remote ON / OFF switching of external equipment with 1 A max
switching current
Operating ambient conditions:
temperature: 0—50 °C
rel. humidity: < 95 % rH (non-condensing)
Storage temperature: -10—55 °C
STANDARDS
Low Voltage Directive 2014/35/EU
EN 60529:1991 Degrees of protection provided by enclosures (IP Code)
Amendment AC:1993 to EN 60529
EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements.
EMC directive 2014/30/EU
EN 60730-1:2011 Automatic electrical controls for household andsimilar use -
Part 1: General requirements
EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residential, commercial and light industrial environments
EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments. Amendments A1:2011 and AC:2012 to EN 61000-6-3
RoHs Directive 2011/65/EU
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 5 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
OPERATIONAL DIAGRAMS
Trimmers: Min < Max Trimmers: Min > Max
Off
Switch
Outputmax
Outputmin
0 %
On
Ao, [%]
100 % Us
DRY contact OFF
DRY contact ON
Potentiometer position Max
Min Off
Switch
Outputmax
Outputmin
0 %
On
Ao, [%]
100 % Us
DRY contact OFF
DRY contact ON
Potentiometer position Max
Min
Appropriate load should be connected to the analogue / modulating output. If the
load should be changed, configure the output type first.
NOTE
WIRING AND CONNECTIONS
Us Supply voltage 5-24 VDC
GND Supply voltage, ground
DC Dry contact for remote ON/OFF
Ao Output signal (min - max)
GND Output, ground
Connections Spring contact terminal block, stranded wires 1,0—1,5 mm² or wires
with cable shoe 0,75—1,0 mm², length 7 mm
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting your potentiometer read carefully “Safety and
Precautions. Then proceed with the following mounting steps:
Flush mounting
1. Remove the knob by pulling it out.
2. Unscrew the washer to remove the cover of the external enclosure.
3. Do the wiring according to the wiring diagram (see Fig. 1 Wiring and connections).
Fig. 1 Wiring and connections
Supply voltage Analogue output
Dry contact
remote ON/OFF
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 6 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
4. Mount the internal enclosure into the wall according to the mounting dimensions
shown in Fig. 2 Mounting dimensions - flush mounting
Fig. 2 Mounting dimensions - flush mounting
82
89
63,5
82
76
58
58
4x ø 3,5mm
4x ø 3,5mm
60
76
Mount the unit so that the terminal block and connections are at the lower side.
NOTE
5. Mount back the cover and secure it with the washer.
6. Put back the knob and turn it to off position
7. Turn on the power supply.
For surface mounting
1. Remove the knob by pulling it out.
2. Unscrew the washer to remove the cover of the external enclosure.
3. Mount the external enclosure onto the surface by means of screws and dowels
adhering to the mounting dimensions shown in Fig. 3 Mounting dimensions -
surface mounting.
Fig. 3 Mounting dimensions - surface mounting
82
89
63,5
82
20 38
49
64
64
4. Insert the cables trough the grommets.
5. Do the wiring according to the wiring diagram (see Fig. 1 Wiring and connections)
6. Insert the internal enclosure into the external one and fix it using the screws.
Mount back the cover and secure it with the nut.
7. Put back the knob and turn it to off position
8. Turn on the power supply.
Mount the unit so that the terminal block and connections are at the lower side.
NOTE
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 7 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
A 5 mm hole can be drilled at the bottom of the external enclosure to drain the
condensed water.
NOTE
SETTINGS
Settings
1
3
2
1 – Min adjustment trimmer ere is always 20%
minimum control range
between the values
determined by the
trimmers.
0 - 80% Us
2 – Max adjustment trimmer 20 - 100%
Us
3 – Header for analogue/ modulating
output type selection
voltage current PWM
1 2 3 4 1 2 3 4 1 2 3 4
OPERATING INSTRUCTIONS
e potentiometer is intended to manually control EC fan speed, AC fan speed
controllers, damper actuators or other devices that require an analogue input signal.
Turn the knob to adjust the output signal.
By default, the output signal goes from minimum to maximum by turning the rotary
knob clockwise. When minimum value is set higher then maximum value, the output
signal goes from maximum to minimum by turning the rotary knob. ere is always
20% minimum control range between the values determined by the trimmers. e
Min trimmer value is taken as a basis. If both trimmers are set to their minimum the
actual control of the output will be between 0% and 20%. If both trimmers are set
to their maximum the actual control of the output will be between 80% and 100%.
VERIFICATION OF INSTALLATION INSTRUCTIONS
Use only tools and equipment with non-conducting handles when working on
electrical devices.
ATTENTION
In case of faulty operation, please check if:
the right voltage is applied;
www.sentera.eu
MIW-SDP-E0US-DC-EN-000 - 21 / 06 / 2022 8 - 8
back to the table of contents
SDP-E0US-DC POTENTIOMETER WITH, MIN & MAX
SETTINGS AND DRY CONTACT
all connections are correct;
the regulated device is functioning.
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completely dry.