Battery Maintenance Guidelines
The battery maintenance instructions listed below are for reference only. Battery manufacturer’s instructions
for transportation, installation, storage or maintenance take precedence over these instructions.
• To prevent damage, inspect batteries every 3 months for:
Signs of battery cracking, leaking or swelling. The battery should be replaced immediately by
authorized personnel using a battery of the identical type and rating.
Signs of battery cable damage. Battery cable should be replaced immediately by Authorized Personnel
using replacement parts specifi ed by vendor.
Loose battery connection hardware. Refer to battery manufacturer’s documentation for the correct
torque and connection hardware for the application.
• Apply battery manufacturer’s specifi ed antioxidant compound on all exposed connections.
• Verify battery terminals and/or exposed connection hardware is not within 2 inches of a conductive
surface. Reposition batteries as necessary to maintain adequate clearance.
• Clean up any electrolyte (battery emission) in accordance with all federal, state, and local regulations or
codes.
• Proper venting of the enclosure is recommended. Follow the Battery Manufacturer’s approved
transportation and storage instructions.
• Always replace batteries with those of an identical type and rating. Never install old or untested batteries.
• Do not charge batteries in a sealed container. Each individual battery should have at least 0.5
inches of space between it and all surrounding surfaces to allow for convection cooling.
• All battery compartments must have adequate ventilation to prevent an accumulation of potentially
dangerous gas.
Recycling and Disposal
Spent or damaged batteries are considered environmentally unsafe. Always recycle used batteries or dispose
of the batteries in accordance with all federal, state and local regulations.
Auxiliary Power Unit (APU) Notes
When the engine is stopping, a small amount of unburned fuel may be detected by the odor of gas fumes.
Fans are used to expel these fumes from the enclosure and may be detected outside the enclosure for a
short period of time after engine shutdown. This is a normal condition and does not present a hazard.
Most utilities add a chemical agent to the gas which produces a strong odor so leaks can be detected before
they reach a dangerous or explosive level. It may be possible to detect this gas additive odor even though the
gas hazard sensor does not issue an alarm. The gas sensor will issue an alarm when the detected levels of
gas reaches 10% - 20% of the Lower Explosive Limit (LEL). The alarm must remain active for at least three
seconds before it will be recognized by the Engine Control Module (ECM).
The gas hazard sensor has a 10 minute delay for periods of purging and power-up. During the purge phase,
the Green alarm light will fl ash. When the purge phase is completed, the light will glow steadily. In the event
the detector has been disconnected from power for more than 24 hours, it may require a period of more than
10 minutes to complete its purge phase. In that event, push the reset button to disable the alarm for repeated
purge cycles. Also, the reset button may be used to disable the alarm for 10 minutes at any time.
If gas fumes are detected before the engine is run, or in excess of approximately 10 minutes after running
the engine, you must check the system for leaks as described in the INSTALLATION manual and correct as
necessary.