Mircom SGM-1004A Four Indicating Circuit Module Owner's manual

Category
Fire protection
Type
Owner's manual
FOUR INDICATING CIRCUIT MODULE SGM-1004A
General
The SGM-1004A Module provides the FA-1000 or
FX-2000 Series Fire Alarm Control panels with up to
4 Class A or B (Style Z or Y) Indicating Circuits.
Applications
The SGM-1004A provides up to four indicating
circuits each rated at 1.7 Amps to signal devices
such as strobes, bells, horns, etc. Each of the
indicating circuits can be configured as non-
silenceable (steady) or silenceable. In addition each
circuit comes with an individual trouble indicator. All
circuits are power limited for use with limited energy
cable. The SGM-1004A is jumper selectable for
individual circuit signal silence. In addition it has
terminals for a bell cut relay.
Features
Four Class A/B (Style Z/Y) Indicating Circuits
Each Indicating Circuit is rated at 1.7 Amps
Each Indicating Circuit can be con gured as Non-Silenceable (Steady) or Silenceable
Outputs resound on subsequent alarm
LEDs (Amber) provided for indication of Indicating Circuit trouble
Programable to any input circuit
All circuits are power limited for use with limited energy cable
Removable terminal blocks for ease of wiring and servicing
Extensive transient protection on all circuits
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, speci cations and models and also to discontinue models.
Installation
The SGM-1004A consists of a PC board which
mounts at the bottom of the chassis. The PC
board is connected via cables to the board on the
main chassis. Space is provided on the dress
panel allowing the application of slide-in labels for
indicating zone description. Labels are provided
with each chassis Removable terminal blocks are
provided for easy connection of eld wiring and
servicing.
5623
NOT TO BE USED FOR INSTALLATION PURPOSES.
S7010 S7010
MEA
approved
7135-1477:106 313-97-E
CATALOG NUMBER
firealarmresources.com
Technical Speci cations
Output Voltage ...................................................................................................................................... 24 VDC Un ltered
Standby Current....................................................................................................................................................... 35 mA
Alarm Current (unloaded) ...................................................................................................................................... 150 mA
Output Current per Zone - Power Limited ............................................................................................................ 1.7 Amp
End of Line Resistor ......................................................................................................................... 3.9K ohm ±5%, ½ W
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com Email: [email protected]
Distributed by:
CAT. 5623
Rev. 5
Typical Wiring Diagram
NOT TO BE USED FOR INSTALLATION PURPOSES.
NOTES:ALL POWER LIMITED CIRCUITS MUST USE TYPE FPL, FPLR,
OR FPLP POWER LIMITED CABLE.
SGM-1004(A) INDICATING CIRCUITS ARE FULLY
SUPERVISED AND RATED FOR 24 VDC UNFILTERED 1.70AMP
MAX. THEY MUST BE WIRED AS SHOWN IN THE WIRING
TABLES.
BELL, HORN, OR STROBE
LEGEND: SEE APPENDIX FOR COMPATIBLE DEVICES.
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
INDICATION
CIRCUIT 1
(POWER
LIMITED)
IND1+ (Z)
STYLE Z
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
INDICATION
CIRCUIT 2
(POWER
LIMITED)
STYLE Y
WIRING
SUPERVISED INDICATING CIRCUIT #1
IND4+ (Z)
IND4- (Z)
IND4- (Y/Z)
SUPERVISED INDICATING CIRCUIT #4
INDICATION
CIRCUIT 3
(POWER
LIMITED)
IND3+ (Z)
STYLE Z
WIRING
IND3- (Y/Z)
IND3+ (Y/Z)
IND4+ (Y/Z)
IND3- (Z)
INDICATION
CIRCUIT 4
(POWER
LIMITED)
STYLE Y
WIRING
SUPERVISED INDICATING CIRCUIT #3
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
firealarmresources.com
  • Page 1 1
  • Page 2 2

Mircom SGM-1004A Four Indicating Circuit Module Owner's manual

Category
Fire protection
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI