Magnetrol Eclipse Enhanced 705 Foundation Fieldbus User manual

Category
Measuring, testing & control
Type
User manual
Guided Wave Radar
Level Transmitter

 

705 software v3.x
 


Table of Contents
1.0 FOUNDATION fieldbus
Overview........................................................................................................................................3
1.1 Description .......................................................................................................................................................................3
1.2 Benefits.............................................................................................................................................................................4
1.3 Device Configuration........................................................................................................................................................4
1.4 Intrinsic Safety..................................................................................................................................................................5
1.5 Link Active Scheduler (LAS).............................................................................................................................................6
2.0 QuickStart Configuration ...................................................................................................................................................7
3.0 Function Blocks ..................................................................................................................................................................8
3.1 Overview ..........................................................................................................................................................................8
3.1.1 Universal Fieldbus Block Parameters.......................................................................................................................8
3.2 Resource Block..................................................................................................................................................................9
3.3 Transducer Block.............................................................................................................................................................12
3.3.1 Transducer Block Parameters ................................................................................................................................12
3.3.2 Password Parameters .............................................................................................................................................12
3.3.3 Configuration Parameters .....................................................................................................................................13
3.3.4 Offset Description ................................................................................................................................................14
3.4 Calibration Parameters....................................................................................................................................................15
3.4.1 Factory Parameters................................................................................................................................................15
3.4.2 Firmware Version..................................................................................................................................................16
3.5 Analog Input Block.........................................................................................................................................................16
3.5.1 AI Block Parameters..............................................................................................................................................16
3.5.2 Local Display of Analog Input Transducer Block Parameters ................................................................................18
3.5.2.1 AI Out Display Screens..................................................................................................................................19
3.6 PID Block.......................................................................................................................................................................20
3.6.1 PID Block Parameters...........................................................................................................................................20
4.0 Model 705 F
OUNDATION fieldbus
Menu .........................................................................................................................23
4.1 Measurement Type: Level Only.......................................................................................................................................23
5.0 Diagnostic Parameters.......................................................................................................................................................26
5.1 Simulation Feature..........................................................................................................................................................27
6.0 Reference Information ......................................................................................................................................................28
6.1 Troubleshooting ..............................................................................................................................................................28
6.1.1 Troubleshooting System Problems.........................................................................................................................28
6.1.2 Status Messages.....................................................................................................................................................29
6.1.3 FF Segment Checklist...........................................................................................................................................31
6.2 References .......................................................................................................................................................................32
Appendix – Transducer Block Parameters ..................................................................................................................32
Configuration Data Sheet ..........................................................................................................................................33
FOUNDATION Fieldbus
Enhanced Eclipse Model 705
Guided Wave Radar Transmitter
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
3
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
1.0 FOUNDATION Fieldbus
Overview
1.1 Description
F
OUNDATION fieldbus
is a digital communications system
that serially interconnects devices in the field. A Fieldbus
system is similar to a Distributed Control System (DCS)
with two exceptions:
Although a F
OUNDATION fieldbus
system can use the same
physical wiring as an existing 4–20 mA device, Fieldbus
devices are not connected point to point, but rather are
multidropped and wired in parallel on a single pair of wires
(referred to as a segment).
•F
OUNDATION fieldbus
is a system that allows the user to
distribute control across a network. Fieldbus devices are
smart and actually maintain control over the system.
Unlike 4–20 mA analog installations in which the two wires
carry a single variable (the varying 4–20 mA current), a digi-
tal communications scheme such as F
OUNDATION fieldbus
considers the two wires as a network. The network can carry
many process variables as well as other information. The
Enhanced Eclipse Model 705FF transmitter is a
F
OUNDATION fieldbus
registered device that communicates
with the H1 F
OUNDATION fieldbus
protocol operating at
31.25 kbits/sec. The H1 physical layer is an approved
IEC 61158 standard.
An IEC61158 shielded twisted pair wire segment can be as
long as 6234 feet (1900 meters) without a repeater. Up to
4 repeaters per segment can be used to extend the distance.
The maximum number of devices allowed on a Fieldbus
segment is 32 although this depends on the current draw
of the devices on any given segment.
Control Room
Power Supply
Terminator
6234 feet (1900 meters) maximum
PC
Terminator
P
ower
Conditioner

4
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
Details regarding cable specifications, grounding, termination,
and other network information can be found in IEC 61158
or the wiring installation application guide AG-140 at
www.fieldbus.org.
1.2 Benefits
The benefits of F
OUNDATION fieldbus
can be found
throughout all phases of an installation:
1. Design/Installation: Connecting multiple devices to a single
pair of wires means less wire and fewer I/O equipment.
Initial Engineering costs are also reduced because the
Fieldbus Foundation requires interoperability, defined as
the ability to operate multiple devices in the same system,
regardless of manufacturer, without a loss of functionality.”
All F
OUNDATION fieldbus
devices must be tested for
interoperability by the Fieldbus Foundation. Magnetrol
Enhanced Model 705 3X FF device registration information
can be found at www.fieldbus.org.
2. Operation: With control now taking place within the
devices in the field, better loop performance and control are
the result. A F
OUNDATION fieldbus
system allows for mul-
tiple variables to be brought back from each device to the
control room for additional trending and reporting.
3. Maintenance: The self-diagnostics residing in the smart
field devices minimizes the need to send maintenance
personnel to the field.
1.3 Device Configuration
The function of a F
OUNDATION fieldbus
device is deter-
mined by the arrangement of a system of blocks defined by
the Fieldbus Foundation. The types of blocks used in a typi-
cal User Application are described as follows:
Resource Block describes the characteristics of the
F
OUNDATION fieldbus
device such as the device name,
manufacturer, and serial number.
Function Blocks are built into the F
OUNDATION fieldbus
devices as needed to provide the desired control system
behavior. The input and output parameters of function
blocks can be linked over the Fieldbus. There can be
numerous function blocks in a single User Application.
Transducer Blocks contain information such as calibration
parameters and sensor type. They are used to connect the
sensor to the input function blocks.
5
Device Descriptions
An important requirement of Fieldbus devices is the inter-
operability concept mentioned earlier. Device Description
(DD) technology is used to achieve this interoperability.
The DD provides extended descriptions for each object and
provides pertinent information needed by the host system.
DDs are similar to the drivers that your personal computer
(PC) uses to operate peripheral devices connected to it. Any
Fieldbus host system can operate with a device if it has the
proper DD and Common File Format (CFF) for that device.
The most recent DD and CFF files can be found on the
F
OUNDATION fieldbus
web site at www.fieldbus.org.
NOTE: Please consult your host system vendor for any host-specific
files that may be needed.
  

1.4 Intrinsic Safety
The H1 physical layer supports Intrinsic Safety (IS) applica-
tions with bus-powered devices. To accomplish this, an IS
barrier or galvanic isolator is placed between the power
supply in the safe area and the device in the hazardous area.
H1 also supports the Fieldbus Intrinsically Safe Concept
(FISCO) model which allows more field devices in a
network. The FISCO model considers the capacitance and
inductance of the wiring to be distributed along its entire
length. Therefore, the stored energy during a fault will be
less and more devices are permitted on a pair of wires.
Instead of the conservative entity model, which only allows
about 90 mA of current, the FISCO model allows a maxi-
mum of 110 mA for Class II C installations and 240 mA
for Class II B installations.
FISCO certifying agencies have limited the maximum
segment length to 1000 meters because the FISCO model
does not rely on standardized ignition curves.
The Enhanced Eclipse Model 705 is available with entity IS,
FISCO IS, FNICO non-incendive, or explosion proof approvals.
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
Model 705 3.x
 
 

  
Dev V1 DD V1 June 2005 Version 3.0A
through Version 3.0K
Dev V2 DD V1 June 2008 Version 3.1A and later
6
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
1.5 Link Active Scheduler (LAS)
The default operating class of the Enhanced Eclipse Model 705
with F
OUNDATION fieldbus
is a basic device. However, it is
capable of being a Link Active Scheduler (LAS). The LAS
controls all communication on a FOUNDATION fieldbus
segment. It maintains the “Live List” of all devices on a
segment, coordinates both the cyclic and acyclic timing and,
at any given time, controls which device publishes data via
Compel data (CD) and Pass Token (PT).
The primary LAS is usually maintained in the host system,
but in the event of a failure, all associated control can be
transferred to a backup LAS in a field device such as the
Enhanced Eclipse Model 705. The operating class can be
changed from basic to LAS using a FOUNDATION fieldbus
configuration tool.
NOTE: The Enhanced Eclipse Model 705 is shipped from the factory
with Device Class set to Basic.
7
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
2.0 QuickStart Configuration
The Eclipse transmitter comes partially configured from
the factory but can be reconfigured in the shop (disregard
fault message due to unattached probe). The minimum
configuration instructions required in the field follow.
1. Power up the transmitter.
The display changes every 5 seconds alternating between
showing the Status, Level and Analog Input Block values.
2. Remove the cover of the lower electronic compartment.
3. Use the Up or Down Arrow ( ) keys to move from one
step of the configuration program to the next step.
4. Press the Enter Arrow ( ) key. The last
character in the first line of the display
changes to an exclamation point (!).
5. Use the Up or Down Arrow ( ) keys to increase or
decrease the value in the display or to scroll through the
choices.
6. Press the Enter Arrow ( ) key to accept a value and move
to the next step of the configuration program (the default
password is 1).
7. After entering the last value, allow 10 seconds before
removing power from the transmitter.
The following configuration entries are the minimum required for
configuration (the default password is 1 from the LCD/keypad).
PrbModel
xxx
PrbModel
(select)
Probe Ln
xxx.x
LvlOfst
xxx.x
Dielctrc
(select)
Select the  to be used
Model 705: 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-F, 7xF-P,
7xF-4, 7xF-x, 7xJ-x, 7xK-x, 7xP-x, 7xQ-x,
7xR-x, 7xS-x, 7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x
Select the type of  to vessel (NPT, BSP, or
flange).
Select from Level Only, Level and Volume, Interface Level
or Interface Level and Volume.
Enter the exact  as printed on the probe
nameplate.
Enter the value. Refer to Section 3.3.4 for
further information. (The unit is shipped from the factory
with offset = 0; i.e., all measurements are referenced to
the bottom of the probe).
Enter the range for the material to be measured.
Level Offset
Probe Length
Probe Mount
Probe Model
Dielectric
of Medium
2
5
6
4
1
PrbMount
(select)
Enter
Down
Up
MeasType
(select)
8
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
3.0 Function Blocks
3.1 Overview
The Enhanced Eclipse Model 705FF is a Guided Wave Radar
(GWR) level transmitter with seven F
OUNDATION fieldbus
Function Blocks (one Resource Block, one Transducer
Block, four Analog Input Blocks, and one PID Block). The
idea of Function Blocks, which a user can customize for a
particular application, is a key concept of Fieldbus topology.
Function Blocks consist of an algorithm, inputs and out-
puts, and a user-defined name.
The TRANSDUCER block output is available to the net-
work through the ANALOG INPUT blocks.
The ANALOG INPUT blocks (AI) take the TRANSDUCER
block level or volume values and makes them available as an
analog value to other function blocks. The AI blocks have
scaling conversion, filtering, and alarm functions.
 
The following are general descriptions of the parameters
common to all blocks. Additional information for a given
parameter is described later in that specific block section.
ST_REV (static data revision): a read only parameter that
gives the revision level of the static data associated with the
block. This parameter will be incremented each time a static
parameter attribute value is written and is a vehicle for
tracking changes in static parameter attributes.
TAG_DESC (tag descriptor): a user assigned parameter
that describes the intended application of any given block.
STRATEGY: a user assigned parameter that identifies
groupings of blocks associated with a given network connec-
tion or control scheme.
ALERT_KEY: a user assigned parameter which may be used
in sorting alarms or events generated by a block.
MODE_BLK: a structured parameter composed of the
actual mode, the target mode, the permitted mode(s), and
the normal mode of operation of a block.
The actual mode is set by the block during its execution to
reflect the mode used during execution.
The target mode may be set and monitored through the
mode parameter.
9
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
The permitted modes are listed for each block.
The block must be in an automatic mode for normal
operation.
NOTE: The MODE_BLK target parameter must be OOS (out of service)
to change configuration and calibration parameters in that func-
t
ion block (when in OOS, the normal algorithm is no longer exe-
cuted and any outstanding alarms are cleared).
All blocks must be in an operating mode for the device to oper-
ate. This requires the Resource Block to be in “AUTO” and the
Transducer Block to be in “AUTO” before the Function Blocks
can be placed in a mode other than OOS (out of service).
BLOCK_ERR: a parameter that reflects the error status of
hardware or software components associated with, and
directly affecting, the correct operation of a block.
NOTE: A BLOCK_ERR of “Simulation Active” in the Resource Block
does not mean simulation is active—it merely indicates that the
simulation (hardware) enabling jumper is present.
3.2 Resource Block
The RESOURCE block contains data specific to the
Enhanced Model 705 transmitter, along with some
information about the firmware.
NOTE: The Resource Block has no control function.
MODE_BLK: Must be in AUTO in order for the remain-
ing blocks in the transmitter to operate.
NOTE: A Resource Block in “out of service” will stop all function block
execution in the transmitter.
RS_STATE (Resource State): identifies the state of the
RESOURCE block state machine. Under normal operating
conditions, it should be “On-Line.”
DD_RESOURCE: a string identifying the tag of the
resource that contains the Device Description for this device.
MANUFAC_ID: contains Magnetrol International’s
F
OUNDATION fieldbus
manufacturers ID number, which is
0x000156.
DEV_TYPE: the model number of the Enhanced Eclipse
Model 705 transmitter (0x0001). It is used by interface
devices to locate the Device Descriptor (DD) file for this
product.
DEV_REV: contains the firmware revision of the Enhanced
Eclipse Model 705 transmitter. It is used by interface
devices to correctly select the associated DD.
10
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
DD_REV: contains the revision of the DD associated with
the version of firmware in the Enhanced Eclipse Model 705
transmitter. It is used by interface devices to correctly select
the associated DD.
RESTART: Default and Processor selections are available.
Default will reset the Model 705 to the established block
configuration.
NOTE: As RESTART DEFAULT will set  configuration parameters
to their default values. Devices need to be reconfigured
following activation of this function
FEATURES: a list of the features available in the transmit-
ter. The Model 705 features include Reports, and Soft Write
Lock.
FEATURES_SEL: allows the user to turn Features on or off.
CYCLE_TYPE: identifies the block execution methods that
are available.
CYCLE_SEL: allows the user to select the block execution
method.
MIN_CYCLE_T: the time duration of the shortest cycle
interval. It puts a lower limit on the scheduling of the
resource.
NV_CYCLE_T: the minimum time interval between copies
of non-volatile (NV) parameters to NV memory. NV mem-
ory is only updated if there has been a significant change in
the dynamic value and the last value saved will be available
for the restart procedure. A value of “0” means it will never
be automatically copied. Entries made by human interface
devices to NV parameters are copied to non-volatile memory
at the time of entry.
NOTE: After completing a large copy, allow several seconds before
removing power from the Eclipse Model 705 transmitter to
ensure that all data has been saved.
FREE_SPACE: shows the amount of available memory for
further configuration. The value is zero percent in a pre-
configured device.
FREE_TIME: the amount of the block processing time that
is free to process additional blocks.
SHED_RCAS: the time duration at which to give up com-
puter writes to function block RCas locations. Shed from
RCas will never happen when SHED_RCAS = 0.
SHED_ROUT: the time duration at which to give up com-
puter writes to function block ROut locations. Shed from
ROut will never happen when SHED_ROUT = 0.
11
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
FAULT_STATE, SET_FSTATE, CLR_FSTATE: these only
apply to output function blocks. (The Model 705 has no
output function blocks).
MAX_NOTIFY: the maximum number of alert reports that
the transmitter can send without getting a confirmation.
The user can set the number low, to control alert flooding,
by adjusting the LIM_NOTIFY parameter value.
LIM_NOTIFY: the maximum numbers of unconfirmed
alert notify messages allowed. No alerts are reported if set
to zero.
CONFIRM_TIME: the time that the transmitter will wait
for confirmation of receipt of a report before trying again.
Retry will not occur if CONFIRM_TIME = 0.
WRITE_LOCK: When set to LOCKED, will prevent any
external change to the static or non-volatile data base in the
Function Block Application of the transmitter. Block con-
nections and calculation results will proceed normally, but
the configuration will be locked.
UPDATE_EVT (Update Event): is an alert generated by a
write to the static data in the block.
BLOCK_ALM (Block Alarm): is used for configuration,
hardware, connection, or system problems in the block. The
cause of any specific alert is entered in the subcode field.
The first alert to become active will set the Active status in
the Status attribute. As soon as the Unreported status is
cleared by the alert reporting task, another block alert may
be reported without clearing the Active status, if the sub-
code has changed.
ALARM_SUM (Alarm Summary): contains the current
alert status, the unacknowledged states, the unreported
states, and the disabled states of the alarms associated with
the block.
ACK_OPTION (Acknowledge Option): selects whether
alarms associated with the block will be automatically
acknowledged.
WRITE_PRI (Write Priority): the priority of the alarm
generated by clearing the write lock.
WRITE ALM (Write Alarm): the alert generated if the
write lock parameter is cleared.
ITK_VER (ITK Version): contains the version of the
Interoperability Test Kit (ITK) used by the Fieldbus
Foundation during their interoperability testing.
12
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
3.3 Transducer Block
The TRANSDUCER block is a custom block containing
parameters that support the Enhanced Eclipse Model 705
level transmitter. It contains the GWR probe configuration,
diagnostics, and calibration data, and outputs level with
status information.
The TRANSDUCER block parameters are grouped in a
useful configuration. There are both read-only parameters
and read-write parameters within the TRANSDUCER block.
The read-only parameters report the block status and
operation modes.
The read-write parameters affect the function block basic
operation, level transmitter operation, and calibration.




 
The first six parameters in the TRANSDUCER block are
the universal parameters discussed in section 3.1.1. The
universal parameters are followed by these additional
required parameters:
UPDATE_EVT (Update Event): an alert generated by a
write to the static data in the TRANSDUCER block.
Another important parameter found later in the TRANS-
DUCER block list is DEVICE_STATUS, which displays
the status of the device. If more than one message exists,
then the messages are displayed in priority order.
If DEVICE_STATUS indicates a problem, refer to
Section 6.1, Troubleshooting (those parameters which are
shaded are password-protected).


 
To change a parameter at the local user interface, a value
matching the user password must be entered (Default=1). If
the user password is entered, the instrument is in the user
mode. After 5 minutes with no keypad activity, the entered
password expires.
Factory password is for use by trained factory personnel only.
From the Host system network, the instrument always
behaves as if it is in the user mode by default. In other
words, it is not necessary to enter the user password in order
to write parameters from the Host system.
13
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
 
This set of parameters within the Transducer Block is impor-
tant and required to configure every Eclipse Model 705
transmitter.
PROBE_MODEL: Select the choice that corresponds to the
first four digits of the model number of the probe. An x
in the selection means that character is variable (the probe
model number is shown on the nameplates attached to both
the transmitter and probe). For example, 7xA-x should be
chosen for probe models beginning with 7EA or 7MA.
PROBE_MOUNT: Select the type of mounting on the
probe. The choices are NPT, BSP, and Flange.
MEASUREMENT_TYPE: Select from LEVEL ONLY,
LEVEL AND VOLUME, INTERFACE, or INTERFACE
AND VOLUME.
PROBE_LENGTH: Enter the exact length of the probe.
The probe length is shown as the last three digits of the
probe model number printed on the nameplates attached to
the transmitter and probe. PROBE_LENGTH is shown in
SENSOR_UNITs.
LEVEL_OFFSET: Enter the distance from the probe tip to
the desired 0% reference in PROBE_UNITs. The accept-
able range is from -300 inches to 600 inches. Refer to
Section 3.3.4 for additional information.
DIELECTRIC_RANGE: Select from 10–100, 3–10, 1.7–
3.0, or 1.7–1.4
NOTE: All dielectric ranges are not available with all probes.
If an unsupported dielectric range is selected, the transmitter
will give a negative response and the value displayed will
revert to its previous value.
THRESHOLD: The threshold can be set as either FIXED
or CFD. This parameter should be set to FIXED in those
applications measuring total level having a lower dielectric
material over a higher dielectric material. (A typical example
for FIXED Threshold is a hydrocarbon application having
water bottoms.)
Offset
Probe Length
Probe Mount
0% Set Point
Probe Model
Dielectric
of Medium
100% Set Point
14
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
 
The parameter referred to as LEVEL_OFFSET in the
Transducer Block is the desired level reading when liquid
surface is at the end of the probe. The Eclipse transmitter is
shipped from the factory with LEVEL_OFFSET set to 0.
With this configuration, all measurements are referenced
from the bottom of the probe. See Example 1.
Example 1
(LEVEL_OFFSET = 0 as shipped from factory):
Application calls for a 72-inch NPT Coaxial probe in
water with the bottom of the probe 10 inches above the
bottom of the tank. The user wants the 0% point at
24 inches and the 100% point at 60 inches as referenced
from the bottom of the probe.
In those applications in which it is desired to reference all
measurements from the bottom of the vessel, the value of
LEVEL_OFFSET should be changed to the distance
between the bottom of the probe and the bottom of the
vessel as shown in Example 2.
Example 2:
Application calls for a 72-inch NPT coaxial probe in
water with the bottom of the probe 10 inches above the
bottom of the tank. The user wants the 0% point at
24 inches and the 100% point at 60 inches as referenced
from the bottom of the tank.
When the Eclipse transmitter is mounted in a chamber/bridle,
it is usually desirable to configure the unit with the 0%
point at the lower process connection and the 100% point
at the upper process connection. The span is the
center-to-center dimension. In this case, a negative
LEVEL_OFFSET needs to be entered. In doing so, all
measurements are then referenced at a point up on the
probe as shown in Example 3.
Example 3:
Application calls for a 48-inch cage-coaxial flanged probe
measuring water in a chamber with the bottom of the
probe 6 inches below the lower process connection. The
user wants the 0% point to be 0 inches at the bottom
process connection and the 100% point to be 30 inches
at the top process connection.
1
0"
60"
100%
L
CD Menu
0%
2
4"
PrbModel
7
xA-x
P
rbMount
NPT
LvlUnits
i
n
P
robe Ln
7
2 in
Lvl Ofst
0
.0 in
Dielctrc
10-100

10"
60"
100%
0
%
24"
PrbModel
7xA-x
PrbMount
NPT
LvlUnits
in
Probe Ln
72 in
Lvl Ofst
10 in
Dielctrc
10-100
LCD Menu

6"
30"
0%
100%
PrbModel
7xR-x
PrbMount
Flange
LvlUnits
in
Probe Ln
48 in
Lvl Ofst
-6.0 in
Dielctrc
10-100
LCD Menu

15
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
3.4 User-Calibration Parameters
One of the main advantages of the Enhanced Eclipse Model
705 GWR transmitter is that the device does not need to be
calibrated in the field. Every Enhanced Eclipse Model 705
transmitter is shipped precisely calibrated from the factory.
On the other hand, part of the advantage of
F
OUNDATION fieldbus
is to provide the ability to monitor
changes and make adjustments to a transmitter. The
Fieldbus
concept allows a user to make calibration adjust-
ments if deemed necessary.
NOTE: The original factory calibration settings are restored when a new
probe length value is assigned.
        

Contact the factory for information on how to perform a
User Calibration.
 
The factory-adjustable calibrated parameters are WINDOW,
CONVERSION_FACTOR, and SCALE_OFFSET.
WINDOW is used to adjust for the variations in the analog
section of the Eclipse TDR measurement engine. CON-
VERSION_FACTOR and SCALE_OFFSET are the main
factory calibration settings.
The following parameters are used for either troubleshoot-
ing or are parameters adjusted at the factory. They should
never be changed in the field.
WINDOW: determines the amount of delay between the
generation of the transmitted signal pulse and the start of
the measurement cycle.
FID_TICKS: a measure of the time to the fiducial (refer-
ence) pulse.
FID_TICKS_SPREAD: provides an indication of the
stability of the FID_TICKS measurement.
LEVEL_TICKS: a measure of the time to the level of the
product being measured.
LEVEL_TICKS_SPREAD: provides an indication of the
stability of the LEVEL_TICKS measurement.
CONVERSION_FACTOR: the slope of the factory-set
calibration line.
SCALE_OFFSET: the intercept of the calibration line.
16
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
 
The last parameter in the TRANSDUCER block gives the
firmware version of the transmitter.
FIRMWARE_VERSION: displays the version of the
firmware.
NOTE: The user should compare the DD file and revision number of the
device with the HOST system to ensure they are at the same
revision level.
Refer to the table in section 1.3.1.
3.5 Analog Input Block
The ANALOG INPUT (AI) block takes the Eclipse Model
705 input data, selected by channel number, and makes it
available to other function blocks at its output:
 
PV: Either the primary analog value for use in executing the
function, or a process value associated with it.
OUT: The primary analog value calculated as a result of
executing the function block.
SIMULATE: Allows the transducer analog input or output
to the block to be manually supplied when simulate is
enabled. When simulate is disabled, the simulate value and
status track the actual value and status
XD_SCALE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point used with the value obtained from the transducer for
a specified channel.
OUT_SCALE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point to be used in displaying the OUT parameter.
GRANT_DENY: Options for controlling access of host
computers and local control panels to operating, tuning,
and alarm parameters of the block.
IO_OPTS: Option which the user may select to alter input
and output block processing.
STATUS_OPTS: Options which the user may select in the
block processing of status.
Offset
Probe Length
XD_SCALE "EU@100%" (in. cm, ft. m)
XD_SCALE "EU@0%" (in. cm, ft. m)
100%
0%

Channel Process Value
1 Level
2 Volume
3 Interface
4 Interface Volume
17
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
CHANNEL: The number of the logical hardware channel
that is connected to this I/O block. This information
defines the transducer to be used going to or from the
physical world.
L_TYPE: Determines if the values passed by the transducer
block to the AI block may be used directly (Direct) or if the
value is in different units and must be converted linearly
(Indirect), or with square root (Ind Sqr Root), using the
input range defined for the transducer and the associated
output range.
LOW_CUT: Limit used in square root processing.
PV_FTIME: Time constant of a single exponential filter for
the PV, in seconds.
FIELD_VAL: Raw value of the field device in % of PV
range, with a status reflecting the Transducer condition,
before signal characterization (L_TYPE) or filtering
(PV_FTIME).
UPDATE_EVT: This alert is generated by any change to
the static data.
BLOCK_ALM: The block alarm is used for all configuration,
hardware, connection failure or system problems in the block.
ALARM_SUM: The current alert status, unacknowledged
states, unreported states, and disabled states of the alarms
associated with the function block.
ACK_OPTION: Selection of whether alarms associated
with the function block will be automatically acknowl-
edged.
ALARM_HYS: Amount the PV must return within the
alarm limits before the alarm condition clears. Alarm hys-
teresis expressed as a percent of the span of the PV.
HI_HI_PRI: Priority of the high high alarm.
HI_HI_LIM: The setting for high high alarm in
engineering units.
HI_PRI: Priority of the high alarm.
HI_LIM: The setting for high alarm in engineering units
LO_PRI: Priority of the low alarm.
LO_LIM: The setting for low alarm in engineering units.
LO_LO_PRI: Priority of the low low alarm.
LO_LO_LIM: The setting for low low alarm in engineering
units.
HI_HI_ALM: The status for high high alarm and its
associated time stamp.
18
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
HI_ALM: Status for high alarm and associated time stamp.
LO_ALM: Status for low alarm and associated time stamp.
LO_LO_ALM: The status for low low alarm and its
associated time stamp.
The TRANSDUCER and AI blocks MODE_BLK parame-
ter must be set to AUTO to pass the PV Value through the
AI to the network.
Transducer scaling, called XD_SCALE, is applied to the
PV from the CHANNEL to produce the FIELD_VAL in
percent. Valid XD_SCALE engineering units is limited
to the five allowable codes of meters (m), centimeters (cm),
feet (ft), inches (in), and percent (%) for the Level channels,
or gallons, liters, % for the volume channels.
The AI blocks can have a BLOCK_ERR when:
1. Channel is not set correctly.
2. XD_SCALE does not have suitable engineering units or has
range incompatibility.
3. SIMULATE parameter is active
4. AI block MODE is O/S (out of service).
NOTE: This can be caused by the Resource Block being OOS or the AI
Block not scheduled for execution.
5. L-TYPE not set or set to Direct with improper
OUT_SCALE.
The AI block uses the STATUS_OPTS setting and the
TRANSDUCER PV LIMIT value to modify the AI PV
and OUT QUALITY.
Damping Filter is a feature of the AI block. The PV_FTIME
parameter is a time constant of a single exponential filter for
the PV, in seconds. This parameter can be used to dampen
out fluctuation in level due to excessive turbulence.
The AI block has multiple ALARM functions that monitor
the OUT parameter for out of bound conditions.

The Model 705 3x FOUNDATION fieldbus
Device Revision
2 transmitter incorporates a feature that allows the devices
Analog Input [AI] block Out values to be displayed on the
local LCD.
NOTE: There are many reasons that AI block Out values can deviate
from the measurement value originating in the Transducer
block, and because the keypad and local display will only pro-
vide access to Transducer block parameters, there is no way to
explore or change the other fieldbus configuration items affect-
ing the AI block output using the keypad and LCD.
19
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
These screens should only be considered as measured value
indicators for configured transmitters.
The screens are not used for commissioning or diagnostic /
troubleshooting purposes.
Prior to full fieldbus configuration (transmitter assigned a per-
manent address, AI block(s) configured and scheduled for exe-
cution, etc.), the value displayed will not reflect the transducer
measurement. (Pre-configuration values will typically be 0).
3.5.2.1 AI Out Display Screens
The Analog Input Out values will be conditionally dis-
played as part of the rotating” home menu screens.
The screens will be formatted as shown where # in the title
is the number of the AI block (1, 2, 3, or 4) and mmm is
one of: “Lvl”, “Vol”, “Ifc”, “IfV”, “---” depending on the
value of the associated AI blocks Channel parameter.
For example, AI1Lvl” would be the most commonly used
AI Out screen.
AI2---” would be displayed when the channel value is 0
[uninitialized] for AI block 2.
The Out value will be displayed subject to limitations nec-
essary for a 6-character display [999999 > Value > -99999].
Representative examples are shown below:
Because the Model 705 transmitter has four Analog Input
blocks any or all of which may be used in particular applica-
tions, a Transducer block parameter controls which AI block
Out values will be displayed.
The fieldbus presentation of this parameter will be similar
to that shown at left (host system dependent).
Any or all (or none) of the AI block Out values can be
selected for display on the LCD.
The local LCD version of this parameter is shown different-
ly due to the limitations of the LCD:
LCD label: AI Disp ”
The default value of the Local AI Display parameter will be
such that AI 1 Out is selected.
*AI#mmm*
######uu
*AI1Vol*
999999 L
*AI3Ifc*
0.0 %
*AI1Lvl*
99.5 cm
Analog Input Out Display
Local AI Display
AI1 Out
AI2 Out
AI3 Out
AI4 Out
None
AI1
AI2
AI1+AI2
AI3
AI1+AI3
AI2+AI3
AIs1,2,3
AI4
AI1+AI4
AI2+AI4
AIs1,2,4
AI3+AI4
AIs1,3,4
AIs2,3,4
All AIs
Analog Input Out Values
To Be Displayed
Out Value
Out Scale units
abbreviation
AI block channel
measurement type
Analog Input block #
20
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
3.6 PID Block
The PID Function Block contains the logic necessary to per-
form Proportional/Integral/Derivative (PID) control. The block
provides filtering, set point limits and rate limits, feedforward
support, output limits, error alarms, and mode shedding.
Although most other function blocks perform functions specific
to the associated device, the PID block may reside in any device
on the network. This includes a valve, a transmitter, or the host
itself.
The Enhanced Model 705 3X PID Block implementation fol-
lows the specifications documented by the Fieldbus Foundation.
 
ACK_OPTION: Used to set auto acknowledgement of
alarms.
ALARM_HYS: The amount the alarm value must return to
before the associated active alarm condition clears.
ALARM_SUM: The summary alarm is used for all process
alarms in the block.
ALERT_KEY: The identification number of the plant unit.
ALG_TYPE: Selects filtering algorithm as Backward or
Bi-linear.
BAL_TIME: The specified time for the internal working
value of bias to return to the operator set bias.
BKCAL_IN: The analog input value and status for another
blocks BKCAL_OUT output.
BKCAL_HYS: The amount the output must change away
from its output limit before the limit status is turned off,
expressed as a percent of the span of the output.
BKCAL_OUT: The value and status required by the
BKCAL_IN input for another block.
BLOCK_ALM: Used for all configuration, hardware, con-
nection failure, or system problems in the block.
BLOCK_ERR: Reflects the error status associated with the
hardware or software components associated with a block.
BYPASS: Used to override the calculation of the block.
CAS_IN: The remote setpoint value from another block.
CONTROL_OPTS: Allows one to specify control strategy
options.
DV_HI_ALM: The DV HI alarm data.
DV_HI_LIM: The setting for the alarm limit used to
detect the deviation high alarm condition.
DV_HI_PRI: The priority of the deviation high alarm.
DV_LO_ALM: The DV LO alarm data.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Magnetrol Eclipse Enhanced 705 Foundation Fieldbus User manual

Category
Measuring, testing & control
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI