10
thermostat prevents simultaneous operation of the heating
and cooling units and is equipped with an ON-AUTO fan
mode that allows the home owner to operate the indoor
blower when only air circulation is desired. Connect the
red, yellow, green and brown low voltage wires to the R or
RC, Y, G and W terminals respectively on the thermostat
base. The black wire is the 24 volt common required on
some thermostats. See Figure 9.
High Effi ciency Motor (3.5, 4, and 5 Ton)
1. Disconnect all electrical power to the unit and remove
the service panel.
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
2. Locate the orange and red wires terminated to the blower
motor. The orange wire controls cooling operation and
the red wire controls the heating operation.
CAUTION:
To avoid personal injury or property damage,
make sure the motor leads cannot come into
contact with any metal components of the unit.
3. Verify the required speed from the airfl ow data found
in Table 4. Place appropriate wire on the appropriate
motor speed tap for the required airfl ow.
4. Check all factory wiring as shown in the wiring diagram
and inspect the connections to make sure none of them
loosened during shipping or installation.
Figure 9. Low Voltage Connections
RED
R
YELLOW
Y
GREEN
G
BROWN
W
ORANGE
RED
R
YELLOW
Y
GREEN
G
BROWN
W
ORANGE
4 WIRE HEAT/COOL THERMOSTAT
Two Stage
Electric Heat
Single Stage Electric Heat
RED
R
YELLOW
Y
GREEN
BROWN
2 WIRE COOLING THERMOSTAT
CONTROL WIRE LEGEND:
GREEN - Blower Relay
RED - Transformer (24V)
YELLOW - Cooling 1st Stage
BROWN - Heating 1st Stage
ORANGE - Heating 2nd Stage
Table 3. Thermostat Wire Gauge
Thermostat
Wire Gauge
Recommended T-Stat Wire
Length (Unit to T-Stat)
2-Wire
(Heating)
5-Wire
(Heating/Cooling)
24 55 25
22 90 45
20 140 70
18 225 110
Blower Speed
For optimum system performance and comfort, it may be
necessary to change the factory speed setting.
WARNING:
To avoid electric shock, personal injury, or death,
turn off the electric power at the disconnect
or the main service panel before making any
electrical connections.
Standard Motor (2, 2.5 and 3 Ton)
1. Disconnect all electrical power to the unit and remove
the service panel.
2. Place the desired blower speed lead on the COM
terminal. Use another wire tie (fi eld supplied) to bundle
the remaining motor leads.
Table 4. Motor Lead Connection
Model
Number
P5RD
Speed
Tap
External Static Pressure (in. WC)
0.1 0.2 0.3 0.4 0.5 0.6
024K
Low* 847 808 770 726 664 562
High** 1,104 1,114 1,064 1,010 935 846
030K
Low
†
847 808 770 726 664 562
High 1,104 1,114 1,064 1,010 935 846
036K
Low
†
1,323 1,285 1,246 1,196 1,146 1,087
High 1,559 1,525 1,486 1,430 1,381 1,315
042K
Tap T1 1,100 900 750 650 580 520
Tap T2 1,170 1,080 1,000 620 900 860
Tap T3 1,220 1,180 1,140 1,100 1,070 1,020
Tap T4* 1,370 1,333 1,300 1,260 1,230 1,180
Tap T5** 1,410 1,340 1,450 1,320 1,280 1,240
048K
Tap T1 1,380 1,360 1,340 1,300 1,260 1,240
Tap T2** 1,530 1,480 1,450 1,420 1,390 1,350
Tap T3* 1,570 1,540 1,500 1,475 1,440 1,405
Tap T4 1,740 1,700 1,650 1,630 1,600 1,560
Tap T5 2,130 2,080 1,970 1,890 1,850 1,800
060K
Tap T1 1,380 1,360 1,340 1,300 1,260 1,240
Tap T2** 1,530 1,480 1,450 1,420 1,390 1,350
Tap T3 1,570 1,540 1,500 1,475 1,440 1,405
Tap T4* 1,740 1,700 1,650 1,630 1,600 1,560
Tap T5 2,130 2,080 1,970 1,890 1,850 1,800
NOTE: Airfl ow performance is with a dry coil
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
†
Factory set cooling and electric heating speed