Unbranded FG7S(A,K) Installation guide

Type
Installation guide
Single Stage High Effi ciency Gas Furnaces
INSTALLATION INSTRUCTIONS
*SA Upfl ow / Horizontal Model *SK Downfl ow Model
80+ AFUE
DO NOT DESTROY THIS MANUAL. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly
could result in serious injury or property
damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or the
gas supplier.
• Do not store or use gasoline or other
ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
WARNING:
RISQUE D’INCENDIE OU D’ EXPLOSION
Le non-respect des avertissements de
sécurité pourrait entraîner des blessures
graves, la mort ou des dommages matériels.
L’installation et l’entretien doivent être
effectués par un installateur qualifié, un
organisme de service ou le fournisseur de
gazstaller, service agency or the gas supplier.
Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
Ne pas tenter d’allumer aucun appareil.
Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de
gaz en employant le téléphone d’un voisin.
Respecter à la lettre les instructions du
fournisseur de gaz.
Si personne ne répond, appeler le service des
incendies.
AVERTISSEMENT
2
IMPORTANT SAFETY INFORMATION .......................3
REQUIREMENTS & CODES .......................................3
Combustion Air Quality ...........................................4
Operation of Furnace During Construction .............4
Installation in a Garage ...........................................4
Clearances to Combustible Materials .....................5
Heating Load ...........................................................5
COMBUSTION AIR & VENTING REQUIREMENTS ....6
General Information ................................................7
Installation in a Confi ned Space ..............................7
Air From Inside ...................................................7
Outdoor Air Using a Crawl Space or
Vented Attic ........................................................7
Outdoor Air Using Vertical Ducts ........................8
Outdoor Air Using Horizontal Ducts ...................8
Air Directly Through an Exterior Wall .................8
Alternate Method of Providing Air from
Outside ...............................................................9
Installation in an Unconfi ned Space ........................9
Category I Venting ...................................................9
Horizontal Venting .................................................. 10
Flexible Vent Systems ............................................ 10
CIRCULATING AIR REQUIREMENTS ......................11
Plenums & Air Ducts ..............................................11
Supply Air Connections .........................................11
Upfl ow / Horizontal Furnaces ............................11
Downfl ow Furnaces ...........................................11
Return Air Connections .........................................11
Upfl ow / Horizontal Furnaces ............................ 11
Side Return Installations ................................. 11
Bottom Return Installations ............................ 12
Downfl ow Furnaces ........................................... 12
Acoustical Treatments............................................ 12
FURNACE INSTALLATION .......................................12
General Requirements ..........................................12
Upfl ow Installation .................................................12
Side Return Air Inlet .........................................12
Bottom Return Air Inlet .....................................12
Downfl ow Installation ............................................12
Installation on a Concrete Slab ........................13
Horizontal Installation ............................................13
Pressure Switches ................................................14
Bottom Panel Removal ..........................................14
Alternate Bottom Panel Removal .....................14
GAS SUPPLY & PIPING ............................................15
Leak Check ...........................................................15
High-Altitude Application .......................................16
Conversion to LP / Propane ..................................18
ELECTRICAL WIRING ...............................................18
Line Voltage Wiring ................................................19
Grounding ..............................................................19
Thermostat / Low Voltage Connections .................20
Heat Anticipator ................................................20
Twinning .................................................................20
START-UP & ADJUSTMENTS ...................................21
Pre-Start Checklist ................................................21
Start-Up Procedures ..............................................21
Verifying & Adjusting Input Rate ............................21
Verifying & Adjusting Temperature Rise ................22
Verifying Burner Operation ....................................22
Verify Operation of the Supply Air
Limit Switch ...........................................................22
OPERATING SEQUENCE .........................................22
Heating Cycle ........................................................22
Cooling Cycle ........................................................23
Fan Mode ..............................................................23
TABLE OF CONTENTS
3
DESCRIPTION OF COMPONENTS ..........................23
MAINTENANCE .........................................................23
Air Filters ...............................................................24
Blower Compartment ............................................24
Cleaning of Burners ..............................................24
Cleaning of Flue Passages ...................................24
Vent System ..........................................................25
Heat Exchanger & Burner Maintenance ...............25
Lubrication ............................................................25
TROUBLESHOOTING ...............................................25
FIGURES & TABLES .................................................26
Figure 18 - Furnace Dimensions ......................26
Airfl ow Data ...........................................................27
Table 4 - Upfl ow / Horizontal Gas Furnaces .....27
Table 5 - Downfl ow Gas Furnaces ....................29
Electrical Information.............................................30
Figure 19 - Wiring Diagram ..............................30
Gas Information .....................................................31
Table 6 - Gas Flow Rates.................................31
Table 7 - Gas Pipe Capacities .........................31
Table 8 - High Altitude Deration Chart for
Propane Gas .....................................32
Table 9 - Natural Gas Heating Values ..............32
Table 10 - High Altitude Deration Chart for
Nat. Gas - High Heating Values .......33
Table 11 - High Altitude Deration Chart for
Nat. Gas - Low Heating Values........33
Location of Furnace Components .........................34
Figure 20 - Furnace Components ....................34
INSTALLATION / PERFORMANCE CHECKLIST .....36
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment.
Pay attention to all safety warnings and any other special
notes highlighted in the manual. Safety markings are
used frequently throughout this manual to designate a
degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that
if not avoided, could result in personal injury or death.
CAUTION indicates a potentially hazardous situation that
if not avoided, may result in minor or moderate injury or
property damage.
REQUIREMENTS & CODES
WARNING:
The information listed below must be followed
during the installation, service, and operation
of this furnace. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious personal
injury or death.
This furnace must be installed in accordance with
these instructions, all applicable local building codes
and the current revision of the National Fuel Gas Code
(NFPA54/ANSI Z223.1) or the Natural Gas and Propane
Installation Code, CAN/CGA B149.1.
Use only with type of gas approved for this furnace.
Refer to the furnace rating plate.
Install this furnace only in a location and position as
specifi ed on page 5.
Provide adequate combustion and ventilation air to the
furnace space as specifi ed on pages 6 - 10.
Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only,
as specifi ed on pages 9 - 10.
Never test for gas leaks with an open fl ame. Use a
commercially available soap solution to check all
connections. See pages 15 - 16.
This furnace is designed to operate with a maximum
external pressure rise of 0.5 inches of water column.
Consult Tables 4 - 5 (pages 27 - 29), and the rating
plate for the proper circulating air fl ow and temperature
rise. It is important that the duct system be designed to
handle the desired fl ow rate and temperature rise. An
improperly designed duct system can result in nuisance
shutdowns, and comfort or noise issues.
When supply ducts carry air circulated by the furnace
to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space
containing the furnace. See pages 11 - 12.
This furnace may be used for temporary heating of
buildings or structures under construction. See the
guidelines listed on page 4.
• A gas-fi red furnace for installation in a residential garage
must be installed as specifi ed on page 4.
This furnace is not approved for installation in mobile
homes. Installing this furnace in a mobile home could
cause fi re, property damage, and/or personal injury.
4
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a
corrosive atmosphere.
To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use outdoor air. However,
the use of indoor air in most applications is acceptable
except as listed:
If the furnace is installed in a confi ned space, it is
required that the necessary combustion air come from
the outdoors by way of attic, crawl space, air duct, or
direct opening. For Installations in confi ned spaces, see
pages 7 - 8 for combustion air requirements.
Installations in these locations may require outdoor air
for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion
air supply may require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners
Masonry acid washing materials
Operating gas furnaces in construction environments can
cause a variety of problems with the furnace. Proper use
of commercial portable space heating equipment during
construction is recommended. This gas furnace may be
used during construction if it is not in violation of any
applicable codes and the following criteria are met:
The installation must meet all applicable codes. The
furnace must be permanently installed according to
the instructions with the furnace including electrical
supply, gas supply, duct work and venting. The furnace
must be controlled by a thermostat properly installed
according to the instructions supplied with the furnace
and thermostat. The installation must include a properly
installed fi lter in the return air system with no by-pass
air. The lter must be inspected frequently and replaced
when necessary.
Combustion air must be supplied from outside the
structure and located such that dust and gases
from construction activity are not introduced into the
combustion system.
Before occupying the structure: The fi lter must be
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the furnace
must be cleaned and/or repaired if found to be dirty,
damaged, or malfunctioning in any way by a qualifi ed
HVAC technician. The furnace shall be inspected and
approved by applicable local authority even if this
requires redundant inspections.
Serial numbers for furnaces used during construction
must be submitted in writing (fax and email also
acceptable). This information will be used to track the
long-term affects of the use during construction on
furnaces. Proof of this submittal shall be available for
the fi nal inspection of the furnace prior to occupancy.
This furnace is designed to operate with return air
temperatures in ranges normally found in occupied
residences, including setbacks. Minimum continuous
return temperature must not fall below 60° F (15° C).
Occasionally a temporary return temperature of 55° F
(12° C) is acceptable. However, operation with a return
temperature below 55° F (12° C) is not allowed.
Operation of Furnace During Construction
CAUTION:
Failure to follow these instructions will void the
factory warranty and may signifi cantly reduce
the life or the performance of the furnace, and/
or result in other unsafe conditions. It is the
responsibility of the installing contractor to
insure these provisions are met.
Installation in a Garage
WARNING:
Do not place combustible materials on or
against the furnace cabinet or within 6 inches
of the vent pipe. Do not place combustible
materials, including gasoline or any other
ammable vapors and liquids, in the vicinity
of the furnace.
This gas-fi red furnace may be installed in a residential
garage with the provision that the burners and igniter
are located no less than 18 inches (457mm) above the
oor. The furnace must be located or protected to prevent
physical damage by vehicles.
5
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada
by CSA International for the minimum clearances to
combustible materials. NOTE: The furnace is listed for
installation on combustible or non-combustible fl ooring.
However, wood is the only combustible fl ooring allowed
for installation. Downfl ow models must use the appropriate
subase kit when installing over a wood fl oor. To obtain
model number and specifi c clearance information, refer
to the furnace rating plate, located inside of the furnace
cabinet.
Access for positioning and servicing the unit must be
considered when locating unit. The need to provide
clearance for access to panels or doors may require
clearance distances over and above the requirements.
Allow 24 inches minimum clearance from the front of
the unit. However 36 inches is strongly recommended.
See Table 1 for minimum clearance requirements.
Table 1. Minimum Clearances to
Combustible Materials
CLEARANCES TO COMBUSTIBLE MATERIALS
Left Side..................0 Inches Top ..........................0 Inches
Right Side ...............0 Inches Front ......................
4 Inches
Vent ......................... 0 Inches Back ........................0 Inches
Allow 24 in. minimum clearance for servicing. Recommended
clearance is 36 in.
UPFLOW & DOWNFLOW
APPLICATIONS
HORIZONTAL
APPLICATIONS
BACK
FRONT
LEFT SIDE
RIGHT SIDE
VENT
VENT
SIDE
TOP
BOTTOM
SIDE
TOP
FRONT
The information listed below is for reference purposes only
and does not necessarily have jurisdiction over local or state
codes. Always consult with local authorities before installing
any gas appliance.
Combustion and Ventilation Air
US: National Fuel Gas Code (NFGC), Air for Combustion
and Ventilation
CANADA: Natural Gas and Propane Installation Codes
(NSCNGPIC), Venting Systems and Air Supply for
Appliances
Duct Systems
US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) Fundamentals Handbook
Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA 70
CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269; or American
Gas Association, 400 N. Capitol, N.W., Washington DC
20001 or www.NFPA.org
CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard,
Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Safety
US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the
Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
CANADA: CAN/CGA-B149.1 and .2–M00 National
Standard of Canada. (NSCNGPIC)
Heating Load
The furnace should be sized to provide the design heating
load requirement. Heating load estimates can be made
using approved methods available from Air Conditioning
Contractors of America (Manual J); American Society of
Heating, Refrigerating, and Air Conditioning Engineers;
or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace
and/or vent to fail prematurely.
The ductwork should be appropriately sized to the capacity
of the furnace to ensure its proper airfl ow rating. For
installations above 2,000 ft., the furnace should have a
sea level input rating large enough that it will meet the
heating load after deration for altitude.
6
COMBUSTION AIR & VENTING REQUIREMENTS
RISQUE D’EMPOISONNEMENT AU
MONOXYDE DE CARBONED
Le non-respect des consignes suivantes portant
sur chacun des appareils raccordés au système
d’évacuation mis en service pourrait entraîner
l’empoisennement au monoxyde de carbone ou
la mort. Les consignes suivantes doivent être
observées pour chaque appareil raccordé au
système d’évacuation mis en service si les autres
appareils raccordés au système ne sont pas en
service:
1. Sceller toute ouverture non utilisée de la systéme
d’évacuation;
2. S’assurer que la systéme d’évacuation présente des
dimensions et une pente horizontale conformes à la
norme ANSI Z223.1/NFPA 54, intitulée National Fuel
Gas Code ou aux codes d’installation CSA-B149.1,
ainsi qu’aux présentes instructions. S’assurer que la
systéme d’évacuation n’est pas bloquée, restreinte,
corrodée, qu’elle ne fuit pas et qu’elle ne présente
aucun autre défaut potentiellement dangereux;
3. Dans la mesure du possible, fermer toutes les portes
et fenêtres du bâtiment, et toutes les portes entre la
pièce où se trouve l’appareil raccordé à la systéme
d’évacuation et les autres pièces du bâtiment.
4. Fermer les registres des foyers;
5. Mettre en service les sécheuses et tout autre appareil
qui n’est pas raccordé à la systéme d’évacuation.
Faire fonctionner à régime maximal tout ventilateur
d’évacuation, tel que les hottes de cuisinière et les
ventilateurs de salles de bains. Ne pas mettre en
service les ventilateurs d’été.
6. Respecter les instructions d’allumage. Mettre en
service l’appareil à l’essai. Régler le thermostat
de manière à ce que l’appareil fonctionne sans
interruption;
7. Vérifi er s’il y a débordement à l’orifi ce d’évacuation
du coupe tirage des appareils dotés d’un coupe
tirage 5 minutes après l’allumage du brûleur
principal. Utiliser la fl amme d’une allumette ou
d’une chandelle.
8. Si l’on constate, au cours de l’un des essais qui
précèdent, que l’évacuation est défi ciente, corriger
le système d’évacuation conformément à la norm
ANSI Z223.1/NFPA 54, National Fuel Gas Code, et
(ou) aux codes d’installation CSA B149.1.
9. Après avoir déterminé que tous les appareils
raccordés à la systéme d’évacuation évacuent
correctement tel que prescrit ci-dessus, rouvrir les
portes et les fenêtres et remettre les ventilateurs
d’évacuation, les registres de foyers et tout
autre appareil fonctionnant au gaz à leur état de
fonctionnement initial.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below
for each appliance connected to the venting
system being placed into operation could
result in carbon monoxide poisoning or death.
The following steps shall be followed with
each individual appliance connected to the
venting system being placed in operation,
while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting
system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or
the CSA B149.1, Natural Gas and Propane
Installation Codes and these instructions.
Determine that there is no blockage or
restriction, leakage, corrosion and other
defi ciencies which could cause an unsafe
condition.
3. As far as practical, close all building doors
and windows and all doors between the space
in which the appliance(s) connected to the
venting system are located and other spaces
of the building.
4. Close replace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on
any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer
exhaust fan.
6. Follow the lighting instructions. Place the
appliance being inspected into operation.
Adjust the thermostat so appliance is
operating continuously.
7. Test for spillage from draft hood equipped
appliances at the draft hood relief opening
after 5 minutes of main burner operation. Use
the fl ame of a match or candle.
8. If improper venting is observed during any of
the above tests, the venting system must be
corrected in accordance with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or CSA
B149.1, Natural Gas and Propane Installation
Codes.
9. After it has been determined that each
appliance connected to the venting system
properly vents when tested as outlined above,
return doors, windows, exhaust fans, fi replace
dampers and any other gas-fi red burning
appliance to their previous conditions of use.
WARNING:
AVERTISSEMENT:
7
General Information
WARNING:
Furnace installation using methods other than
those described in the following sections must
comply with the National Fuel Gas Code (NFGC)
and all applicable local codes.
Instructions for determining the adequacy of combustion
air for an installation can be found in the current revision
of the NFGC (ANSI Z223.1 / NFPA54). Consult local
codes for special requirements. These requirements
are for US installations as found in the NFGC.
The requirements in Canada (B149.1) are structured
differently. Consult with B149.1 and local code offi cials
for Canadian installations.
Provisions must be made during the installation of
this furnace that provide an adequate supply of air for
combustion.
CAUTION:
Exhaust fans, clothes dryers, replaces and
other appliances that force air from the house
to the outdoors can create a negative pressure
inside the house, resulting in improper furnace
operation or unsafe conditions such as fl ame roll
out. It is imperative that suffi cient air exchange
with the outdoors is provided to prevent
depressurization. Additional information about
how to test for negative pressure problems can
be found in the NFGC.
Air openings on top of the furnace and openings in closet
doors or walls must never be restricted. If the furnace is
operated without adequate air for combustion, the fl ame
roll-out switch will open, turning off the gas supply to the
burners. NOTE: This safety device is a manually reset
switch. DO NOT install jumper wires across these
switches to defeat their function or reset a switch
without identifying and correcting the fault condition.
If a switch must be replaced, use only the correct sized part
specifi ed in the Replacement Parts List provided online.
Installation In A Confi ned Space
A confi ned space is an area with volume less than 50
cubic feet per 1,000 Btuh of the combined input rates of
all appliances drawing combustion air from that space.
Furnace closets, small equipment rooms and garages are
confi ned spaces. Furnaces installed in a confi ned space
which supply heated air to areas outside the space must
draw return air from outside the space and must have the
return air ducts tightly sealed to the furnace.
The required sizing of these openings is determined by
whether inside or outside air is used to support combustion,
the method by which the air is brought to the space, and
by the total input rate of all appliances in the space. In
all cases, the minimum dimension of any combustion air
opening is 3 inches.
Air From Inside
If combustion air is taken from the heated space, the two
openings must each have a free area of at least one square
inch per 1,000 Btuh of total input of all appliances in the
confi ned space, but not less than 100 square inches of
free area (Figure 1). See example.
Example:
If the combined input rate of all appliances is less
than or equal to 100,000 Btuh, each opening must
have a free area of at least 100 square inches. If the
combined input rate of all appliances is 120,000 Btuh,
each opening must have a free area of at least 120
square inches.
Furnace
12" Max.
Water
Heater
Vent or
Chimney
NOTES:
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1,000
Btuh of total input rating,
whichever is greater.
Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.
12” Max.
See
Notes
See Notes
Figure 1. Combustion Air Drawn from Inside
Total Input Rating
(Btuh)
Minimum Free Area
(Each Opening)
Round Duct
Diameter
40,000 100 sq. In 12 inches
60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches
100,000 100 sq. In 12 inches
120,000 120 sq. In 13 inches
140,000 140 sq. In 14 inches
160,000 160 sq. In 15 inches
Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the
outdoors, each opening shall have a minimum free area
of 1 square inch per 4,000 Btuh of total appliance input.
The openings shall exchange directly, or by ducts, with
the outdoor spaces (crawl or attic) that freely exchange
with the outdoors (Figure 2, page 8).
8
Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical
ducts, the openings and ducts must have a minimum
free area of one square inch per 4,000 Btuh of total
appliance input. In installations drawing combustion air
from a ventilated attic, both air ducts must extend above
the attic insulation (Figure 3).
Figure 2. Combustion Air Drawn from a Crawl
Space or Vented Attic
Attic
Insulation
Crawl Space
Ventilated Louvers for
unheated crawl space
Inlet air duct must be at
least 1 sq. in. per 4,000
Btuh of total input rating.
Outlet air duct must be
at least 1 sq. in. per
4,000 Btuh of total
input rating. Must
extend above attic
insulation
Water
Heater
Furnace
Vent or
Chimney
Ventilation louvers
at each end of attic
Figure 4. Combustion Air Drawn from Outside
Through Horizontal Ducts
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
12" Max
12" Max
Furnace
Vent or
Chimney
Water Heater
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Air Duct
Air Duct
NOTE: Each
opening to
outside must
be at least 1
sq. in. per 2,000
Btuh of total
input rating.
See
Note
Total Input Rating
(Btuh)
Minimum Free Area
(Each Opening)
Round Duct
Diameter
40,000 10 sq. In 5 inches
60,000 15 sq. In 6 inches
80,000 20 sq. In 7 inches
100,000 25 sq. In 8 inches
120,000 30 sq. In 9 inches
140,000 35 sq. In 10 inches
160,000 40 sq. In 10 inches
Figure 5. Combustion Air Drawn from Outside
Through an Exterior Wall
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
12" Max
12" Max
Furnace
NOTE: Each opening
to outside must be at
least 1 sq. in. per
4,000 Btuh of total
input rating.
Vent or
Chimney
Water Heater
See
Note
Total Input Rating
(Btuh)
Minimum Free Area
(Each Opening)
Round Duct
Diameter
40,000 10 sq. In 4 inches
60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches
100,000 25 sq. In 6 inches
120,000 30 sq. In 6 inches
140,000 35 sq. In 7 inches
160,000 40 sq. In 8 inches
Figure 3. Combustion Air Drawn from Outside
Through Vertical Ducts
Inlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Inlet and Outlet
Ducts must
extend above
attic insulation.
Outlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Ventilation Louvers at
each end of attic
Attic
Insulation
12" Max
Furnace
Water
Heater
Vent or
Chimney
Total Input Rating
(Btuh)
Minimum Free Area
(Each Opening)
Round Duct
Diameter
40,000 100 sq. In 12 inches
60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches
100,000 100 sq. In 12 inches
120,000 120 sq. In 13 inches
140,000 140 sq. In 14 inches
160,000 160 sq. In 15 inches
Air Directly Through An Exterior Wall
If combustion air is provided directly through an exterior
wall, the two openings must each have free area of at
least one square inch per 4,000 Btuh of total appliance
input (Figure 5).
Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal
ducts, the openings and ducts must have a minimum free
area of one square inch per 2,000 Btuh of total appliance
input (Figure 4).
9
Alternate Method of Providing
Air from Outside:
If acceptable under local Codes, it is permitted to provide
outside air using one opening (See NFGC). Generally,
confi ned spaces must have two openings in the space
for combustion air. One opening must be within 12
inches of the ceiling, and the other must be within 12
inches of the fl oor. However, an alternative method
recently adopted by the NFGC uses one opening within
12 inches of the top of the space. This method may be
used if it is acceptable to the local codes.
The following conditions must be met:
1. The opening must start within 12” of the top of the
structure and connect with the out of doors through
vertical or horizontal ducts or be ducted to a crawl
or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1 sq.
in. per 3,000 Btu per hour of the total input rating of
all equipment located in the enclosure.
3. The free area must not be less than the sum of all
the areas of the vent connectors in the enclosure.
Example:
A space with a water heater rated at 45,000 Btuh
input and a furnace rated at 75,000 Btuh requires a
volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to
be considered unconfi ned. If the space has an 8 foot
ceiling, the fl oor area of the space must be 750 square
feet (6,000 / 8 = 750).
Installation In An Unconfi ned Space
An unconfi ned space is an area including all rooms not
separated by doors with a volume greater than 50 cubic
feet per 1,000 Btuh of the combined input rates of all
appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will
not require outside air for combustion. However, in homes
built for energy effi ciency (low air change rates), it may
be necessary to provide outside air to ensure adequate
combustion and venting, even though the furnace is located
in an unconfi ned space. See example.
Category I Venting
This furnace is listed as a Category I vented appliance.
Category I furnaces generally operate with a slight
negative pressure (draft) and must be vented vertically or
near vertical. Additionally it is important to guard against
excessive condensation.
WARNING:
Upon completion of the furnace installation,
carefully inspect the entire fl ue system both
inside and outside the furnace to assure it is
properly sealed. Leaks in the fl ue system can
result in serious personal injury or death due
to exposure of fl ue products, including carbon
monoxide.
This furnace must be vented in compliance with
the current revision of the National Fuel Gas Code
(ANSI-Z223.1/NFPA54) and the instructions provided
below. Consult local codes for special requirements.
In Canada, venting shall conform to the requirements of
the current (CAN/CGA B149.1 or .2) installation codes.
Consult local codes for special requirements.
Category I furnace installations must be connected
to a factory built chimney or vent complying with a
recognized standard, or a masonry or concrete chimney
lined with a lining material acceptable to the authority
having jurisdiction.
WARNING:
Venting into an unlined masonry chimney or
concrete chimney is prohibited. This may result
in improper draft and excess condensation
forming in the chimney.
This furnace may be vented with a dedicated venting
system or common vented with other Category I
appliances. The vent system dimensions and material
must conform to the NFGC or local Codes. Generally,
this means using Type B vent pipe or a lined masonry
chimney. When consulting the vent sizing tables in the
NFGC, the MAX capacity of the vent must be greater
than the furnaces high fi re rate. The MIN capacity must
be lower than the low fi re rate. If the venting system
is inappropriate for the furnace, the venting system
will need to be modifi ed to comply with NFGC or local
codes. The minimum diameter of any vent pipe is 4
inches.
The venting system should be designed to have the
minimum number of elbows or turns. All horizontal runs
shall slope upwards from the furnace at ¼ inch per
running foot of vent. Supports for the vent pipe must
be installed a minimum of every fi ve feet along the vent
run to ensure no displacement after installation. Under
no circumstances shall any portion of the vent system
10
extend into or pass through any return air duct, supply
air duct, or plenum.
Single wall vent connectors may be used under the
limited capacity ranges found in the vent sizing tables.
It is recommended that Type B double wall vent be
used for the connector whenever possible. An existing
masonry chimney should be inspected and relined if
necessary.
In the U.S., this furnace must never be vented to
a chimney or fl ue that services a fi replace or other
appliance designed to burn solid fuel. If the furnace
vent is to be connected to a chimney serving a fi replace,
the fi replace must be sealed off from the chimney. In
Canada, common venting with a fi replace is permitted.
Consult B149.1 and your local code authority.
Single wall metal vertical vents shall not be used for
Category I venting. The furnace vent, if metal, may
be insulated if local codes allow. Any part of the vent
system, metal vent only, not exposed to weather,
but which are exposed to temperatures below 35° F
(1° C) must be insulated to prevent condensation. All
vent insulation shall be foil backed fi berglass of one
inch minimum thickness.
Sheet metal fasteners should be used to secure the vent
pipe to the furnace fl ue. However, the NFGC states that
alternative vent products may be attached according to
the vent manufacturers instructions.
When an existing furnace is removed from a vent
system serving other appliances, the existing vent
system may no longer be sized to properly vent the
remaining appliances. An improperly sized venting
system can result in the formation of condensate,
leakage, or spillage. The existing vent system should
also be checked to make sure it remains in compliance
with NFGC. If it isn’t, the vent system must be brought
into compliance before installing the furnace.
Horizontal Venting
WARNING:
Horizontal vent systems must be sealed with
a high temperature sealant that can withstand
temperatures of 450° F. Recommended sealants:
Dow Corning Sealant 736 RTV; GE 106 RTV;
High Tech Ind., High TEMP RED.
This furnace is not approved for horizontal venting
without the use of an add-on power venter. Power venters
establish negative pressure in the vent piping and the
furnace operates as if connected to a Category I vertical
vent. The power venter is only for use when exhausting
through an exterior wall.
The power venter must be installed according to the
instructions provided by the power venter manufacturer
and applicable requirements of local codes. For Canadian
installations please refer to the Canadian Installation Code
(CAN/CGA-B149.1 or 2) and/or local codes.
The outlet of the vent must be at least 12 inches above
the highest expected snow accumulation.
Flexible Vent Systems
Flexible venting systems are approved for use providing
they are listed for the application and meet all local Code
requirements. These systems are primarily used to line
existing masonry chimneys. They must be sized to the
application according to the sizing tables in the National
Fuel Gas Code, including the required 20% reduction in
maximum capacity.
Flexible venting systems are permitted to be used as the
vent connector. However, great care must be taken to
ensure that there are no sags in the venting system which
could accumulate condensate. The fl exible vent system
must be supported at no more than 5 foot intervals and
maintain a minimum slope of ¼ inch per foot of horizontal
run.
11
WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the
circulation of combustion products into the
living space can create potentially hazardous
conditions including carbon monoxide
poisoning that could result in personal injury
or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confi ned spaces, all return
ductwork must be adequately sealed. When
return air is provided through the bottom of the
furnace, the joint between the furnace and the
return air plenum must be air tight.
The surface that the furnace is mounted on must
provide sound physical support of the furnace
with no gaps, cracks or sagging between the
furnace and the fl oor or platform.
Return air and circulating air ductwork must
not be connected to any other heat producing
device such as a fi replace insert, stove, etc. This
may result in fi re, explosion, carbon monoxide
poisoning, personal injury, or property damage.
Plenums & Air Ducts
Plenums and air ducts must be installed in accordance
with the Standard for the Installation of Air Conditioning
and Ventilating Systems (NFPA No. 90A) or the
Standard for the Installation of Warm Air Heating and
Air Conditioning Systems (NFPA No. 90B).
Tables 4 - 5 (pages 27 - 29) contain the maximum
airfl ow and temperature rise data for each furnace input
rate. If the maximum airfl ow is 1,600 CFM or more, it is
recommended that two openings be used for return air
on upfl ow furnaces. Downfl ow furnaces can only use
one return opening.
It is recommended that the outlet duct contain a
removable access panel. The opening should be
accessible when the furnace is installed in service and
shall be of a size that smoke or refl ected light may be
observed inside the casing to indicate the presence of
leaks in the heat exchanger. The cover for the opening
shall be attached in such a manner as to prevent leaks.
If outside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system
must be designed so that the return air is not less than
60° F (15° C) during operation. If a combination of indoor
and outdoor air is used, the ducts and damper system
must be designed so that the return air supply to the
furnace is equal to the return air supply under normal,
indoor return air applications.
When a cooling system is installed which uses the
furnace blower to provide airfl ow over the indoor coil,
the coil must be installed downstream (on the outlet
side) of the furnace or in parallel with the furnace.
If a cooling system is installed in parallel with the
furnace, a damper must be installed to prevent chilled
air from entering the furnace and condensing on the
heat exchanger. If a manually operated damper is
installed, it must be designed so that operation of
the furnace is prevented when the damper is in the
cooling position and operation of the cooling system is
prevented when the damper is in the heating position.
It is good practice to seal all connections and joints
with industrial grade sealing tape or liquid sealant.
Requirements for sealing ductwork vary from region
to region. Consult with local codes for requirements
specifi c to your area.
Supply Air Connections
The supply air must be delivered to the heated space by
duct(s) secured to the furnace casing, running full size
and without interruption.
Upfl ow & Horizontal Furnaces
To attach the supply air duct to the furnace, bend the
furnace fl anges (Figure 18, page 26) upward 90° with a
pair of wide duct pliers. Position the duct on top of the
furnace and secure together with sheet metal screws. The
screws must penetrate the sheet metal casing and furnace
ange. Tape or seal all seams if required by local code.
Downfl ow Furnaces
To attach the supply air duct to the downfl ow furnace,
position the furnace over the duct and secure together
with sheet metal screws. The screws must penetrate the
duct and furnace casing.
Return Air Connections
In applications where the supply ducts carry heated air
to areas outside the space where the furnace is installed,
the return air must be delivered to the furnace by duct(s)
secured to the furnace casing, running full size and without
interruption.
Upfl ow & Horizontal Furnaces
For upfl ow installations, the return air ductwork may
be connected to the left side, right side, or bottom. The
bottom panel (Figure 18) must be installed for left or right
return air. NOTE: Do not use the back of the furnace
for return air.
Side Return Installations
To attach the return air duct to the left or right side of
the furnace, punch out the four knockouts from the side
of the furnace (Figure 18, page 26). Using sharp metal
CIRCULATING AIR REQUIREMENTS
12
FURNACE INSTALLATION
*SA series gas furnaces are shipped ready for installation in
the upfl ow or horizontal right or left positions. Only the *SK
series gas furnace may be used for downfl ow operation.
General Requirements
The furnace must be leveled at installation and attached
to a properly installed duct system. See Table 1
(page 5) for the required clearances needed to move
the furnace to its installation point (hallways, doorways,
stairs, etc).
The furnace must be installed so that all electrical
components are protected from water.
The furnace must be installed upstream from a
refrigeration system. (If applicable)
The furnace requires special venting materials and
installation procedures. See pages 9 -10 for venting
guidelines and specifi cations.
Upfl ow Installation
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
Side Return Air Inlet
*SA series gas furnaces are shipped with the bottom panel
installed (Figure 18). If the upfl ow furnace is installed with
side return air, the bottom panel must not be removed.
Bottom Return Air Inlet
*SA series gas furnaces are shipped with the bottom panel
installed. If the upfl ow furnace is installed with bottom
return air, the bottom panel must be removed. See Bottom
Panel Removal on page 14.
Downfl ow Installation
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
WARNING:
Failure to install the downfl ow sub-base kit may
result in fi re, property damage or personal injury.
To install the furnace on combustible fl ooring, a special
sub-base is required. Downfl ow sub-base kits are factory
supplied accessories and are listed according to the cabinet
letter of the furnace. For ‘A’ size cabinets use Sub-Base
kit #902974 only. For ‘B’, ‘C’, and ‘D’ size cabinets use
Kit #904911. Please follow the instructions provided
with the kit.
cutters, cut an opening between all four knockouts to
expose the blower assembly. Position the return air duct
over the opening in the side and secure together with
sheet metal screws. The screws must penetrate the duct
and furnace casing.
WARNING:
The solid base of the furnace must be in
place when the furnace is installed with side
return air ducts. Removal of all or part of the
base could cause circulation of combustible
products into the living space and create
potentially hazardous conditions, including
carbon monoxide poisoning that could result
in personal injury or death.
Bottom Return Installations
The bottom panel (Figure 18) must be removed from the
bottom of the furnace for bottom return air. If bottom panel
is still installed, go to page 14 for removal instructions.
Position the furnace over the return air duct and secure
together with sheet metal screws. The screws must
penetrate the duct and furnace casing.
Downfl ow Furnaces
To attach the return air duct to the furnace, bend the
furnace fl anges (Figure 18) upward 90° with a pair of
wide duct pliers. Position the duct on top of the furnace
and secure together with sheet metal screws. The screws
must penetrate the sheet metal casing and furnace fl ange.
Tape or seal all seams if required by local code.
Acoustical Treatments
Damping ducts, fl exible vibration isolators, or pleated
media-style fi lters on the return air inlet of the furnace
may be used to reduce the transmission of equipment
noise eminating from the furnace. These treatments can
produce a quieter installation, particularly in the heated
space. However, they can increase the pressure drop in
the duct system. Care must be taken to maintain the proper
maximum pressure rise across the furnace, temperature
rise and fl ow rate. This may mean increasing the duct
size and/or reducing the blower speed. These treatments
must be constructed and installed in accordance with
NFPA and SMACNA construction standards. Consult
with local codes for special requirements. For best sound
performance, be sure to install all the needed gaskets and
grommets around penetrations into the furnace, such as
for electrical wiring.
13
Figure 8. *SA Horizontal Installation on a Platform
Gas Inlet
Wood or
non-combustible
Platform
Type “B” Vent
Coil Plenum
Electrical Supply
Connection
Figure 9. *SA Horizontally Suspended in Attic
Threaded
Rod
Lag
Bolt
Nuts (x2)
Washer
and
Lockwasher
Nuts (x2)
WARNING:
The downfl ow sub-base kit must not be installed
directly on carpeting, tile, or any combustible
material other than wood fl ooring.
A downfl ow sub-base kit is not necessary if the furnace
is installed on a factory or site-built cased air conditioning
coil. However, the plenum attached to the coil casing
must be installed so that its surfaces are at least 1” from
combustible construction.
Installation on a Concrete Slab
1. Create an opening in the fl oor according to the
dimensions in Figure 6.
2. Position the plenum and the furnace as shown in
Figure 7.
“A”
“B”
Opening in concrete floor
*SK Models Dim. “A” Dim. “B”
054-23A 13 1/4 19 1/4
072-24B 16 5/8 19 1/4
090-24B 16 5/8 19 1/4
108-35C 20 1/8 19 1/4
126-45D 23 5/8 19 1/4
NOTE: Dimensions shown in Inches.
Figure 6. Cutout Dimensions
If suspending the furnace from the ceiling, assemble a
support frame (Figure 9) using slotted iron channel and
full threaded rod. Fasten the frame together with nuts,
washers, and lockwashers. Secure the support frame to the
rafters with lag bolts. The furnace can also be suspended
using steel straps around each end of the furnace. The
straps should be attached to the furnace with sheet metal
screws and to the rafters with bolts.
It is recommended for further reduction of fi re hazard
that cement board or sheet metal be placed between the
furnace and the combustible fl oor and extend 12 inches
beyond the front of the door and top of the furnace.
Concrete
Floor
Furnace
Sheet
Metal
Plenum
Figure 7. Furnace on a Concrete Slab
Horizontal Installation
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
The *SA series gas furnace can be installed horizontally
(Figure 8) in an attic, basement, crawl space or alcove.
It can also be suspended from a ceiling in a basement
or utility room in either a right to left airfl ow or left to right
airfl ow as shown in Figure 9.
*SA series furnaces are shipped with the bottom panel
installed. If the furnace is installed horizontally, remove
the bottom panel from the furnace before attaching the
duct system. See Bottom Panel Removal on page 14.
If installing the furnace in an attic, it is required that a drip
pan be placed under the furnace. If the installation is on a
combustible platform (Figure 8), it is recommended that
the drip pan extend at least 12 inches past the top and
front of the furnace.
14
Figure 12. Alternate Removal Method
1
4
2
7
3
6
5
Alternate Bottom Panel Removal
If the bottom panel cannot be removed using the previous
instructions, the steps below are an alternate method for
removing the bottom panel. See Figure 12.
1. Remove the door (1) from the blower compartment .
2. Remove all screws securing the bottom panel (2) to
the front brace (3).
3. Remove two screws (4) securing the furnace cabinet
to the blower deck (5).
4. Remove all screws (6) securing the furnace cabinet
to the bottom panel (2).
5. Remove the screw (7) securing the bottom corner of
the furnace cabinet to the front brace (3).
6. Carefully spread the bottom corner of the furnace
cabinet outwards while sliding the bottom panel (2)
out through the front of the furnace.
7. Reassemble the furnace in reverse order.
Bottom Panel Removal
The steps listed below describe how to remove the bottom
panel from the furnace. See Figure 11.
1. Remove the door (1) from the blower compartment.
2. Disconnect the blower motor wiring harness (2) from
the control board.
3. Remove two screws (3) securing the blower assembly
(4) to the furnace.
4. Carefully pull the blower assembly (4) out thru the
front of the furnace.
5. Remove all screws (5) securing bottom panel (6) to
bottom of furnace and front brace (7).
6. Lift up and slide bottom panel (6) out through front of
furnace.
7. Reinstall the blower assembly (4) in reverse order.
6
7
5
1
2
3
4
Figure 11. Bottom Panel Removal
Pressure Switches
Figure 10 displays the proper routing
of pressure switch tubing for *SA &
*SK furnaces. On both furnaces, the
tubing connects at one end of the
pressure switch and is routed directly
onto the static tap of the inducer
assembly.
Figure 10. Pressure Switch Tubing for *SA & *SK Furnaces
15
All gas piping must be installed in compliance with
local codes and utility regulations. In the absence
of local codes the gas line installation must comply
with the latest edition of the National Fuel Gas Code
(ANSI Z223.1) or (CAN/CGA B149.1 or .2) Installation
Codes.
Some local regulations require the installation
of a manual main shut-off valve and ground joint
union external to the furnace as shown in Figure 13
(page 17). The shut-off valve should be readily
accessible for service and/or emergency use.
Consult the local utility or gas supplier for
additional requirements regarding placement of the
manual main gas shut-off.
• Gas piping must never run in or through air ducts,
chimneys, gas vents, or elevator shafts.
Compounds used on threaded joints of gas piping
must be resistant to the actions of LP propane gas.
• The main gas valve and main power disconnect to
the furnace must be properly labeled by the installer
in case emergency shutdown is required.
• Flexible gas connectors are not recommended for
this type of furnace but may be used if allowed by
local jurisdiction. Only new fl exible connectors
may be used. Do not use a connector which has
previously serviced another gas appliance.
A drip leg should be installed in the vertical pipe
run to the unit (Figure 13).
Table 7 (page 31) lists gas pipe capacities for standard
pipe sizes as a function of length in typical applications
based on nominal pressure drop in the line.
The furnace may be installed for either left or right side gas
entry. When connecting the gas supply, provide clearance
between the gas supply line and the entry hole in the
furnace casing to avoid unwanted noise and/or damage to
the furnace. Typical gas hookups are shown in Figure 13.
Leak Check
GAS SUPPLY & PIPING
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly
could result in serious injury or property
damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or
the gas supplier.
• Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fi re department.
WARNING:
RISQUE D’INCENDIE OU D’ EXPLOSION
Le non-respect des avertissements de sécurité
pourrait entraîner des blessures graves, la mort
ou des dommages matériels.
• L’installation et l’entretien doivent être effectués
par un installateur qualifié, un organisme de
service ou le fournisseur de gazstaller, service
agency or the gas supplier.
Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables dans le
voisinage de cet appareil, ni de tout autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
Appeler immédiatement le fournisseur de gaz en
employant le téléphone d’un voisin. Respecter à
la lettre les instructions du fournisseur de gaz.
Si personne ne répond, appeler le service des
incendies.
AVERTISSEMENT:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Never test for gas leaks with an open fl ame.
Use a commercially available soap solution
made specifi cally for the detection of leaks
to check all connections. A fi re or explosion
may result causing property damage, personal
injury or loss of life.
WARNING:
16
Installation Example
Elevation: .................................................. 5,000 feet
Type of Gas: ........................................... Natural Gas
Local Heating Value of Gas: .............................. 750
From Table 9, fi nd 750 and follow down the column,
stop at the 5,000 feet row. The heating value listed is
LOW. Table 11 will be used to determine orifi ce size and
manifold pressure.
After the gas piping to the furnace is complete, all
connections must be tested for gas leaks. This includes
pipe connections at the main gas valve, emergency shutoff
valve and fl exible gas connectors (if applicable). The soap
and water solution can be applied on each joint or union
using a small paintbrush. If any bubbling is observed,
the connection is not sealed adequately and must be
retightened. Repeat the tightening and soap check process
until bubbling ceases.
IMPORTANT NOTE: When pressure testing gas supply
lines at pressures greater than 1/2 psig (14 inch W.C.),
the gas supply piping system must be disconnected
from the furnace to prevent damage to the gas control
valve. If the test pressure is less than or equal to 1/2
psig (14 inch W.C.), close the manual shut-off valve.
High Altitude Application
High altitude conversion with this furnace depends on
the installation altitude and the heating value of the gas.
Installation of this furnace at altitudes above 2,000 feet
shall be in accordance with local codes, or in the absence
of local codes, the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 or National Standard of Canada, Natural Gas &
Propane Installation Code CGA B149.1. Please consult
your local code authority.
WARNING:
The reduction of input rating necessary for high
altitude installation may only be accomplished
with factory supplied orifi ces. Do not attempt to
drill out orifi ces in the fi eld. Improperly drilled
orifi ces may cause fi re, explosion, carbon
monoxide poisoning, personal injury or death.
The furnaces are shipped from the factory with orifi ces
and gas regulator settings for natural gas operation at sea
level altitudes. At 2000 feet, the NFGC requires that this
appliance be derated 4% for each 1,000 feet of altitude.
For example, at 2,000 feet the input needs to be reduced
8%, at 3,000 feet (12%), etc. This deration is in reference
to the input rate and gas heating value at sea level.
To derate the furnace requires knowing the heating value of
the gas at the installation site. Heating values at particular
job sites vary for two reasons:
1. The chemical mixture of the gas varies across regions
and is expressed as the “sea level heating value”.
2. The heating value varies by altitude. For this reason,
especially in high altitude areas, the local gas utility
specifi es the heating value at the residence’s gas
meter as the “local value”.
For added fl exibility, two tables have been provided for
natural gas installations with HIGH or LOW heating
values at sea level. Tables 10 and 11 (page 33) contain
the orifi ce sizes and manifold pressure to use at various
altitudes. Table 10 (High) is for natural gas installations
with a heating value of more than 1,000 Btu per cubic foot
and Table 11 (Low) is for less than 1,000 Btu per cubic
foot. To determine which table to use:
1. Consult the local utility for the local heating value at
your installation site.
2. From Table 9 (page 32), fi nd your local heating value
as supplied by the utility company. Follow down the
column and stop at your altitude level.
3. If your sea level heating value is HIGH, use Table 10
or if it’s LOW, use Table 11 (page 33).
After changing the regulator pressure or the orifi ces, it is
required that you measure the gas input rate. This may be
accomplished in the usual way, by clocking the gas meter
and using the local gas heating value. See Verifying and
Adjusting the Input Rate section (page 21).
NOTE: Observe the action of the burners to make sure
there is no yellowing, lifting or fl ashback of the fl ame.
RISQUE D’INDENDIE OU D’EXPLOSION
Le non-respect des avertissements de
sécurité pourrait d’entraîner des blessures
graves, la mort ou des dommages matériels.
Ne jamais utiliser une fl amme nue por vérifi er la
présence des fuites de gaz. Pour la vérifi cation
de tous les joints, utiliser plutôt une solution
savonneuse commerciale fabriquée spécifi quement
pur la détection des fuites de gaz. Un incendie ou
une explosion peut entraîner des dommages
matériels, des blessures ou la mort.
AVERTISSEMENT:
17
COMPONENTS:
(1) Automatic Gas Valve
(w/ manual shut-off)
(2) Burner Assembly (3) Dripleg (4) Elbow
(5) Ground Joint Union (6) Manifold (7) Plug (8) Shut - Off Valve
NOTE: Some utilities require Shut- Off Valve to be 4 - 5 feet above fl oor.
Figure 13. Typical Gas Connections
3
5
UPFLOW MODELS
DOWNFLOW MODELS
8
Right Side Entry
Left Side Entry
Right Side Entry
Left Side Entry
6
8
3
5
7
See
Note
See
Note
1
7
1
See
Note
4
1
RCYGW
STATUS
FLAME
180
COOL
HEAT
120
90
60
BLOWER
OFF
DELAY
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
24V
L1A
5
NEUTRALS
2
63
4
1
7
8
9
5
2
63
4
1
FAN
8
3
5
See
Note
RCYGW
STATUS
FLAME
180
COOL
HEAT
120
90
60
BLOWER
OFF
DELAY
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
24V
L1A
5
NEUTRALS
2
63
4
1
7
8
9
5
2
63
4
1
FAN
RCYGW
STATUS
FLAME
180
COOL
HEAT
120
90
60
BLOWER
OFF
DELAY
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
24V
L1A
5
NEUTRALS
2
63
4
1
7
8
9
5
2
63
4
1
FAN
2
6
2
1
RCYGW
STATUS
FLAME
180
COOL
HEAT
120
90
60
BLOWER
OFF
DELAY
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
24V
L1A
5
NEUTRALS
2
63
4
1
7
8
9
5
2
63
4
1
FAN
6
2
3
5
8
6
2
18
Conversion to LP / Propane
WARNING:
The furnace was shipped from the factory
equipped to operate on natural gas. Conversion
to LP / Propane gas must be performed by
qualifi ed service personnel using a factory
supplied conversion kit. Failure to use the
proper conversion kit can cause fi re, explosion,
property damage, carbon monoxide poisoning,
personal injury, or death.
Conversion to LP / Propane is detailed in the installation
instructions provided with the conversion kit. Generally,
this will require the replacement of the burner orifi ces and
the spring found under the cap screw on the pressure
regulator. In the U.S. if installation is above 2,000 ft., refer
to Table 8 (page 32) to determine the correct orifi ce size
and manifold pressure. See example below.
Electrical connections must be in compliance with all
applicable local codes and the current revision of the
National Electric Code (ANSI/NFPA 70).
For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
IMPORTANT NOTE: If replacing any of the original
wires supplied with the furnace, the replacement wire
must be copper wiring and have a temperature rating
of at least 105° F (40° C). For electrical specifi cations,
refer to the furnace nameplate or Table 2 (page 19).
ELECTRICAL WIRING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
power to furnace.
When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.”
WARNING:
RISQUE DE CHOC ÉLECTRIQUE, D’INCENDIE
OU D’EXPLOSION
Le non-respect des avertissements de sécurité
pourrait entraîner
un fonctionnement dangereux
de l’appareil,
des blessures graves, la mort ou des
dommages matériels.
Un entretein incorrect pourrait entraîner un
fonctionnement dangereux de l’appareil, des
blessures graves, la mort ou des dommages
matériels
• Couper toute alimentation électrique au
générateur d’air chaud avant de prodéder
aux travaux d’entretein.
• Au moment de l’entretien des commandes,
étiquetez tous les fi ls avant de les débrancher.
S’assurer de les raccorder correctement.
• S’assurer que l’appareil fonctionne
adéquatement aprés l’entretien.
AVERTISSEMENT:
Installation Example
Elevation: .................................................. 5,000 feet
Type of Gas: ......................................... Propane Gas
Input BTUH of Furnace: ................................72,000
From Table 8 , fi nd 5,000 and follow across the row, stop
at the 72,000 feet column. The manifold pressure listed
is 10.0 and the orifi ce size is 57.
When conversion is complete, verify the manifold pressure
and input rate are correct as listed in the Tables. Approved
conversion kits are listed below:
The United States LP / Propane Gas Sea Level and
High Altitude Conversion Kit (P/N 904914) is for LP /
Propane conversion in the United States at altitudes
between zero and 10,000 ft. above sea level. Please
follow the instructions provided with the kit.
The Canadian LP / Propane Gas Sea Level and
High Altitude Conversion Kit (P/N 904915) is for LP /
Propane conversions in Canada at altitudes between
zero and 4,500 ft. above sea level. Please follow the
instructions provided with the kit.
19
to the black wire. The furnace will not operate unless
the polarity and ground are properly connected as
shown in Figure 14.
Grounding
WARNING:
To minimize personal injury, the furnace cabinet
must have an uninterrupted or unbroken
electrical ground. The controls used in this
furnace require an earth ground to operate
properly. Acceptable methods include electrical
wire or conduit approved for ground service.
Do not use gas piping as an electrical ground!
Line Voltage Wiring
It is recommended that the line voltage (115 VAC) to
the furnace be supplied from a dedicated branch circuit
containing the correct fuse or circuit breaker for the
furnace (Table 2).
IMPORTANT NOTES:
An electrical disconnect must be installed readily
accessible from and located within sight of the furnace.
See Figure 14 or the wiring diagram label inside of
the control door. Any other wiring methods must be
acceptable to authority having jurisdiction.
Proper line voltage polarity must be maintained in
order for the control system to operate correctly.
Verify the incoming neutral line is connected to the
white wire and the incoming “hot” line is connected
Furnace
Model
*SA/*SK
Furnace
Input
(Btuh)
Cabinet
Width
(in.)
Nominal
Electrical
Supply
Maximum
Operating
Voltage
Minimum
Operating
Voltage
Maximum
Furnace
Amperes
Minimum
Wire
Gauge
Maximum
Fuse or Circuit
Breaker Amps*
045C-23A 45,000 14 1/4 115-60-1 127 103 6.3 14 15
054C-23A 54,000 14 1/4 115-60-1 127 103 6.3 14 15
072C-24B 72,000 17 1/2 115-60-1 127 103 9.7 14 20
072C-35C 72,000 21 115-60-1 127 103 9.0 14 15
090C-24B 90,000 17 1/2 115-60-1 127 103 9.7 14 20
090C-35C 90,000 21 115-60-1 127 103 9.0 14 15
108C-35C 108,000 21 115-60-1 127 103 9.0 14 15
126C-45D 126,000 24 1/2 115-60-1 127 103 15.2 12 30
Thermostat Wire Gauge
Recommended Thermostat Wire Length
2 - wire - Heating 4 or 5 wire - Cooling
24 55 ft. 25 ft.
22 90 ft. 45 ft.
20 140 ft. 70 ft.
18 225 ft. 110 ft.
*
Time-delay fuses or circuit breakers are required.
Table 2. Wire Length & Voltage Specifi cations
Figure 14. Line Voltage Field Wiring
Field Supplied
Disconnect w/in
Sight of Furnace
Field Supplied
Panel Connector
Field Supplied
Fused Service
Panel
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Black
White
Black
White
Black
White
Field Line Voltage Wiring
Factory Line Voltage Wiring
Ground
Ground
Junction Box (may be int. or ext.
to the furnace). These connections
can be made in the field supplied
disconnect at the furnace.
Ground
20
Figure 15. Low Voltage Field, Four-wire
Heating/Cooling Applications
RCYGW
STATUS
FLAME
GREEN
RED
180
COOL
HEAT
120
90
60
YELLOW
BLOWER
OFF
DELAY
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
COM
SPEED
SELECT
3 AMP
FUSE
24V
5
NEUTRALS
ROOM
THERMOSTAT
A/C CONDENSING UNIT
CONDENSING UNIT
CONTROL BOX
EXPANSION PORT
(MOTOR CONNECTION)
FIELD WIRING
LOW VOLTAGE
CONNECTION
R
C
Y
G
W
NOTE: The “Y” terminal
on the control board
must be connected to the
thermostat for proper
cooling mode operation.
Connect
R & W
For Heating
Only
2
ELECTRONIC AIR CLEANER
MOTOR SPEED TAPS
(NOT USED)
HUMIDIFIER TAP
NEUTRAL LEADS
6
3
4
1
7
8
9
5
2
63
4
1
FAN
Thermostat / Low Voltage Connections
• The furnace is designed to be controleed by a 24 VAC
thermostat. The thermostat’s wiring must comply with
the current provisions of the NEC (ANSI/NFPA 70) and
with applicable local codes having jurisdiction.
The thermostat must be installed according to the
instructions supplied by the thermostat manufacturer.
Low voltage connections (24 VAC) from the thermostat
are wired to the terminal strip on the integrated control in
the furnace. Figure 15 contains the proper connections
for heating only (two-wire) and heating/cooling (four-
wire) applications. Recommended minimum wire gauge
for thermostat wiring is shown in Table 2 (page 19).
The thermostat should be mounted about 5 feet
above the fl oor on an inside wall. DO NOT install the
thermostat on an outside wall or any other location
where its operation may be adversely affected by radiant
heat from fi replaces, sunlight, or lighting fi xtures, and
convective heat from warm air registers or electrical
appliances. Refer to the thermostat manufacturer’s
instruction sheet for detailed mounting information.
The six pin terminal marked “Expansion Port” (Figure
15) is not used in the single stage furnace as shipped
from the factory. It is used for the furnace control board
to communicate to a fi xed speed or variable speed high
effi ciency motor that may be optionally installed. Please
contact your distributor for the proper upgrade motor
kit.
Heat Anticipator
Set the heat anticipator according to the instructions
supplied by the thermostat manufacturer. To determine
the heat anticipator setting:
1. Add the current draw of the system components; or
2. Measure the current fl ow on the thermostat R-W circuit
after the circulating blower motor has started.
Twinning
Single stage furnaces are not supplied with a built-
in twinning capability. Other valuable features and
enhancements were made to the new control that made it
necessary to remove the twinning capability. For twinning
of single stage furnaces with PSC motors, a twinning kit
(920919) is available for purchase. Please follow the
instructions provided with the kit.
If both single stage furnaces are upgraded to the fi xed
speed iSEER ™ blower, the twin terminal on the blower
control boards (Figure 16) may be used to twin the single
stage furnaces only if the following criteria are met:
• Both furnaces and motors must be the same size.
Both motors must be on the same speed for cooling
and heating.
Both furnaces must have a common return duct and
common supply plenum.
Both furnaces must be the same phase and on the
same leg of power.
IMPORTANT NOTE: Furnaces equipped with variable
speed iSEER ™ motors may not be twinned under
any circumstances.
WARNING:
When servicing either twinned furnace, power
must be turned off on both furnaces. Failure to
comply may result in improper operation leading
to damage to the furnaces or personal injury!
For twinning of single stage furnaces equipped with
xed speed iSEER ™ blowers, refer to Figure 16 and the
following instructions:
1. Turn off all power to both furnaces.
2. Attach a wire between the two twin terminals on the
twinning control boards. Use fi eld supplied wire and
two 3/16” wire terminals.
FURNACE
W
G
Y
C
R
THERMOSTAT
WG
YR
A/C
FSHE
TWIN TERMINAL
BOARD
UNIT
BOARD
FURNACE
BOARD
FSHE
TWIN TERMINAL
BOARD
FURNACE 1 FURNACE 2
W
G
Y
C
R
Figure 16. Single Stage Twinning
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Unbranded FG7S(A,K) Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI