Omega LVCN-51 Series Owner's manual

Category
Security access control systems
Type
Owner's manual
1
2
3
INTRODUCTION/TABLEOFCONTENTS StepOne
The LVCN51 Series Continuous Relay Controller is a generalpurpose level controller which provides single
tank level indication with dual relays and a repeater 420 mA output.The LVCN51 Series features both a
single 10A SPDT and a single 10A Latching SPDT relay.This package allows for a system that can perform
automaticoperations(fillorempty)andanalarmoperation(high or low).The LVCN51Seriescanalsobea
controller that can perform dual alarms (2high, 2low or 1high, 1low).Package the controller with a
transmitterthatprovidesa420mAoutputandanenclosuretoprotectthecontrollerfromtheelements.
Features
3.5digitLEDdisplayindicateslevelincustomerengineeringunits.
FailSaferelaycontrolofpumps,valvesoralarmswitha0to60seconddelay.
PolypropyleneenclosurecanbeDINrailmountedorbackpanelmounted.
Easysetupwithpushbuttoncalibrationfordisplayandrela
ysettings.
ACpowered
TableofContents
Specifications:.........................................................................................................................................................3
Dimensions:.............................................................................................................................................................3
SafetyPrecautions:.................................................................................................................................................4
MakeaFailSafeSystem:............................................................................................................................5
Components:...............................................................................................................................................5
Installation:............................................................................................................................................................5
GettingStarted:.......................................................................................................................................................6
FeaturesoftheSingleInputHighorLowAlarmRelay:..............................................................................6
FeaturesoftheLatchingRelay(AutomaticFillorEmpty):.........................................................................6
GuidetoControls:.......................................................................................................................................7
Electrical:.................................................................................................................................................................8
WiringtoInputTerminals:.........................................................................................................................8
SettingInputPolarity:.................................................................................................................................9
RepeaterOutput:........................................................................................................................................9
VACPowerInputWiring:.........................................................................................................................10
Changingfrom120to240VAC:...............................................................................................................10
RelayInputWiring:...............................................................................................................................
....10
ApplicationExmaples:...........................................................................................................................................11
LowLevelAlarm:.......................................................................................................................................11
HighLevelAlarm:......................................................................................................................................11
AutomaticFill:...........................................................................................................................................12
AutomaticEmpty:.....................................................................................................................................12
Programming:......................................................................................................................................................13
Appendix:..............................................................................................................................................................14
ControllerLogic:........................................................................................................................................14
RelayLatchingLogicTab
le:.......................................................................................................................14
FactoryReset:...........................................................................................................................................14
LockoutFunction:.....................................................................................................................................16
Troubleshooting:.......................................................................................................................................15
Exercise:...............................................................................................................................................................16
4
SPECIFICATIONS/DIMENSIONS StepTwo
Displaytype: LED,3.5digit
Displayunits: Engineering
Displayoutput: 0to999or0.0to199.9
LEDindicators: Powerandrelaystatus
Bargraphdisplay: 420mAwithsetpoints
Configuration: Pushbutton
Alarmindication: Amber:<4mA
Red:>20mA
Security: Lockoutmode
Sensorinput: (1)420mAtransmitter
Supplyvoltage: Selectable120VAC/240VAC
50‐60Hz.
Consumption: 5Wattmaximum
Sensorsupply: 24VDC@1.5Watts
Looppower: 420mA,18VDC
Contacttype: (1)SPDT
(1)LatchedSPDT
Contactrating: 250VAC,10A
Contactoutput: Selectable,NOorNC
Contactlatch: ONorOFF
Contactconfiguration: 1:Highorlowlevelalarm
2:Highandlowlevelalarm
3:Automaticfillorempty
4:Automaticfilloremptywithalarm
Contactdelay: 060seconds
Failsafety: Powerfailsafe
Repeateroutput: 420mA,1236VDC
Ambienttemperature: F:‐40°to158°
C:‐40°to70°
Enclosuretype: 35mmDIN(EN50022)
Enclosurematerial: Polypropylene
(U.L.94VO)
CECompliance: EN500822immunity
EN55011emission
EN610101Safety
TopView‐AllModels
SideView‐AllModels
InternalControllerLogic

5
SAFETYPRECAUTIONS StepThree
AboutThisManual:PLEASEREADTHEENTIREMANUALPRIORTOINSTALLINGORUSINGTHISPRODUCT.
ThismanualincludesinformationonthecontinuousrelaycontrollerfromOMEGAENGINEERING:LVCN51
series.
User’s Responsibility for Safety:OMEGAENGINEERING manufactures several models of controller,with
differentmountingandswitchingconfigurations.Itistheuser’sresponsibilitytoselectacontrollermodel
that is appropriate for the application, install it properly, perform tests of the installed system, and
maintainallcomponents.
Electrical Shock Hazard:It is possible to contact components on the controller that carry high voltage,
causing seriousinjury or death.All power to the controllerand the relay circuit(s) it controls should be
turned OFF prior to working on the controller.If it is necessary to make adjustments during powered
operation,useextremecautionanduseonlyinsulatedtools.Makingadjustmentstopoweredcontrollers
isnotrecommended.Wiringshouldbeperformedbyqualifiedpersonnelinaccordancewithallapplicable
national,stateandlocalelectricalcodes.
FlammableorExplosiveApplications:TheLVCN51Seriescontinuousrelaycontrollersshouldnotbeused
withexplosiveorflammableliquids,whichrequireanintrinsicallysafeorexplosionproofrating.Ifyouare
unsure of the suitability of a controller for your installation, consult your Omega Engineering
representativeforfurtherinformation.
InstallInaDryLocation:Thecontrollerhousingisnotdesignedtobeimmersed.Wheninstalledproperly,
itshouldbemountedinsuchawaythat it doesnot normallycomeintocontact with liquid.Refertoan
industryreferencetoensure thatcompoundsthatmaysplashontothecontrollerhousingwill notdamage
it.Suchdamageisnotcoveredbythewarranty.
RelayContactRating:Therelayisratedfora10ampresistiveload.Manyloads(suchasamotorduring
startuporincandescentlights)arereactiveandmayhaveaninrushcurrentcharacteristicthatmaybe10
to 20 times their steadystate load rating.The use of a contact protection circuit may be necessary for
yourinstallationifthe10ampratingdoesnotprovideanamplemarginforsuchinrushcurrents.Incritical
applications,redundantbackupsystemsandalarmsmustbeusedinadditiontotheprimarysystem.Such
backupsystemsshouldusedifferentsensortechnologieswherepossible.
6
SAFETYPRECAUTIONS/INSTALLATION StepThree
Make a FailSafe System: Design a failsafe system that accommodates the possibility of relay or power
failure.If power is cut off to the controller, it will deenergize the relay.Make sure that the deenergized
stateoftherelayisthesafestateinyourprocess.Forexample,ifcontrollerpowerislost,apumpfillingatank
willturnoffifitisconnectedtotheNormallyOpensideoftherelay.
While the internal relay is reliable, over the course of time relay failure is possible in two modes: under a
heavyloadthecontactsmaybe“welded”orstuckintotheenergizedposition, orcorrosionmaybuildupona
contact so that it will not complete the circuit when it should.In critical applications, redundant backup
systems and alarms must be used in addition to the primary system.Such backup systems should use
differentsensortechnologieswherepossible.
While this manual offers some examples and suggestions to help explain the operation of OMEGA
ENGINEERINGproducts,suchexamplesareforinformationonlyandarenotintendedasacompleteguideto
installinganyspecificsystem.
Components:
LVCN51 ‐Singleinputwithdualrelays,3.5digitLEDdisplayandrepeateroutput.
LVCN51CE ‐Singleinputwithdualrelays,3.5digitLEDdisplayandrepeateroutputwithCEapproval.
Owner’sManual
PanelDIN Rail Mounting:The controllermay bemountedby either a back panelusing two screws through
mountingholeslocatedatthecornersofthecontrollerorbysnappingthecontrolleron35mmDINRail.

Note:Alwaysinstallthecontrollerinalocationwhereitdoesnotcomeintocontactwithliquid.

7
GETTINGSTARTED StepFour
FeaturesofaSingleInputHighorLowRelay:SingleInputRelays(Relay1orRelay2w/latchturnedOFF)are
designedtoswitchfromasinglesetpoint.ItturnsitsinternalrelayONorOFF(assetbytheinvertswitch)in
responsetothepresenceofliquid,andchangestherelaystatusbackagainwhenthesensorisdry.
High Alarm:Invert is OFF.
Relay will energize when the
levelrisesabovethehighalarm
setting and will deenergize
when it drops below the high
alarmsetting.
LowAlarm:InvertisON.Relay
will energize when the level
drops below the low alarm
setting and will deenergize
when it rises above the low
alarmsetting.
Singleinputhighorlowrelaysmaybeusedwithanydevicethatoutputsa420mAsignal.Therelayisasingle
pole, double throw type; the controlled device can be connected to either the normally open or normally
closedsideoftherelay.Atimedelayfrom0to60secondscanbesetbeforetherelayrespondstothesensor
input.Typicalapplicationsforsingleinputrelaysarehighlevelorlowlevelswitch/alarmoperations (opening
a drain valve whenever liquid level rises to a setpoint) and overflow protection (turning off a pump or
soundinganalarmwhenahighlevelisreached).
FeaturesofaLatchingRelay(automaticfillorempty):Thelatchingrelay(relay2only)isdesignedtoswitcha
relay on and off at two different levels.It turns its internal relay ON or OFF (as set by the invert switch) in
responsewhenthelevelisabovethehighsettingorbelowthelowsetting.Therelaywillnotchangeitsstate
whenthelevelisbetweenthehighandlowsetting.
AutomaticEmpty:
Latch is ON & Invert is OFF.Relay
will energize when level reaches
high setting (both settings are
submersed).Relaywilldeenergize
when level is below the bottom
setting(bothsettingsaredry).
AutomaticEmpty:
Latch is ON & Invert is ON.Relay
will energize when level is below
the bottom setting (both switches
are dry).Relay will deenergize
when level is above the high
setting(bothsettingsarewet).

8
GETTINGSTARTED(continued) StepFour
The Latching Relay (Automatic Fill/Empty) may be used with any device that outputs a 420 mA signal.The
relayisasingle pole,doublethrowtype;thecontrolleddevicecanbeconnectedtoeitherthenormallyopen
ornormallyclosedsideoftherelay.TypicalapplicationsforLatchingRelaysareautomaticfilling(startingfill
pump at a low level and stopping pump at a high level) or automatic emptying operations (opening a drain
valveatahighlevelandclosingvalveatlowlevel).
GuidetoControls:Belowisalistingandthelocationofthedifferentcomponentsforthecontroller:
1. Powerindicator:ThisGreenLEDlightswhenACpowerisON.
2. Relay indicator:This Red LED will light whenever the controller energizes the relay, in response to the
transmitterinputandafterthetimedelay.
3. ACPowerterminals:Connectionof120VACpowertothecontroller.Thesettingmaybechangedto240
VAC if desired.This requires changing internal jumpers; this is covered in the Installation section of the
manual.Polarity(neutralandhot)doesnotmatter.
4. Relay terminals (NC, C, NO):Connect the device you wish to control (pump, alarm etc.) to these
terminals: supply to the COM terminal, and the device to the NO or NC terminal as required.The
switcheddeviceshouldbe anoninductiveloadof notmorethan10 amps;forreactiveloadsthecurrent
must be derated or protection circuits used.When the red LED is ON and the relay is in the energized
state,theNOterminalwillbeclosedandtheNCterminalwillbeopen.
5. Invertswitch:Thisswitchreversesthelogicoftherelaycontrolinresponsetotheswitch(es):conditions
thatusedtoenergizetherelaywillnowdeenergizetherelayandviceversa.
6. Timedelay:Setsdelayfrom0to60
seconds.HoldDelaybuttontoincreasedelayin5secondincrements.
7. Digitaldisplay:Showsthecurrent420mAsignalinengineeringunits.
8. Input terminals:Connect the transmitter wires to these terminals:A 24 VDC power is provided for
currentloopwithanadditional28VDCpowerterminalifrequired.
9. Latchswitch(relay2):Thisswitchdetermineshowtherelaywillbeenergizedinresponsetothetwoset
points.WhenLATCHisOFF,therelayrespondstosetpointRLY2Aonly;whenLATCHisON,therelaywill
energiz
eordeenergizeonlywhenbothsetpoints(RLY2AandRLY2B)areinthesamecondition(bothwet
orbothdry).Therelaywillremainlatcheduntilbothsetpointschangeconditions.
10. BarGraph:Displays420mAsignalasapercentageoftherange.
11. OP/SET:Usedtoscrollbetweensetpointsdurin
gprogramming.
12. 20/Down:UsedtodecreasedisplayvalueduringprogrammingandforEasyCal™Spansetup.
13. 4/Up:UsedtoincreasedisplayvalueduringprogrammingandforEasyCal™Offsetsetup.
14. RepeaterOutput:Isolatedterminalwhichreproducestheinput 420mAsignal.Terminalrequires12
36
VDCpowerforoperation.
9
ELECTRICAL StepFive
WiringtoInputTerminals:Signalinputisalwaysthroughthe24VDCterminal.The28VDC
terminal is used as an alternative power supply for threewire devices.Please note a
difference between 2wire and 3wire level transmitters and sourcing and sinking modes
below.Below is a quick review of wiring the LVCN51 Series to common 420 mA
transmitters.
LVCN2700Series(LVU2710,LUV2718,LVU2726&
LVU2732)&LVCN414Series(LVCN414,LNCV414
I,LVCN210&LVCN318)
Sourcingmode(FactorySetting)
LVU800Series(LVU809,LVU816,LVU826&
LVU832)
SourcingMode(FactorySetting)

LVU300Series(LVU301only)
SourcingMode(FactorySetting)
LVU300Series(LVU303only)
Sinkingmode(internaljumpermustbechanged)

UltrasonicLevelTransmitter(IntrinsicallySafe)(LVU201Aonly)
Sinkingmode(internaljumpermustbechanged)

10
ELECTRICAL(continued) StepFive
Setting Input Polarity (Sourcing vs. Sinking modes):The LVCN51 Series can be set in one of two modes,
sourcingandsinking.TheLVCN51Seriesisshippedfromthefactoryinthesourcingmode.Thisiscompa tible
withanylooppoweredtransmittersuchastheLVCN2700Series(LVU2710,LUV2718,LVU2726&LVU2732),
LVU800 Series (LVU809, LVU816, LVU826 & LVU832), LVCN414 Series (LVCN414, LNCV414I, LVCN210 &
LVCN318)andthethreewireUltrasonicLVU300Series(LVU301only)withnoadjustmentrequired.Ifusing
aLVU300Series(LVU303only)orUltrasonic Level Transmitter (Intrinsically Safe)(LVU201Aonly),follow
theinstructionsbelow.
1. Removethebackpanelofthecontrollerandgentlyslidetheprinted
circuit
board(PCB)fromthehousing.UsecautionwhenremovingthePCB.
2. LocatejumpersJWAandJWBonthePCB.
3. Tochangefromsourcingtosinking,removejumperfromJWAandplaceon
JWB.TheLVCN51
Seriesisshippedfromthefactoryinthesourcingmode
(JWAactive).
4. GentlyreturnPCBintohousingandreplacebackpanel.
Note:Looppowereddevicescanoperateineitherthesouringorsinkingmodes.
SourcingMode
SinkingMode
NoChange
Required
LVCN2700Series(LVU2710,LUV2718,LVU2726&LVU2732),LVU800
Series(LVU809,LVU816,LVU826&LVU832),LVCN414Series
(LVCN414,LNCV414I,LVCN210&LVCN318)andthethreewire
UltrasonicLVU300Series(LVU301only)
Sinkingor
Loop
Devices
Change
Required
LVU300Series(LVU303only)or
UltrasonicLevelTransmitter(IntrinsicallySafe)(LVU201Aonly)
Sourcing
Devices
RepeaterOutput:Theisolatedrepeateroutputreproducesthe
input420mAcurrentsignal.Thissignalcanberepeatedtoany
other device that accepts a 420 mA input, such as a PLC, DCS,
SCADA, chart recorder or another display.The repeated 420
mAsignalisnotanexcitedoutput.Anexternalpowersupplyis
required and should not exceed a maximum of 36 VDC.See
the wiring diagram to the right for instructions in wiri ng all
threecomponents(repeateroutput,powersupplyandthenew
device)inserieswitheachother.

11
ELECTRICAL(continued) StepFive
VACPowerInputWiri ng:ObservethePOWERSUPPLYlabel on the LVCN51Series. Thelabel identifies the
power requirement (120 or 240 VAC) and the terminal wiring.Note: Polarity does not matter with the AC
inputterminal.
Changing from 120 to 240 VAC:The LVCN51 Series is shipped from the factory configured as a 120 VAC
powereddevice.
Toswitchto240VAC,followtheinstructionsbelow.
1. Remove the back panel of the controller and gently slide the printed
circuitboard (PCB)fromthehousing.Usecautionwhen removing the
PCB.
2. LocatejumpersJWAandJWBonthePCB.
3. To change from sourcing to sinking, remove jumper from
JWA and
place on JWB.The LVCN51 SERIES is shipped fromthe factory in the
sourcingmode(JWAactive).
4. GentlyreturnPCBintohousingandreplacebackpanel.
120VACJumperSetting
240VACJumperSetting
RelayInputWiring:Therelayisasinglepole,double
throwtyperatedat250VoltsAC,10Amps.Thetwo
terminal NO and NC (normally open and normally
closed) will be used in different applications.
Remember that the "normal" state is when the relay
coilisdeenergizedandtheRedre
layLEDisOff/de
energized.

12
APPLICATIONEXAMPLES StepSeven
LowLevelAlarm:Thegoalistomakesurethattheliquidleveldoesnotfallbelowacertainpoint.Ifitdoes,
analarmissupposedtosound,alertingtheoperatorofalowlevelcondition.
Ifpowerisaccidentallycuttothecontroller,thesensor'sabilitytonotifytheoperatorofalowlevelcondition
couldbelost.Thesystemmustalerttheoperatornotonlytolowliquidlevel,buttocontrollerpowerloss.
To do this, connect the hot lead of the alarm to the NC side of the relay
terminalofthecontroller.Ifpowerislost,therelaywillbedeenergized,and
the alarm will sound (if there is still power to the alarm circuit itself).The
alarm circuit should have a noninterruptible power supply or some other
indicatororbackupalarmtowarnofapowerfailureinthealarmcircuit.
In this application, the normal status of the sensor at the bottom if the tank
will be wet, and the relay will be energized holding the alarm circuit open.
Both the relay LED and the Input LED will be on simultaneously, so for this
application,InvertshouldbesettotheOFFposition.
HighLevelAlarm:Inthesamemanor,thissystemcanbeusedtosoundanalarmwhenfluidreachesahigh
level, with just a change in the location of the sensor and the setting of the
Invertswitch.
The alarm is still connected to the NC side of the relay to allow for a power
failurealarm.
The sensor is normally dry.In this condition, we want the relay to be
energized so the alarm does not sound: i.e., the Red relay LED should be on
whenevertheInputLEDisAmber.SoweturnInvertOn.Ifthefluidlevelrises
tothehigh sensor point, thesensorgoeson,therelaydeenergizes,and the
alarmsounds.

13
APPLICATIONEXAMPLES(cont.) StepSeven
Automatic Fill:This system consists of a tank with a valve controller by the
LVCN51 Series.At a low set point, the valve opens, filling the tank.At the
high set point, the valve closes.Part of a proper failsafe design for this
particularsystemis that if powerislost to thecontroller for any reason,the
valvefillingthe tank must close.Therefore, we connect the valvetotheNO
sideoftherelay.Whentherelayisenergized,thevalvewillopenandfillthe
tank.TherelayindicatorwillcorresponddirectlytotheOpen/Closestatusof
thevalve.
NOTE: If the device’s load exceeds the rating of the controller’s relay, a
stepperrelayofhighercapacitymustbeusedaspartofthesystemdesign.
DeterminingthesettingsofLATCHandINVERT:Thisisthewaythesystemmustoperate:
Whentheliquidlevelisbelowthelowsetpoint,thevalveshouldopen,startingtofillthetank.
Whentheliquidisabovethelowsetpoint,thevalvewillremainopen.
Whentheliquidreachesthehighsetpoint,thevalveshouldclose.
Latch:Inanytwosensorcontrolsystem,LATCHmustbeON.
Invert:ReferringtothelogicchartinStepNine,welookforthesettingthatwilldeenergizetherelay(valve
close)whenbothinputsarewet.Inthissystem,InvertshouldbeON.
AutomaticEmpty:Inthesamemanner,thecontrollercanbeusedtoautomaticallyemptyatankwithjusta
changetothesettingoftheINVERTswitch:
ThevalveisstillconnectedtotheNOsideoftherelaytoallowforapowerfailurefailsafecondition.
Thenormalstateofthevalveisclosed.Inthisstate,wewanttherelaytobeenergizedatthehighset
point(openingvalvetodraintank).Therelaywilldeenergizeatthelowsetpoint(closingvalve).
Note:Afailsafedesignisimportant.Ifthetankisbeingpassivelyfilled,andavalvemustbe usedtoactively
emptyit,apowerfailuretoeitherthecontrollerorthepumpcircuitswillcauseoverflow.

14
PROGRAMMING StepEight
OFFSET:Equivalenttothe4mAsetpointonthetransmitter.Enterthevalueyouwouldliketoseewhenthe
LVCN51Seriesreceives4mA.
SPAN:Equivalenttothe20mAsetpointonthetransmitter.Enterthevalueyouwouldliketoseewhenthe
LVCN51Seriesreceives20mA.
RLY1,RLY2A,RLY2B:Setpoints
forRelays.ValuesmustbebetweenOFFSETandSPAN.
Settingvalues:WiththeLatchOff,ignoresteps9and10.RLY2Bwillnotshowduringtheprogramming
sectionwithLatchOff.
1. PresstheSETbuttononce.Immediately,theLEDbargraphwillbegintoflashone
Greenbarnex
ttoOFFSET.
2. UseUP/DWNbuttonstochangedisplaytothedesiredOFFSETvalue.
3. PresstheSETbuttonagain.Immediately,theLEDbargraphwilljumponeGreenbarto
therightnexttoSPAN.
4. UseUP/DWNbuttonstochangedisplaytothedesiredSPANvalue.
5. PresstheSETbuttonagain.Immediately,theLEDbargraphwilljumponeGreenbarto
therightnexttoRLY1.
6. UseUP/DWNbuttonstochangedisplaytothedesiredRLY1value.
7. PresstheSETbuttonagain.Immediately,theLEDbargraphwilljumponeGreenbarto
therightnexttoRLY2A.
8. UseUP/DWNbuttonstochangedisplaytothedesiredRLY2Avalue.
9. PresstheSETbuttonagain.Immediately,theLEDbargraphwilljumponeGreenbarto
therightnexttoRLY2B.
10. UseUP/DWNbuttonstochangedisplaytothedesiredRLY2Bvalue.
11. PresstheSETbuttonagain.Immediately,theLEDbargraphwillreturnbacktoit
normaloperationofsolidbars.
EasyCalCalibration:TheOffsetandSpanpoints may be programmed directlytoaspecificleve
linthetank.
These are the EasyCal 4 (Empty tank) and EasyCal 20 (Full tank) values.Note: the level of the tank must
physicallybeatitsdesiredlevelwhenusingEasyCal.Ifnot,theEasyCalwillacceptthelevelandthevalueson
thedisplaywillbeincorrect.Usethefactoryresettostartoverifthisoccurs.
To calibrate EC4, set the tank to the new Offset level.Press [4]
buttononceand[E]willappearinthedisplay.Press[4]buttonagain
and[C]willappearinthedisplayandEC4isset.
To calibrate EC20, set the tank to the new Span level. Pr
ess [20]
buttononceand[E]willappearinthedisplay.Press[20]buttonagain
and[C]willappearinthedisplayandEC20isset.

15
APPENDIX StepNine
ControllerLogic:Pleaseusethefollowingguidetounderstandtheoperationofthecontrollers.
1. PowerLED:MakesuretheGreenpowerLEDisONwhenpowerissuppliedtothecontroller.
2. BarGraphLED:ThebargraphLEDonthecontrollerwillalwaysindicate the proportional 420mAinput
signalgoingtotheLVCN51Seriescontroller.i.e.:ifthetankis25%full,then25%ofthebargraphwill be
litGreen.IfasingleAmberbarappears,thisindicatesaninputcurrentoflessthan4mA.IfasingleRed
LED appears, this indicates an input current greater than 20 mA.Use this feature to confirm the input
signalfortheLVCN51Series.
3. RelayLEDs:Thenormalstateofthe relayiswhentheLEDisOFF.Whentherelaybecomesenergized,the
RedLEDwilllight.Ifpowerisremovedfromthecontroller,therelaywillreturntothenormalstate(LED
OFF).
4. Display:Willindicatetheproportionalleveloftheliquidbaseduponthe420mAinput.IfEasyCalisused
foreithertheemptytanklevel,fulltanklevelorboth,thedisplaywillignorethe420mAinputsignaland
usetheEasyCalsettingasitsemptyand/orfullposition.
RelayLatchLogicTable(relay2only):
Therelaycaneitherbeanindependentrelay(highorlowlevelalarm)
orcanbealatchingrelay(automaticfillorempty)withlatchON.WithLatchOFF,therelaywillonlyrespond
totheRLY2Asetting.RLY2Bwillbeignored.
WithLatchOFF,thesettingforRLY
2Bwill be ignored.
Allchanges to
the relay’s state will occur from
theRLY2Asetting.
InvertOFF LatchOFF
RLY2A RLY2B Relay
ON
OFF
NoEffect
NoEffect
ON
OFF
InvertON LatchOFF
RLY2A RLY2B Relay
ON
OFF
NoEffect
NoEffect
OFF
ON
With Latch ON, the relay will
actuate when the level is above
RLY2AandRLY2B.Therelaywill
not change its condition if the
level is between RLY 2A and RLY
2B.Therelaywillreverseitsstate
when the level is below both RLY
2AandRLY2Bsettings.
InvertOFF LatchON
RLY2A RLY2B Relay
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
NoChange
NoChange
OFF
InvertON LatchON
RLY2A RLY2B Relay
ON
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
NoChange
NoChange
ON
Factory Reset:Returns the LVCN51 Series to its original factory settings,
includingsettingtheOFFSET to 4 mA and theSPANto20mA.Toperforma
FactoryReset,firstremovepowertothecontroller.Holdboththe4/UPand
20/DWN buttons while adding power to the LVCN51 Series.An “F” for
Factory Reset will appear in the display indication the Factory Reset was
achieved.If an “E” for Error appears, the Factory Reset was not performed
and you will need to try again.Note: make sure both buttons are pressed
whileaddingpower.The“E”willappearifonlyoneofthebuttonsispressed.
Factory
SettingsforLVCN51Series
OFFSET SPAN RLY1 RLY2A RLY2B
4.0 20.0 6.0 18.0 8.0

16
APPENDIX(continued) StepNine
LockOutFunction:ThebuttonsonthefaceoftheLVCN51Seriescanbedisengagedorlockedout.To
lockoutthebuttons,pressbothdelaybuttonsandtheDWNbuttonsimultaneously(seebelowleft).Thiswill
lockoutallofthebuttonsandpreventanaccidentalchangingofsettings.Tounlockthebuttons,pressboth
delaybuttonsandtheUPbuttonsimultaneously(seebelowright).
LockOutON
(LOCKED)
LockOutOFF
(UNLOCKED)
Troubleshooting
PROBLEM SOLUTION
Displayisnotreading
correctlevel.
First check the Bar Graph to make sure it is indicating
the correct level.If not, check transmitter.If so,
performafactoryresetontheLVCN51Seriesandreset
values.
BarGraphisnotindicating
thecorrectlevel.
Checkthetransmitter’s420mAoutputmakingsureitis
spannedcorrectlyfortheapplication.
BarGraphshowsasingle
Amberbar.
This indicates acurrentinput less than 4mA.Checkfor
looseoropenwiresbetweenthetransmitterandLVCN
51Seriesandchecktheoutputofthetransmitter.
BarGraphshowsasingle
Redbar.
This indicates a current input greater than 20mA.
Remove power immediately.Check for a short in the
wiring between the transmitter and LVCN51 Series or
for some other power source that is affecting the input
loop.
RLY2Bdoesnotappear. FlipLatchswitchtoON.
Relayswitchesonlyfrom
RLY2A(ignoresRLY2B).
LatchisturnedOFF.FlipthelatchswitchtoturnON.
LevelreachesalarmON,
butrelayisOFF.
First, check to make sure the input LED is ON.If not,
checkwiringtosensor.
Second, check status of Relay LED.If incorrect, flip the
Invertswitchtochangetherelaystate.
PumporValveissupposed
tostop,butitdoesnot.
First,checktomakesurethebar graphisindicatingthe
correct level.Next check the relay settings. Finally,
check status of Relay LED.If incorrect, flip the Invert
switchtochangetherelaystate.
Controllerispowered,but
nothinghappens.
First check the Power LED to make sure it is Green.If
not,checkthewiring,powerandmakesuretheterminal
isseatedcorrectly.
17
EXERCISE StepTen
The following exercise demonstrates inventory
control with automatic filling and a high level alarm.
The usable range is 60 inches of liquid.The pump
starts filling at 10 inches of liquid and stops filling at
50 inches of liquid.A high level alarm occurs at 55
inchesofliquid.
EnterallvaluesintotheLVCN51Seriesininches.The
OFFSET is the corresponding 4 mA setting in inches.
The SPAN is the corresponding 20mA setting in
inches.RLY2AandRLY2Bisdedicatedtothefillingof
the tank because RELAY2 is a latching relay.RLY1 is
dedicatedtothehighlevelalarmbecauseitisasingle
set point relay.
Use the following values for
programmingtheLVCN51Series.
OFFSET
0.0
SPAN
60.0
RLY1
55.0
RLY2A
50.0
RLY2B
10.0
The next exercise demonstrates the same inventory
control with automatic filling and a high level alarm.
However,theunitshavebeenchangesfrominchesto
gallons.Within the tank, 1” = 50 gallons of liquid.
The usable range is now 300 gallons of liquid.The
pump starts filling at 50 gallons of liquid and stops
filling at 250 gallons of liquid.A high level alarm
occursat275gallonsofliquid.
Enter all values into the LVCN51 Series in gallons.
The OFFSET is the corr esponding 4 mA setting in
gallons.TheSPANisthecorresponding20mAsetting
ingallons.RLY2AandRLY2Bisdedicatedtothefilling
ofthetankbecauseRELAY2isalatchingrelay.
RLY1is
dedicatedtothehighlevelalarmbecauseitisasingle
set point relay.Use the following values for
programmingtheLVCN51Series.
OFFSET
0
SPAN
300
RLY1
275
RLY2A
250
RLY2B
50

18
EXERCISE(continued) StepTen
The following exercise demonstrates inventory
control with a high and low level alarm.The usable
rangeisbetween16and56inchesofliquid.Thehigh
level alarm occurs at 50 inches of liquid and the low
levelalarmoccursat20"ofliquid.
EnterallvaluesintotheLVCN51Seriesininches.The
OFFSET is the corresponding 4mA setting in inches.
The SPAN is the corresponding 20mA setting in
inches.RLY1 is dedicated to the high level alarm
because it is a single set point relay.RLY2A is
dedicated to the low level alarm because the latch is
turned off on Relay 2.Use the following valu
es for
programmingtheLVCN51Series.
OFFSET
0.0
SPAN
65.0
RLY1
50.0
RLY2A
20.0
RLY2B
N/A
The next exercise demonstrates the same inventory
controlwitha highandlowlevelalarm.However,the
units have been changes from inches to gallons.
Alongthe straight sideofthetank,1”=50gallonsof
liquid.The usable range is now from 50 to 250
gallons of liquid.The high level alarm occurs at 220
gallons of liquid.The low level alarm occurs at 70
gallonsofliquid.
EnterallvaluesintotheLVCN51Seriesingallons.
TheOFFSETisthecorresponding4mAsettingin
gallons.TheSPANisthecorresponding20mAsetting
ingallons.RLY1isdedicatedtothehighlevelalarm
becauseitisasinglesetpointrelay.RLY2Ais
dedicatedtothelowlevelalarmbecausethelatchis
turnedoffonRelay2.Usethefollowingvaluesfor
programmingtheLC521001.
OFFSET
0
SPAN
250
RLY1
220
RLY2A
70
RLY2B
N/A

19
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Omega LVCN-51 Series Owner's manual

Category
Security access control systems
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI