  • Hello! I am an AI chatbot trained to assist you with the nvent raychem tcontrol-cont-03 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
TCONTROL-CONT-03
COMPACT MICROPROCESSOR CONTROLLER
OPERATING AND INSTALLATION MANUAL
nVent.com | 3
CONTENTS
Section − 1 Introduction ...................................................... 4
1.1 Preface ........................................................................4
1.2 Type designation ........................................................ 5
1.3 Scope of delivery ........................................................ 5
1.4 Accessories ................................................................ 5
1.5 Type-dependent factory settings ...............................6
Section − 2 Installation .......................................................9
2.1 Installation site and ambient conditions ...................9
2.2 Dimensions ..................................................................9
2.3 Installation ................................................................... 9
Section − 3 Electrical connection ......................................10
3.1 Installation notes.......................................................10
3.2 Electrical isolation ..................................................... 11
3.3 Connection diagram ..................................................11
Section − 4 Operation .......................................................12
4.1 Display and operating elements ............................... 12
4.2 Level concept ............................................................12
4.3 Userlevelconguration ............................................13
4.4 Deningvarioususerlevels ...................................... 14
4.5 Entries and operator prompting ...............................14
4.6 Controller ...................................................................15
4.7 Display of the software version ................................ 16
Section − 5 Operator level .................................................17
Section − 6 Parameter level ..............................................17
Section − 7 Conguration level .........................................19
7.1 Analoginput ..............................................................21
7.2 Controller ...................................................................23
7.3 Rampfunction ...........................................................26
7.4 Limit comparators ..................................................... 26
7.5 Timer .......................................................................... 28
7.6 Outputs ......................................................................30
7.7 Binaryfunctions ........................................................32
7.8 Display/Operation/Servicecounter .......................... 34
7.9 Interface .....................................................................38
Section − 8 Supplement ....................................................39
8.1 Technical Data ...........................................................39
8.2 Alarmandfaultmessages .......................................43
8.3 Self-optimization .......................................................44
4 | nVent.com
1. Introduction
1.1 Preface
Pleasereadthismanualbeforecommissioningthedevice.Keep
themanualinaplaceaccessibletoallusersatalltimes.Your
commentsareappreciatedandmayassistusinimprovingthis
manual.
Allnecessarysettingsaredescribedinthisoperatingmanual.
Manipulationsnotdescribedinthemanualorexpresslyforbidden
willjeopardizeyourwarrantyrights.Pleasecontactthenearest
subsidiaryortheheadoffice,shouldyouencounterproblems.
Themanualisvalidfromdevice software version 223.01.04
Chapter 4.7 “Display of the software version
Warning signs
DANGER!
This symbol indicates that Injury or death caused by electrical
shockcan/mayoccur,iftherespectiveprotectivemeasuresare
notcarriedout.
CAUTION!
This symbol in combination with the signal word indicates
that Damage to assets or data losswilloccur,iftherespective
protectivemeasuresarenotcarriedout.
Note symbols
TIP!
This symbol refers to an Important informationabouttheproduct
oritshandlingoradditionaluse.
REFERENCE!
This symbol refers to Further informationinothersections,
chaptersormanuals.
nVent.com | 5
1.2 Type designation
Type key Type description
702071/9-1131-23-00
(nVent Part No.:
1244-0006829)
TCONTROL-CONT-03
nominaldimension48mmx48mm
1analoginput
3 relays
702071/9-1134-23-00
(nVent Part No.:
1244-0006830)
TCONTROL-CONT-03/MA
nominaldimension48mmx48mm
1analoginput
2 relays
1analogoutput(usercongurable
0/4…20 mA or 0/2…10 V)
702071/9-1131-23-53
(nVent Part No.:
1244-0006982)
TCONTROL-CONT-03/COM
nominaldimension48mmx48mm
1analoginput
3 relays
Interface RS485
702071/9-1134-23-53
(nVent Part No.:
1244-0006981)
TCONTROL-CONT-03/COMA
nominaldimension48mmx48mm
1analoginput
2 relays
1analogoutput|(usercongurable
0/4…20 mA or 0/2…10 V)
Interface RS485
1.3 Scope of delivery
Controller(includingsealandfasteningelements)
OperatingandInstallationmanualINSTALL-148inDINA4format
1.4 Accessories
Computer aided setup and configuration utility
(TCONTROL-CONT-03/CONFIG)
Content:
MiniCDwithsoftware,license+manuals
PCinterfacewithUSB/TTLconverter,cableandconnector
Hardware requirements (PC):
512 MB RAM
250 MB free space on hard disk
CD ROM drive
Free USB interface
Operating system:
Microsoft
1
Windows 2000 / XP / Vista / 7
(32-bit and 64-bit version)
6 | nVent.com
1.5 Type-dependent factory settings
The following tables show the type-dependent factory settings.
The standard factory settings are shown in the respective
sectionsofthismanual.
The settings for type TCONTROL-CONT-03 are also valid for type
TCONTROL-CONT-03/COM.
The settings for type TCONTROL-CONT-03/MA are also valid for
type TCONTROL-CONT-03/COMA.
Set points (available within User level - USEr)
Parameter Factory setting for type
TCONTROL- CONT-03 TCONTROL- CONT-03/MA
Set point 1 (SP1) 5.0 5.0
Set point 2 (SP2) 0.0 0.0
Parameter level (PArA)
Parameter Factory setting for type
TCONTROL- CONT-03 TCONTROL- CONT-03/MA
Proportional
band(Pb1)
0.0 10.0
Derivativetime(dt) 0 s 80 s
Reset time (rt) 0 s 350 s
Configuration level (ConF)
Parameter Factory setting for type
TCONTROL- CONT-03 TCONTROL- CONT-03/MA
Analog input (InP):
Scale low level (SCL) -50 -50
Scale high level
(SCH)
250 250
Controller (Cntr):
Controller type
(CtYP)
1 (= 2-state ON/OFF) 4(=continuous
4…20 mA)
Outputvalueat
OutofRange
100 100
Manualmode inhibited inhibited
Self-optimization inhibited inhibited
1
Microsoft and Windows are registered trademarks of Microsoft Corporation.
nVent.com | 7
Conguration level (ConF) cont...
Parameter Factory setting for type
TCONTROL- CONT-03 TCONTROL- CONT-03/MA
Limit comparator 1 (LC1):
Function(FnCt) lk8 lk8
Alarmvalue(AL) 2.0 2.0
ResponsebyOutof
Range (ACrA)
1 (= ON) 1 (= ON)
Limit comparator 2 (LC2):
Function(FnCt) lk7 lk7
Alarmvalue(AL) 120.0 120.0
ResponsebyOutof
Range (ACrA)
1 (= ON) 1 (= ON)
Binary outputs (OutL):
Binaryoutput1
(Out1)
1(=Controlleroutput1) 5 (= Limit comparator 1)
Binaryoutput2
(Out2)
5 (= Limit comparator 1) 6 (= Limit comparator 2)
Binaryoutput3
(Out3)
0(=nofunction) 0(=nofunction)
Binaryoutput4
(Out4)
6 (= Limit comparator 2)
Analog output (OutA):
Type of signal
(SiGn)
3 (= 4…20 mA)
Display/Operation/Service counter (diSP):
Decimal place
(dECP)
1 (= one digit after
decimal point)
1 (= one digit after
decimal point)
Service interval
(oCAL)
30000 0 (= switched off)
Level inhibit Parameter and
Congurationlevel
Parameter and
Congurationlevel
8 | nVent.com
User level (USEr) configuration
Factory setting for type
TCONTROL-CONT-03 TCONTROL-CONT-03/MA
# Parameter Name Parameter Name
1 Set point 1 SP1 Set point 1 SP1
2 Limit comparator 1:
Limitvalue
(Alarmvalue)
AL1 Limit comparator 1: Limit
value
(Alarmvalue)
AL1
3 Limit comparator 2:
Limitvalue
(Alarmvalue)
AL2 Limit comparator 2: Limit
value
(Alarmvalue)
AL2
4 Mains ON delay
(Power ON delay)
Strt Mains ON delay
(Power ON delay)
Strt
5 Analoginput:
Probe type
(Sensor type)
InP Analoginput:Probetype
(Sensor type)
InP
6 Display:
Decimal point
dEC Display: Decimal point dEC
7 Parameter set 1:
Proportional band 1
Pb1 Parameter set 1:
Proportional band 1
Pb1
8 Parameter set 1:
Cycle time 1
CY1 (Switched off)
Undocumented parameters
Parameter Factory setting for type
TCONTROL- CONT-03 TCONTROL- CONT-03/MA
Bit parameter:
Parameter 11
(enablestouse
for parameter
“Cy”values
from 1 to 9999)
ON ON
TCRUC-BE.БЛ08.B.01634
nVent.com | 9
2. Installation
2.1 Installation site and ambient conditions
Theambientconditionsattheinstallationsitemustmeetthe
requirementsspecifiedinthetechnicaldata.
Chapter8.1“TechnicalData”Thedeviceisnotsuitableforuse
inareaswithanexplosionhazard(Exareas).
Cleaning the device front
Thedevicefrontcanbecleanedusingwarmorhotwater
(possiblyaddingslightlyacidic,neutralorslightlyalkaline
cleaning agent). It has a limited resistance to organic solvents
(e.g.methylatedspirits,whitespirit,etc.).Donotuseabrasive
orhigh-pressurecleaningequipment.
2.2 Dimensions
Close mounting
Minimum spacing of panelcut-outs horizontal vertical
withoutsetupplug > 8 mm > 8 mm
withsetupplug > 8 mm > 65 mm
45
+0.6
45
+0.6
48
48
44.5
50
90.5
5
44.5
48
(2
)
(1
)
(1) ConnectionforPCinterfaceadapter(setupplug)
(2) Panelcut-out
2.3 Installation
1. Insertthedevicefromthefrontintothepanelcut-out.
2. Pushthefasteningframefromthepanelrearontothedevicebodyand
pressthespringsagainstthepanelrearuntilthelugsengageintheirslots
anditissucientlyfastened.
10 | nVent.com
3. Electrical connection
3.1 Installation notes
Thechoiceofcable,theinstallationandtheelectrical
connectionofthedevicemustconformtotherequirements
ofVDE0100“RegulationsontheInstallationofPowerCircuits
with Nominal Voltages below 1000 V” or the appropriate local
regulations.
Theelectricalconnectionmustonlybecarriedoutbyqualified
personnel.
Theinstrumentshallbeoperatedbymainsprotectedwitha
branchcircuitryovercurrentprotectiondevicenotmorethan
20Amps.Forservicing/repairingaDisconnectingDeviceshall
beprovidedtodisconnectallconductors.
Theloadcircuitmustbefusedforthemaximumrelaycurrent,
inordertopreventtheoutputrelaycontactsbecomingwelded
intheeventofashortcircuitoccurringatthatpoint.
The electromagnetic compatibility conforms to the standards
andregulationscitedinthetechnicaldata.
Runinput,outputandsupplycablesseparatelyandnotin
parallel with one another.
Sensorandinterfacecablesshouldbeshieldedcableswith
twistedconductors.Donotruncablesclosetocurrent-carrying
componentsorcables.Groundtheshieldingononeside.
Donotconnectanyadditionalloadstothesupplyterminalsof
the device.
DANGER!
Hazardouselectricalvoltage.
Injuryordeathcausedbyelectricshock.Theelectricalconnection
mustonlybecarriedoutbyqualifiedpersonnel.
TIP!
Identify the device version by way of the type key.
Installation information on conductor cross sections
Cable size Cross section
Solid core ≤1.3mm
2
Strandedwire,withcore-end
ferrule
≤1.0mm
2
Plug-interminalstrips(screwterminals).
nVent.com | 11
3.2 Electrical isolation
2300 V AC
30 V AC
50 V DC
2300 V AC
30 V AC
50 V DC
(1)
(2)
(3)
(7)
(6)
(5)
(4)
(1)Analoginput
(2)Binaryinputs/OutputK3(Logics)
(3)Setupinterface
(4)Voltagesupply
(5) RS485 interface
(6)Analogoutput
(7)OutputsK1,K2andK4(relay)
3.3 Connection diagram
1
2
5
6
N(L-)
L1(L+)
14
13
17
20
21
22
23
RxD/TxD
0/4—20mA
-
+
0/2—10V
+
AC/
DC
19
18
0/4—20mA
0/2—10V
+
-
+
-
24
(1)
(2)
(5.1)
(4)
(8
)
(7)
(6
)
-
+
(6.1)
(6.2)(6.3) (6.4)
(3)
0/14V
+
-
(5.2)
(1) Output1(K1):Relay230
V AC/3 A
(2) Output2(K2):Relay230V
AC/3 A
(3) Output3(K3):Logic0/14
V (alternative to binary
input1,congurable)
(4) Output4(K4)(option):Analog
outputorRelay230VAC/3A
(5.1) Binaryinput1
(for potential-free contact);
(alternativetooutput3,
congurable)
(5.2) (5.2)Binaryinput2
(for potential-free contact);
(alternativetoinput
0/2—10V,congurablewith
setupprogram)
(6) Analoginput
(6.1) Standardsignals(input
0/2—10V alternative to
binaryinput2)
(6.2) Thermocouple
(6.3) RTDtemperatureprobe
(3 wire)
(6.4) RTDtemperatureprobe
(2 wire)
(7) RS485 interface (Option) (8) Voltagesupply110—240VAC
(Option: 20—30 V AC/DC)
12 | nVent.com
4. Operation
4.1 Display and operating elements
(1) Red 7-segment display(factory-setting:Processvalue);
4-digit,configurabledecimalplace(automaticadjustmenton
display overflow)
(2) Green 7-segment display(factory-setting:Setpointvalue);
4-digit,configurabledecimalplace,servesalsoforoperator
guide(displayofparameterandlevelsymbols)
(3) Signals, yellow LED
Switchingstatesofthebinaryoutputs1...4(displaylit=ON)
(4) Keys
Programming key
leavelevel/functionkey
Chapter7.8“Display/Operation/Servicecounter”
Valuereduction/previousparameter
Valueincrease/nextparameter
(5) Signals, green LED
Manualmodeactive
Rampfunctionactive
Timer active
4.2 Level concept
Theparametersforthedevicesettingarestructuredindifferent
levels.
Normal display
>2s
or timeout
Navigation principle
one level
backward
one level
forward
next/previous
parameter
F
EXIT
F
EXIT
PArA
ConF
OPr/USEr
1
1. Either the Operator (OPr) or
the User level (USEr) exists
Conguration level ConF
- Analog input in P
- Controller Cntr
- Ramp function rAFC
- Limit comparators LC
- Timer tFCt
- Outputs OutP
- Binary functions b
,
nF
- Display d
,
SP
- Interface intF
Operator level OPr
Set points, process data, ...
User level USEr
Up to any eigth parameters
(ex-factory: preassigned)
Parameter level PAr A
-Pb1,dt,rt...
nVent.com | 13
Chapter 5 “Operator level”
Chapter 6 “Parameter level”
Chapter7“Configurationlevel”
TIP!
If no key is pressed for 180 s the device changes back to normal
display(factory-setting).ThesettingcanbechangedintheSetup
program(Display/Operation/Servicecounter->Operation->
Time-out).
4.3 User level configuration
Amaximumofeightfrequentlyusedparameterscanbemade
availableintheUserlevel.UsetheSetupprogramtoconfigure
these parameters.
Oncetheseparametersareselectedacustomerfriendlyname
canbeassigned.Namescanconsistoutofmaximumfour
characters (represented on 7-segment display). If no name is
assignedthefactorydefaultswillbeused.
Figure shows the menu of the Setup program
(in case of TCONTROL-CONT-03/MA and .../COMA parameter 8 is
switched off)
14 | nVent.com
4.4 Defining various user levels
Accesstotheindividuallevelscanbeinhibited.
Code
Operator, User
level
Parameter
level
Configuration
level
0 free free free
1 free free inhibited
2 free inhibited inhibited
3 inhibited inhibited inhibited
1. Forcodeentryuse
and (simultaneouslyfor>5s)
2. Change code by pressing
(display blinks!)
3. Entercodeusing
and (Ex-factory:alllevelsenabled)
4. Returntothenormaldisplayusing
orautomaticreturnafter
180 s
Theparameterandconfigurationlevelcanalsobeinhibitedvia
thebinaryfunction.
Chapter7.7“Binaryfunctions”
4.5 Entries and operator prompting
Entering values
Whenentriesaremadewithinthelevels,theparametersymbol
appears in the lower display.
Change value
(top - red)
Parameter flashes
Select parameter
(bottom - green)
P
1. Select parameter by pressing or
2. Changetotheentrymodeusing
(lower display blinks)
3. Changeavalueusing
and
Thevaluealtersdynamicallyforaslongasthekeyiskept
pressed.
4. Take over the entry with
orautomaticreturnafter2sor
cancel the entry with
thevaluewillnotbeapplied.
TIP!
Ifthefunctionkey
ispressedfor>2s,thedevicechanges
back to normal display.
nVent.com | 15
Time entry
A decimal place is mapped in the centre and on the right to
displaytimes.Thetimeunitcanbeconfigured.
Chapter 7.5 “Timer”
Change value
(top - red)
Parameter flashes
Select Parameter
(bottom - green)
P
1. Select parameter by pressing or
2. Changetotheentrymodeusing
(lower display blinks)
3. Changeavalueusing
and
Thevaluealtersdynamicallyforaslongasthekeyiskeptpressed.
4. Take over the entry with
orautomaticreturnafter2sor
cancel the entry with
thevaluewillnotbeapplied.
4.6 Controller
Increase set point value
Reduce set point value
Normal display:
Regulation to set
point value 21,0
>2s
Manual mode:
Output value 30%
Further levels:
P
alternatively
1
P
F
EXIT
F
EXIT
Normal display
Innormaldisplay,thecontrollerregulatestotheenteredsetpoint
value.
Changing the set point value
From the normal display:
1. Changethesetpointvalueusing
and (thevaluewillbe
automaticallyapplied)
Thelongerthekeyiskeptpressed,thefasterthesetpoint
valuechanges.
USEr
1
OPr
1
PArA
ConF
16 | nVent.com
Changing to the manual mode
Inthemanualmode,thecontrolleroutputvaluecanbechanged
manually.
1. Changetothemanualmodeusingfunctionkey
(> 2 s)
(ex-factorysetting)
Theoutputvalueisdisplayedinpercentinthelowerdisplay.
The"Manualmodeactive"LEDisalsolit.
2. Changetheoutputvalueusing
and
Withamodulatingcontroller,theactuatorisopenedorclosed
usingthekeys.
Thevariouslevelscanbeaccessedinthemanualmode.
TheSetupprogramcanbeusedtoconfigurethedefaultoutput
valueonachangeover.Themanualmodecanalsobeinhibited.
Chapter 7.2 “Controller”
Thecontrollerautomaticallychangestomanualmodeinthe
eventofoverrange/underrangeandprobebreak.
Manual mode exit
1. Exitthemanualmodeusingfunctionkey
(> 2 s)
Operation via binary functions
Furtheroperatingpossibilitiesforthefixedvaluecontrollercanbe
realisedviabinaryfunctions.
Chapter7.7“Binaryfunctions”
4.7 Display of the software version
Simultaneouslypressthe and keys to display the software
version.
Four-digitdisplay;example:“01.01”incaseofsoftwareversion
xxx.01.01
Levels can be inhibited.
Chapter 4.4 „Defining various user levels
Normal display
>2s
or timeout
Navigation principle
one level
backward
one level
forward
next/previous
parameter
F
EXIT
F
EXIT
Levels can be inhibited.
Chapter4.4“Definingvarioususerlevels”
Operator level OPr
Setpointvalues,
processdata,...
1. Operator level (OPr) only visible
if no User level (USEr) exists
OPr
1
nVent.com | 17
5. Operator level
Parameters
Dependingontheconfiguration,thefollowingvaluesaredisplayed:
Symbol Meaning
SP 1
Setpointvalue1(canbeedited)
SP 2
Setpointvalue2(canbeedited),onlywhenswitching
overtosetpointvalue2v
Chapter7.7“Binaryfunctions”
SPr
Rampsetpointvalue(onlyifcongured)
Chapter7.3“Rampfunction
inP 1
Measuredvalueofanaloginput1
y
Outputvalue
t1
Timertime(onlyifconguredandtimerisnotrunning)
Chapter 7.5 “Timer”
tL
Timerrunningtime(onlyiftimerruns)
Chapter 7.5 “Timer”
tr
Residualtimerrunningtime(onlyiftimerruns)
Chapter 7.5 “Timer”
OC
Servicecounterdisplay(onlyifservicecounterrunsor
aslongasareachedlimitvaluewasnotreset)
Chapter7.8“Display/Operation/Servicecounter”
6. Parameter level
Normal display
>2s
or timeout
Navigation principle
one level
backward
one level
forward
next/previous
parameter
F
EXIT
F
EXIT
Levels can be inhibited.
Chapter4.4“Definingvarioususerlevels”
Parameter level PArA
Pb1
.
.
.
y2
PArA
OPr/USEr
1
1. Either the Operator (OPr) or
the User level (USEr) exists
18 | nVent.com
Parameters Symbol
Value
range Description
Proportional
band
Pb1
0…9999 Proportional band
AtPb1,2=0,thecontrollerstructure
isineffective.Forthecontinuous
controllerPb1,2mustbe>0.
Pb2
1)
0…9999
Derivative
time
dt
0…
9999s
Inuencesthedifferentialcomponent
ofthecontrolleroutputsignal
The larger the derivative time
the higher the effectiveness of
the D component.
Reset time
rt
0…
9999s
Inuencestheintegralcomponentof
thecontrolleroutputsignal
The larger the reset time the lower the
effectiveness of the I component.
1)For3-statecontrollersonly(controlleroutput2)
Cycle time
ofoutput
Cy1
0…
20…
9999s
Foraswitchingoutput,thecycletime
shouldbeselectedsuchthatonone
handnoinadmissibleprocessvalues
uctuationsaregeneratedandon
the other hand no overload of the
actuatorsoccursbythecyclicsupply
of energy.
Cy2
1)
0…
20…
9999s
Dead band
db
0.0…
999.9
Spacing between the two control
contacts of the 3-state controller and
themodulatingcontroller
Hysteresis
HyS1
0.0…
1.0…
999.9
Hysteresis for switching controller
withPb1,2=0.
100%
y
x
w
HyS1,2
0%
HyS2
1)
0.0…
1.0…
999.9
Valve
runtime
tt
5…60…
3000s
Usedruntimerangeofthecontrol
valve(actuator)ofthemodulating
controller
Operating
value
y0
-100…
0…
+100%
OutputvalueforPandPDcontrollers
(forx=wisy=Y0)
Output
valuelimits
y1
0…100% Maximumoutputvaluelimit
Minimumoutputvaluelimit
(Only effective when Pb>0!)
y2
-100…
+100%
1)For3-statecontrollersonly(controlleroutput2)
nVent.com | 19
Standard factory settings are shown bold.
Non-standard factory settings:
Chapter 1.5 “Type-dependent factory settings”
Parameter display independent of the controller type:
Chapter 7.2 “Controller”
Decimal places for some parameters depend on the device
setting:
Chapter7.8“Display/Operation/Servicecounter”
7. Configuration level
Normal display
>2s
or timeout
Navigation principle
one level
backward
one level
forward
next/previous
parameter
F
EXIT
F
EXIT
Levels can be inhibited.
Chapter4.4“Definingvarioususerlevels”
TIP!
Parametersarenotdisplayedunlesstheequipmentlevelpermits
thefunctionassignedtotheparameter.Thismeans,forexample,
thatinterfaceparameterscanonlybeconfigured,ifthedeviceis
equippedwithaninterface.
TIP!
SomeparameterscanonlybeprogrammedthroughtheSetup
program.Inthefollowingtables,thesearemarkedinthe
“Parameters”columnwith“(Setup)”.
TIP!
Standard factory settings are displayed bold in the following
tablesinthe“Value/Selection”and“Description”columns.
Non-standard factory settings are shown in Chapter 1.5
“Type-dependent factory settings”.
TIP!
Foractivationofbinaryinput2thesetupprogramisrequired
(Hardware assistant).
Conguration level ConF
- Analog input in P
- Controller Cntr
- Ramp function rAFC
- Limit comparators LC
- Timer tFCt
- Outputs OutP
- Binary functions b
,
nF
- Display d
,
SP
- Interface intF
PArA
ConF
OPr/USEr
1
1. Either the Operator (OPr) or
the User level (USEr) exists
20 | nVent.com
Analog selector
SomeparametersintheConfigurationlevelallowuserstoselectfroma
seriesofanalogvalues.Thelistbelowshowsallavailableoptions.
Value Description
0 Deactivated
1 Analoginput
2 Processvalue
3 Currentsetpointvalue
4 Ramplimitvalue
5 Rampsetpointvalue
6 (Reserved)
7 (Reserved)
8 Setpointvalue1
9 Setpointvalue2
10 Controlleroutputvalue(-100%…+100%)
11 Controlleroutput1(0…+100%;e.g.“Heating”)
12 Controlleroutput2(0…-100%;e.g.“Cooling”)
13 Timerruntime(timeunitofthetimer)
14 Residualtimerruntime(timeunitofthetimer)
15 (Reserved)
16 (Reserved)
17 (Reserved)
/