FläktGroup LQAZ-08 Water trap Installation guide

Type
Installation guide
FläktGroup DC_9197GB 20180328_R0 Specifications are subject to alteration without notice
LQAZ-08 WATER TRAP
MAINTENANCE
1. Drain pipe of the unit section
2. Elbow
3. Base frame or other support with a height of at least 150 mm
4. U-bend
5. Non-return valve with cleaning cover
6. 32 mm i.d. outlet with compression coupling
7. Floor gully
MAINTENANCE INTERVAL
6 months. Check and clean the water trap.
CLEANING THE WATER TRAP
The water trap must be unscrewed and re-assembled by hand.
Check that the pipes/hoses are not blocked, and clean any dirt and
deposits from the water trap.
0ϒ
ϒC
1
2
5
4
6
3
7
N.B.
The water trap and discharge pipe must not be
subjected to temperatures below freezing. If the
unit is installed outdoors, the drain pipe, water
trap and discharge pipe should be insulated.
The water trap should not be exposed to direct
sunlight.