-3-
(3) As the blade continues opening and the blade
tip touches the Duogap® operating lever, cur-
rent flow is divided momentarily into two cur-
rent paths:
(A) Blade, arc bolt, arcing horn and contact
terminal.
(B) Blade, blade tip, interrupter and contact
terminal.
As the blade continues, path (A) is lost and
path (B) only remains.
3
(4) Current flow continues through blade, blade
tip, operating lever, interrupter and contact
terminal. When air-gap is adequate to prevent
arc re-strike between blade and arcing horn,
the interrupter trips and breaks load internally.
Loadbreak occurs when the two contacts, part-
ing simultaneously, split the circuit allowing a
double break in the circuit. The heat of the arcs
cause gases to generate from the delrin sleeve
and liner which expels and cools the arc. The
gas pressure is then vented through the
weather/insect shield.
(5) The blade tip separates from the interrupter
operating lever after the interruption, resetting
the interrupter for the next operation.
During closing, the switch blade arc bolt picks
up the arcing horn before the blade tip brushes
past the operating lever of the interrupter, thus
only limited current is through the interrupter.
5
4
WEATHER/INSECT
SHIELD