DANLERS ISI-CESR10V Installation guide

Type
Installation guide
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: ISI-CESR10V is only compatible to work with DANLERS enabled app.
ISI-CESR10V
Ceiling Surface Mount Passive Infra Red (PIR)
Occupancy Detector & Photocell for DALI ballasts
Input: 100-240 Vac 50/60Hz
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: [email protected]
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
30/03/2022 DAT0156 ISI-CESR10V
This ISI-CESR10V Lighting Control can be
mounted directly onto solid ceilings or onto a range
of different mounting boxes. Confi gurable for any
room occupancy style, via the DANLERS APP on
Google Play or Apple APP Store.
INSTALLATION
To be installed by a competent person with
reference to BS 7671 or equivalent local standards.
If in doubt consult a qualifi ed electrician.
Plan where the ISI-CESR 0V is to be located
(see diagram 1). Switch off supply and check for
hidden cables and pipes.
The ISI-CESR10V should be connected as
shown in diagrams 2 and 3:
L Live in.
N Neutral in.
+ Control line (polarity dependent)
- Control line (polarity dependent)
Knockout or drill the appropriate holes on the
mounting plate for attaching the plate to the
ceiling or back box (if applicable). Feed cables
through the appropriate (side or rear) entry hole.
Screw the back mounting plate to the ceiling or
back box via the mounting holes. Wire the cables
into the sensor head block terminal. Push the
sensor head onto the mounting plate and align
the side clips with the slots on the sensor heads.
OPERATION
To check the operation of the ISI-CESR10V:
Turn on the supply then after 20 seconds if the
sensor has recognised movement of a person
within its zone of detection the integral red
LED on ISI-CESR10V will stay illuminated for 4
seconds before the red LED turns off.
Thereafter, every time movement is detected
by ISI-CESR10V the integral red LED will stay
illuminated for 4 seconds.
The control also features adjustable time out (time
lag) control and daylight threshold control which
are confi gured by the DANLERS APP.
PRECAUTIONS
• Do not place the ISI-CESR10V near heat
sources, fans or in ventilated ceiling voids.
• Do not place close to, or positioned such
that, any light source points directly into the
ISI-CESR10V.
• Ensure wires and cables are securely held within
the connection terminals.
• The ISI-CESR10V should be protected by a 6
Ampere mcb or fuse.
Disconnect the ISI-CESR10V from the
circuit before performing insulation testing
of the wiring circuit.
TECHNICAL DETAILS
INPUT
Voltage: 100 - 240Vac
Frequency: 50/60Hz
Max. mains current: 20mA
Standby current: 18mA
OUTPUT
Output: 0-10VDC
Output Current: 40mA
(maximum 20 ballasts)
RADIO TRANSCEIVER
Operating frequencies: 2.4... 2,483 GHz
Max. output power: +4 dBm
LUX PARAMETERS
Range: 5 - 2000 lux
OPERATING CONDITIONS
Note: The temperature difference between the
detection target and the background must be at
least 4 °C.
Ambient temperature: -20... +40 °C (lout
20mA)
Storage temperature: -25... +75 °C
Max. relative humidity: 0... 80%, non cond.
CONNECTORS
Terminal block
Wire size:
0.5mm2 - 2.5mm2 solid
or stranded
Wire strip length: 6-7mm
Tightening torque: 0,4 Nm/4 Kgf.cm
MECHANICAL DATA
Dimensions: 49mm x 91mm x 91mm
Weight: 98g (unpacked)
Degree of protection: IP20
Protection class: Built-in Class 2
Material (casing) Flame-retardant
polycarbonate
Finish / Colour Matt /White (RAL 9003)
Protection class: Built-in Class 2
CONFORMITY AND STANDARDS
EMC emission:
EN 301 489-1 V2.2.0, EN 301 489-17 V3.1.1,
EN 55032: 2015, EN61000-3-2: 2014,
EN61000-3-3: 2013
EMC immunity:
EN 301 489-1 V2.2.0, EN 301 489-17 V3.1.1
Environment:
Complies with WEEE and RoHS directives
5 YEAR WARRANTY
ISI-CESR10V comes with a 5 year
warranty from the date of manufacture
and is CE marked.
up to 5m
up to 7m
Strong detection zone
i.e. person moving arm
or walking towards PIR
For optimum coverage recommended
mounting height: 2.4 to 5m
Secondary detection
zone i.e. person walking
perpendicular to PIR
DIAGRAM 1
Suggested typical wiring
N
L
230 Vac
6A MCB
or fuse
+
N
L
-
+
-
Control Lines
DIAGRAM 2
DIAGRAM 3
L
N
Ballast
Dimming
Control Lines
Ballast
ISI CESR 10V
plan side
49mm
91mm
91mm
80mm
9mm
DIAGRAM 4
  • Page 1 1

DANLERS ISI-CESR10V Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI