West Control Solutions CO 2/U User manual

Type
User manual

West Control Solutions CO 2/U is a power supply module for sensors, used for energizing transmitters, especially strain gauge or semi-conductor bridges for pressure sensors within the KS vario/vario system. Here is a brief summary of its capabilities:

  • Provides a supply voltage for pressure sensors, isolated from the remaining system
  • Offers two 10 V d.c. constant voltage outputs for energizing 1 or 2 strain gauge pressure sensors
  • Delivers an output current of 2 x 40 mA or 1 x 80 mA, with a maximum total of 80 mA
  • Features a typical accuracy of 0.6% and drift of 0.3%
  • Includes a short circuit protection for up to 1 hour

West Control Solutions CO 2/U is a power supply module for sensors, used for energizing transmitters, especially strain gauge or semi-conductor bridges for pressure sensors within the KS vario/vario system. Here is a brief summary of its capabilities:

  • Provides a supply voltage for pressure sensors, isolated from the remaining system
  • Offers two 10 V d.c. constant voltage outputs for energizing 1 or 2 strain gauge pressure sensors
  • Delivers an output current of 2 x 40 mA or 1 x 80 mA, with a maximum total of 80 mA
  • Features a typical accuracy of 0.6% and drift of 0.3%
  • Includes a short circuit protection for up to 1 hour
©PMA Prozeß- und Maschinen-Automation GmbH 2004. Printed in Germany
All rights reserved. No part of this document may be
reproduced or published in any form or by any means without prior written permission
by the copyright owner.
A publication of PMA Prozeß- und Maschinen-Automation GmbH
Subject to change without notice.
PMA Prozeß- und Maschinen-Automation GmbH
P.O. Box 31 02 29
D 34058 Kassel
Germany
Restriction of warranty:
No warranty is given for the complete correctness of this manual, since errors can never avoided
completely despite utmost care. Any hints are welcome and gratefully accepted.
Datasheet and Operating Instructions for VARIO Power supply Module for Sensors
9499 040 72811 3
1
11
1 General
GeneralGeneral
General
The vario power supply module for sensors is used for energizing transmitters, especially strain gauge or
semi-conductor bridges for pressure sensors within the KS vario/vario system.
The module provides a supply voltage for pressure sensors, which is isolated from the remaining system.
Power supply module for sensors, VARIO CO 2/U, order no. KSVC-103-02221
Power supply module for sensors, VARIO CO 2/U, order no. KSVC-103-02221Power supply module for sensors, VARIO CO 2/U, order no. KSVC-103-02221
Power supply module for sensors, VARIO CO 2/U, order no. KSVC-103-02221
2
22
2 Technical data
Technical dataTechnical data
Technical data
:
Supply voltage
Supply voltageSupply voltage
Supply voltage
: 24 V d.c. (from the analog voltage (U
ana
) of the vario station.
Current consumption
Current consumptionCurrent consumption
Current consumption
: approx. 120 mA
Output voltage
Output voltageOutput voltage
Output voltage
: 2 x 10 V d.c. constant voltage outputs for energization of 1 or 2
strain gauge pressure sensors
Output current
Output currentOutput current
Output current
: 2 x 40 mA or 1 x 80 mA. The sum must not exceed 80 mA.
Accuracy
AccuracyAccuracy
Accuracy
: typ. 0,6 %
Drift
DriftDrift
Drift
: typ. 0,3 %
Short circuit protection
Short circuit protectionShort circuit protection
Short circuit protection
:max. 1 h
Galvanic isolation
Galvanic isolationGalvanic isolation
Galvanic isolation
: isolated from the supply voltage (U
ana
), outputs galvanically
connected.
Display element
Display elementDisplay element
Display element
: 1 LED, yellow, for indication of the output voltage
Connection technique
Connection techniqueConnection technique
Connection technique
: cage clamp, 2-wire connection with screening
Dimensions
DimensionsDimensions
Dimensions
: 12,2 x 120 x 76 mm
Weight
WeightWeight
Weight
: approx. 70 g
Datasheet and Operating Instructions for VARIO Power supply Module for Sensors
9499 040 728114
Temperature range
Temperature rangeTemperature range
Temperature range
: operation: -25 °C to 55°C storage/transport: -25 °C to 85 °C
Humidity
HumidityHumidity
Humidity
: operation/storage/transport: average 75 %, 85 % occasional
Protection type
Protection typeProtection type
Protection type
: IP20 to IEC 60529
Bus interface
Bus interfaceBus interface
Bus interface
: not required, however, the internal bus is looped through the
module.
Accessories
AccessoriesAccessories
Accessories
: connector, inscription field (delivered with the unit)
3
33
3 Pin allocation and elementary circuit diagram
Pin allocation and elementary circuit diagram Pin allocation and elementary circuit diagram
Pin allocation and elementary circuit diagram
The screening earth connection must be made via the
function earth (FE).
function earth (FE).function earth (FE).
function earth (FE).
The screening is
connected to earth only with a non-interrupted connection up to the bus coupler module provided. (The
function earth is looped through all modules and connected to earth centrally at the bus coupler module.)
Datasheet and Operating Instructions for VARIO Power supply Module for Sensors
9499 040 72811 5
4
44
4 Pressure sensor connection
Pressure sensor connectionPressure sensor connection
Pressure sensor connection
Normally, pressure sensors consist of a full bridge circuit which must be energized by a voltage
galvanically isolated from the system. The diagonal voltage is applied to a controller module input (mV),
which is configured accordingly.
Sensor calibration is by means of a built-in resistor of a defined value in the pressure sensor. Without
pressure applied, the resistor changes the bridge resistance so that 80 % nominal output voltage are
available at its output. The relevant values are given in the pressure sensor data sheet. This resistance can
be connected in parallel to a bridge arm by an external relay, whereby a detuning of the bridge is caused.
The following relay modules are provided:
VARIO relay output module VARIO DO 1/230, order no. KSVC-102-01211 or VARIO relay output
module VARIO DO 4/230, order no. KSVC-102-01231.
These modules permit control of the relay, i.e. bridge resistance change, via the system bus.
When using these relay modules, the following information must be taken into account:
For using the module for switching the calibrating resistor, the only load must be the calibrating resistor.
The sparks generated by higher currents/voltages cause contact consumption and increase the contact
resistance, i.e. correct switching of a "dry circuit" is not ensured any more.
Datasheet and Operating Instructions for VARIO Power supply Module for Sensors
9499 040 728116
The relay modules should be always at the right end of a KS vario station. In these modules, the voltage
U
b
and U
s
(both 24V) are interrupted. Consequently, these voltage would have to be fed in again behind
the relay module.
The connector of a relay module (colour: median gray) must not be plugged into other modules, because
when using for purposes varying from the "calibrating relay", higher voltages (230 V AC) may also be
applied to the contacts. These can destroy the components of the contacted module components unless
plugged in correctly.
Although this connector is coded mechanically for protection against being inserted completely into other
modules by closing of contact holes 1.1 and 2.1, electrical connections can occur even with partial faulty
connection.
For extending the cable fitted to the pressure sensor, the same or a very similar cable type must be used
(6-wire, screened).
Datasheet and Operating Instructions for VARIO Power supply Module for Sensors
9499 040 72811 7
5
55
5 Maintenance and behaviour in case of fault
Maintenance and behaviour in case of faultMaintenance and behaviour in case of fault
Maintenance and behaviour in case of fault
The power supply module for sensors and the relay module do not need particular maintenance and no
components require any preventive maintenance or care.
5.1
5.15.1
5.1 Trouble shooting
Trouble shootingTrouble shooting
Trouble shooting
To start with, all possibilities of trouble sources due to connected instruments and cables (input leads,
wiring, equipment connected in the output circuit) should be checked. Unless the trouble was found after
these checkings, the instrument must be returned to the manufacturer:
PMA Prozeß- und Maschinen-Automation GmbH
PMA Prozeß- und Maschinen-Automation GmbHPMA Prozeß- und Maschinen-Automation GmbH
PMA Prozeß- und Maschinen-Automation GmbH
Service-Abteilung
Service-AbteilungService-Abteilung
Service-Abteilung
Miramstraße 87
Miramstraße 87Miramstraße 87
Miramstraße 87
D 34123 Kassel
D 34123 KasselD 34123 Kassel
D 34123 Kassel
If the trouble is found to be due to failure of a fuse, the cause must be determined and corrected. The
spare fuse must have the same rating as the original type.
Unless the LED is lit despite intact fuse and correctly connected supply voltage, the bus coupler is
defective and must be returned to the manufacturer for repair.
5.2
5.25.2
5.2 Shut-down
Shut-downShut-down
Shut-down
Before disconnecting the unit, disconnect the system
Before disconnecting the unit, disconnect the systemBefore disconnecting the unit, disconnect the system
Before disconnecting the unit, disconnect the system
completely
completelycompletely
completely
from the supply voltage and check that other
from the supply voltage and check that otherfrom the supply voltage and check that other
from the supply voltage and check that other
equipment connected in
equipment connected inequipment connected in
equipment connected in
the overall system is not effected.
the overall system is not effected.the overall system is not effected.
the overall system is not effected.
WARNING!
WARNING!WARNING!
WARNING! WARNING!
WARNING!WARNING!
WARNING!
When the instrument is suspected of being unsafe, it must be taken
When the instrument is suspected of being unsafe, it must be takenWhen the instrument is suspected of being unsafe, it must be taken
When the instrument is suspected of being unsafe, it must be taken
out of operation and protected against accidental switch-on.
out of operation and protected against accidental switch-on.out of operation and protected against accidental switch-on.
out of operation and protected against accidental switch-on.
5.3
5.35.3
5.3 Customer Support Hotline
Customer Support HotlineCustomer Support Hotline
Customer Support Hotline
For further questions beyond the scope of the KS 800 operating manual, please, contact one of the
following telephone numbers from Monday to Friday, between 8 a.m. and 16 p.m.
Tel. Custumer Support:
Tel. Custumer Support:Tel. Custumer Support:
Tel. Custumer Support: 49 561 505 3091
49 561 505 309149 561 505 3091
49 561 505 3091
Tel. Repair:
Tel. Repair:Tel. Repair:
Tel. Repair: 49 561 505 1257
49 561 505 125749 561 505 1257
49 561 505 1257
Tel. Sales Dept.:
Tel. Sales Dept.:Tel. Sales Dept.:
Tel. Sales Dept.: 49 561 505 1307
49 561 505 130749 561 505 1307
49 561 505 1307
e-mail:
e-mail:e-mail:
mailbox@pma-online.demailbox@pma-online.de
mailbox@pma-online.de
Subject to change without notice
Printed in Germany 9499-040-72811 (03/2004) ©PMA Prozeß-und Maschinen-Automation GmbH
Postfach 31 02 29, D - 34058 Kassel
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

West Control Solutions CO 2/U User manual

Type
User manual

West Control Solutions CO 2/U is a power supply module for sensors, used for energizing transmitters, especially strain gauge or semi-conductor bridges for pressure sensors within the KS vario/vario system. Here is a brief summary of its capabilities:

  • Provides a supply voltage for pressure sensors, isolated from the remaining system
  • Offers two 10 V d.c. constant voltage outputs for energizing 1 or 2 strain gauge pressure sensors
  • Delivers an output current of 2 x 40 mA or 1 x 80 mA, with a maximum total of 80 mA
  • Features a typical accuracy of 0.6% and drift of 0.3%
  • Includes a short circuit protection for up to 1 hour