ABB VD4 Series User manual

Type
User manual
VD4
Vacuum circuit-breaker
PRODUCT MANUAL
VD4
Vacuum circuit-breaker
Global proven reputation
Accountable solution for safety and reliability
Wide range offering, easy business and
convenient installation
Your safety first always!
Only install switchgear and/or switchboards in enclosed rooms suitable for
electrical equipment.
Ensure that installation, operation and maintenance are carried out by
specialist electricians only.
Comply in full with the legally recognized standards (DIN VDE / IEC), the
connection conditions of the local electrical utility and the applicable safety
at work regulations.
Observe the relevant information in the instruction manual for all actions
involving switchgear and switchboards.
Danger!
Pay special attention to the hazard notes in the instruction manual marked with
this warning symbol.
Make sure that under operation condition of the switchgear or switchboard
the specified data are not exceeded.
Keep the instruction manual accessible to all persons concerned with
installation, operation and maintenance.
The user’s personnel are to act responsibly in all matters affecting safety at
work and the correct handling of the switchgear.
If you have any further questions on this instruction manual, the members of our
field organization will be pleased to provide the required information.
That's why our instruction manual begins with these recommendations:
WARNUNG
Anerkannte Regeln der Technik und Betriebsanleitungen
beachten !
Gefährliche Spannung
kann elektrischen Schock und Verbrennungen verursachen.
Vor Aufnahme von Arbeiten jeder Art dieses Gerät unbedingt freischalten,
erden und kurzschließen.
WARNING
Always observe the instruction manual and follow the rules
of good engineering practice !
Hazardous voltage
can cause electrical shock and burns.
Disconnect power, then earth and short-circuit before proceeding
with any work on this equipment.
4
Contents Page
7.2 Preparatory activities 38
7.3 Movement of the withdrawable part 38
7.3.1 Manual insertion from the
test/disconnected position to
the service position 38
7.3.2 Manual withdrawal from the service
position into the test/disconnected
position 39
7.3.3 Motor-driven movement of the
withdrawable part 39
7.3.4 Withdrawal from the test/disconnected
position onto the service truck 39
7.3.5 Insertion from the service truck into
the test/disconnected position 40
7.4 Operation of the circuit-breaker 40
7.4.1 Charging the spring energy
storage mechanism 40
7.4.2 Closing and opening the circuit-breaker 40
8 Maintenance 42
8.1 General 42
8.1.1 Service-life 42
8.2 Inspection and functional testing 42
8.2.1 Switching device in general 42
8.2.2 Stored-energy spring mechanism 42
8.2.3 Breaker pole 43
8.2.4 Withdrawable assembly 43
8.3 Servicing 43
8.3.1 Switching devices in general 43
8.3.2 Stored-energy spring mechanism 43
8.3.3 Breaker pole 43
8.4 Repair 44
8.4.1 VD4 circuit-breaker run-on block 44
8.4.2 Replacement of circuit-breaker
parts and accessories 44
8.4.3 Touch up of surfaces 44
8.4.4 Circuit-breakers in general 45
8.4.5 Replacement of contact systems 45
8.4.6 Replacement of withdrawable assembly 45
8.5 Testing withdrawable parts with a
VD4 type circuit-breaker 45
8.5.1 Motor-driven withdrawable parts 45
8.5.2 Checking the correctness of
dimensional settings 45
8.5.3 Checking auxiliary switch settings
on type A withdrawable parts 46
8.5.4 Checking auxiliary switch settings
on type B withdrawable parts 46
8.5.5 Checking the direction of rotation of the
travel motors on motor-driven
withdrawable parts 46
8.5.6 Testing of interlock conditions 46
8.6 Spare parts, auxiliary materials, lubricants 47
8.6.1 Spare parts 47
8.6.2 Auxiliary materials 49
9 Application of the
X-ray regulations 53
10 Comparison of designations to
VDE-DIN 40719 Part 2
and IEC 61346-1/IEC 61346-2 54
We reserve all rights to this publication. Misuse, particularly including duplication and making available of this manual –
or extracts – to third parties is prohibited. The information supplied is without liability. Subject to alteration.
© ABB AG, 2005
Contents Page
1 Summary 5
1.1 General 5
1.2 Standards and specifications 5
1.2.1 Switchgear manufacture 5
1.2.2 Installation and operation 5
1.3 Operating conditions 5
1.3.1 Normal operating conditions 5
1.3.2 Special operating conditions 5
2 Technical data
Circuit-breakers for fixed installation 6
2.1 Technical data and weight 6
2.2 Technical data
Releases and blocking magnet 7
2.3 Technical data
Charging motor for stored-energy
spring mechanisms 8
2.4 Permissible number of vacuum
interrupter switching operations 11
2.5 Dimensional drawings
Circuit-breakers for fixed installation 13
2.6 Circuit-breaker wiring diagram 16
3 Technical data
Circuit-breakers on withdrawable part 17
3.1 Technical data and weight 17
3.2 Dimensional drawings 19
3.3 Wiring diagrams for C.B. on
withdrawable part 26
4 Structure and function 32
4.1 Basic structure of the C.B. on
withdrawable part 32
4.2 Structure on the breaker poles 32
4.3 Structure of the breaker
operating mechanism 32
4.3.1 Releases, blocking magnet and
auxiliary switches 32
4.3.2 Mounting of the VD4 on trucks from
other manufacturers 33
4.4 Function 33
4.4.1 Charging of the spring energy
storage mechanism 33
4.4.2 Closing procedure 33
4.4.3 Opening procedure 34
4.4.4 Auto-reclosing sequence 34
4.4.5 Quenching principle of the
vacuum interrupter 34
4.5 Interlocks/protection against
maloperation 34
5 Despatch and storage 37
5.1 Condition on delivery 37
5.2 Packaging 37
5.3 Transport 37
5.4 Delivery 37
5.5 Intermediate storage 37
6 Installation and mounting of the breaker 38
7 Commissioning/Operation 38
7.1 Note on safety at work 38
5
1 Summary
1.1 General
(Figures 2/1 to 2/8)
The vacuum circuit-breakers of type VD4 are
intended for indoor installation in air-insulated
switchgear systems. They have a switching
capacity capable of handling the loads occuring
at start-up and shutdown of equipment and plant
units both in normal and in fault state.
Vacuum circuit-breakers have particular advan-
tages for use in networks where there is a high
switching frequency in the working current range
and/or where a certain number of short-circuit
breaking operations are expected. Type VD4
vacuum circuit-breakers are suitable for autore-
closing, and have exceptionally high operating
reliability and long life.
The vacuum circuit-breakers of type VD4,
designed in column form, can be supplied both
as individual units for fixed installation and
mounted on chassis. Their basic structure is
shown in figures 2/1 to 2/8.
1.2 Standards and specifications
1.2.1 Switchgear manufacture
The switchgear complies with the following
specifications in accordance with DIN VDE and
the relevant IEC publications:
VDE 0670, part 1000 and IEC 60694
VDE 0671, part 100, and IEC 62271-100.
1.2.2 Installation and operation
The relevant specifications are to be taken into
account during installation and operation,
particularly:
DIN VDE 0101, Power installations exceeding
AC 1 kV
VDE 0105, Operation of electrial installations
DIN VDE 0141, Earthing systems for special power
installations with rated voltages above 1 kV
Accident prevention regulations issued by the
appropriate professional bodies or comparable
organisations.
In Germany, these comprise the following safety
regulations:
Health and Safety at Work Standards BGV A1
and BGV A3
• Safety guidelines for auxiliary and operating
materials
Order-related details provided by ABB.
1.3 Operating conditions
1.3.1 Normal operating conditions
Design to VDE 0670, part 1000, “Common
specifications for high-voltage switchgear and
controlgear standards“ and IEC publication
60694, with the following limit values:
Ambient temperature:
Maximum +40 °C
Maximum 24 hour average +35 °C
Minimum (according to
“minus 5 indoor class”) –5 °C
Humidity:
the average value of the
relative humidity, measured over
a period of 24 h, does not exceed 95%
the average value of the water
vapour pressure, over a period
of 24 h, does not exceed 2,2 kPa
the average value of the
relative humidity, over a period
of one month, does not exceed 90%
the average value of the water
vapour pressure, over a period
of one month, does not exceed 1,8 kPa
Maximum site altitude:
1000 m above sea level.
1.3.2 Special operating conditions
Special operating conditions are to be agreed on
by the manufacturer and user. The manufacturer
must be consulted in advance about each special
operating condition:
Site altitude over 1000 m:
Allow for the reduction in the dielectric
strength of the air.
Increased ambient temperature:
Current carrying capacity is reduced.
Provide additional ventilation for heat
dissipation.
Climate:
Avoid the risk of corrosion or other damage in
areas:
with high humidity and/or
with major rapid temperature fluctuations.
Implement preventive measures (e.g. electric
heaters) to preclude condensation pheno-
mena.
6
2 Technical data
Circuit-breaker for fixed installation
2.1 Technical data and weight
1)
When the operating voltage is lower than the rated voltage, the same values apply as for rated voltage. Higher values on request.
2)
Individual unit (without chassis) with motor-operated mechanism and basic release equipment.
Breaker Rated Rated Rated short- Short- Rated short- Rated short- Pole Weight
2)
Permissible number
type voltage current circuit- circuit circuit circuit centres of vacuum interrupter
breaking breaking making duration switching operations
current current current.
symm.
2)
asymm.
2)
(peak)
2)
VM1... kV A kA kA kA s mm approx. kg Figure 2/9 Page 11/12
1206-16 12 630 16 17.4 40 3 150/210 69/74 Diagram A
1212-16 1250 150/210 70/75 Diagram B
1206-20 630 20 21.8 50 3 150/210 69/74 Diagram C
1212-20 1250 150/210 70/75 Diagram D
1216-20 1600 210/275 147/155 Diagram D
1220-20 2000 210/275 147/155 Diagram D
1225-20 2500 210/275 147/155 Diagram D
1206-25 630 25 27.3 63 3 150/210 69/74 Diagram E
1212-25 1250 150/210 70/75 Diagram E
1216-25 1600 210/275 147/155 Diagram E
1220-25 2000 210/275 147/155 Diagram E
1225-25 2500 210/275 151/159 Diagram E
1206-31 630 31.5 34.3 80 3 150/210 80/85 Diagram F
1212-31 1250 150/210 81/86 Diagram F
1216-31 1600 210/275 147/155 Diagram F
1220-31 2000 210/275 147/155 Diagram F
1225-31 2500 210/275 151/159 Diagram F
1212-40 1250 40 43.6 100 3 210 94 Diagram G
1216-40 1600 210/275 147/155 Diagram G
1220-40 2000 210/275 147/155 Diagram G
1225-40 2500 210/275 151/159 Diagram G
1706-16 17.5 630 16 17.4 40 3 150/210 69/74 Diagram A
1712-16 1250 150/210 70/75 Diagram B
1706-20 630 20 21.8 50 3 150/210 69/74 Diagram D
1712-20 1250 150/210 70/75 Diagram D
1716-20 1600 210/275 147/155 Diagram D
1720-20 2000 210/275 147/155 Diagram D
1725-20 2500 210/275 151/159 Diagram D
1706-25 630 25 27.3 63 3 150/210 80/85 Diagram E
1712-25 1250 150/210 81/86 Diagram E
1716-25 1600 210/275 147/155 Diagram E
1720-25 2000 210/275 147/155 Diagram E
1725-25 2500 210/275 151/159 Diagram E
1706-31 630 31.5 34.3 80 3 150/210 90/93 Diagram F
1712-31 1250 150/210 91/94 Diagram F
1716-31 1600 275 155 Diagram F
1720-31 2000 275 155 Diagram F
1725-31 2500 275 159 Diagram F
1712-40 1250 40 43.6 100 3 210 94 Diagram G
1716-40 1600 210/275 147/155 Diagram G
1720-40 2000 210/275 147/155 Diagram G
1725-40 2500 210/275 151/159 Diagram G
2406-16 24 630 16 17.4 40 3 210/275 76/81 Diagram A
2412-16 1250 210/275 78/83 Diagram B
2416-16 1600 275 167 Diagram B
2420-16 2000 275 167 Diagram B
2425-16 2500 275 167 Diagram B
2406-20 630 20 21.8 50 3 210/275 76/81 Diagram D
2412-20 1250 210/275 78/83 Diagram D
2416-20 1600 275 167 Diagram D
2420-20 2000 275 167 Diagram D
2425-20 2500 275 167 Diagram D
2406-25 630 25 27.3 63 3 210/275 76/81 Diagram E
2412-25 1250 210/275 82/87 Diagram E
2416-25 1600 275 167 Diagram E
2420-25 2000 275 167 Diagram E
2425-25 2500 275 173 Diagram E
7
Rated voltage kV 12 17.5 24
Rated frequency Hz 50/60 50/60 50/60
Rated lightning impulse withstand voltage kV 75 95 125
Rated power frequency withstand voltage kV 28
1)
38
1)
50
Rate of rise of transient recovery voltage kV/µs 0.34 0.42 0.47
Peak of transient recovery voltage kV 20.6 30 41
Rated operating sequence O-3 min-CO-3 min-CO
Rated operating sequence with autoreclosing O-0.3 s-CO-3 min-CO
1)
At the rated supply voltage.
2)
If the activating relay contact cannot itself interrupt the release
coil current.
Guideline values for function times:
Closing time approx. 60 ms
Opening time 45 ms
Arcing time (at 50 Hz) 15 ms
Break time 60 ms
Minimum command
time on closing 20 ms
1)
(120 ms
2)
)
Minimum command
time on opening 20 ms
1)
( 80 ms
2)
)
2.2 Technical data
Releases and blocking magnet
Equipment Power consumption
1)
AC DC
VA W
Shunt release OFF -Y2
3)
, -Y9
3)
250 250
-Y2
5)
, -Y9
5)
310 310
Shunt release ON -Y3
3)
250 250
-Y3
5)
310 310
Blocking magnet -Y1
3) 5)
10 10
Undervoltage release: -Y4
• undelayed
3) 5)
11 10
• delayed
4)
10
Indirect overcurrent release -Y7
with intermediate current transformer:
• two-phase 3.5
2)
/15
• three-phase 2.0
2)
/15
1)
Approximate values
2)
With short-circuited intermediate current transformer
3)
Rated supply voltages AC: 110 and 220 V, DC: 24, 48, 60, 110 and 220 V.
4)
See RN3U for supply voltage
5)
Rated supply voltage AC: 240 V, DC: 125 and 240 V.
1)
42 kV on request.
8
Figure 2/1: VD4 circuit-breaker for fixed installation,
12 kV, 1250 A, mechanism side
1)
Approximate values
2)
At rated supply voltage
Figure 2/2: VD4 circuit-breaker for fixed installation,
12 kV, 1250 A, pole side
2.3 Technical data
Motor-operated mechanisms
Groschopp-Motor
Rated Power Motor protection Charging
supply consumpt- (ABB-Stotz m.c.b.) time
voltage ion
1)
(maxi-
mum)
2)
V VA/W A s
AC
110 260 1.6 S 281UC-K 10
220 260 0.75 10
240 260 0.75 10
DC
60 240 3.0 S 282UC-K 10
110 230 1.6 10
125 260 1.6 10
220 240 0.75 10
240 260 0.75 10
Gefeg-Motor
Rated Power Motor protection Charging
supply consumpt- (ABB-Stotz m.c.b.) time
voltage ion
1)
(maxi-
mum)
2)
V VA/W A s
AC
110 150 1.6 S 281UC-K 15
220 150 0.75 15
240 170 0.75 15
DC
24 130 4.0 S 282UC-K 15
48 130 3.0 15
60 130 2.0 15
110 140 1.0 15
125 160 1.0 15
220 140 0.75 15
240 150 0.75 15
9
Figure 2/5: Vacuum circuit-breaker, type VD4, high-current,
for 12 kV and rated current 2000 A, mechanism side
Figure 2/6: Vacuum circuit-breaker, type VD4, high-current,
for 12 kV and rated current 2000 A, pole side
Figure 2/3: VD4 circuit-breaker for fixed installation,
24 kV, 1250 A, mechanism side
Figure 2/4: VD4 circuit-breaker for fixed installation,
24 kV, 1250 A, pole side
10
Figure 2/7: VD4 circuit-breaker, on withdrawable part,
12 kV, 630 A, mechanism side
Figure 2/8: VD4 circuit-breaker, on withdrawable part,
12 kV, 630 A, pole side
11
2.4 Permissible number of vacuum interrupter switching operations
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
Diagram C) Diagram D)
Diagram A) Diagram B)
Figure 2/9: Permissible number of vacuum interrupter operating cycles n as a function of the breaking current I
a
.
(Reference see section 2.1 and 3.1 – Technical data page 6 and 17)
12
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
0,05
5
0,1 0,2 0,3 0,4 0,5 0,6 0,8 1
6
7
8
10
2
3
4
5
6
7
8
10
2
2
3
4
5
6
7
8
10
3
2
3
4
5
6
7
8
4
2
3
4
5
6
7
8
10
5
234567810920304050
10
Breaking current l
a
(kA)
Number of operating cycles n
Figure 2/9: Permissible number of vacuum interrupter operating cycles n as a function of the breaking current I
a
.
(Reference see section 2.1 and 3.1 – Technical data page 6 and 17)
Diagram G)
Diagram E) Diagram F)
13
K = Cable entry
T = Handling bores, both sides
A = View “A"
GA = Tested terminal zone
M = Minimum distance to DIN VDE 0101
A1 = Terminal for 630 A
A2 = Terminal for 1250 A
A3 = Terminal bar to DIN 46 433,
for 17.5 kV shrink sleeve fitted
= Earthing conductor terminal, use contact washer
Figure 2/10: Dimensional drawing of circuit-breaker type VD4:
• 12 kV, 630 A and 1250 A, ... 31.5 kA
• 17.5 kV, 630 A and 1250 A, ... 31.5 kA
Rated Rated Rated
voltage current short-
circuit
breaking
current
kV A kA p a a
1
cdf
24 630/ ... 25 210 570 515 520 570 390
1250 275 700 645 650 700 488
K = Cable entry
T = Handling bore, both sides
A = View “A"
GA = Tested terminal zone
M = Minimum distance to DIN VDE 0101
A1 = Terminal for 630 A
A2 = Terminal for 1250 A
A3 = Terminal bar to DIN 46 433,
for 24 kV shrink sleeve fitted
= Earthing conductor terminal, use contact washer
Figure 2/11: Dimensional drawing of circuit-breaker type VD4:
24 kV, 630 A and 1250 A, ... 25 kA.
Rated Rated Rated
voltage current short-
circuit
breaking
current
kV A kA p a a
1
cdf
12 630/ ... 31.5 150 450 395 400 450 300
1250 210 570 515 520 570 390
17.5 630/ ... 31.5 150 450 395 400 450 300
1250 210 570 515 520 570 390
A3
200
MM
MM
GA
24
40(50)
f
M12
200
A
ø45
22
22
!
433
T
pp
25
c
a
a1
35
d
VD 4ABB
M12
461
608
95
K
ø115
A
40 °
80 °
M12
205
217,5
77,5
345
409
424
44
550
100
M
30
60
368
480
24
30
475
A1
M12
Insertion
depth 18 + 2
M10
Insertion
depth 15 + 1
A2
M12
f
M
24
M
200
40 (50)
A3
M
M
200
GA
ø45
22
22
A1
M12
Insertion
depth 18 + 2
M10
Insertion
depth 15 + 1
A2
A
25
35
!
c
a
a1
T
pp
433
d
VD 4ABB
631
K
40 °
80 °
M12
310
282,5
77,5
345
409
424
44
550
100
M
30
60
368
480
24
A
608
95
ø115
30
475
M12
2.5 Dimensional drawings
Circuit-breakers for fixed installation
14
K = Cable entry
T = Handling bores, both sides
Note: Remove the lifting lugs on both sides before commissioning
A = View „A“
GA = Tested terminal zone
M = Minimum distance to DIN VDE 0101
A1 = Terminal for contact arm
A2 = Terminal for connecting bar
A3 = Terminal bar to DIN 46 433,
for 17.5 kV shrink sleeve fitted
= Earthing conductor terminal, use contact washer
1)
Breakers with rated currents 2500 A are fitted with a cooling element.
Figure 2/13: Dimensional drawing of circuit-breaker type VD4:
high-current.
• 12/17.5 kV, 1600 ...2500 A
1)
, ...40 kA
Figure 2/12: Dimensional drawing of circuit-breaker type VD4:
• 12/17.5 kV, ...1600 A, 40 kA.
K = Cable entry
T = Handling bores, both sides
Note: Remove the lifting lugs on both sides before commissioning
A = View „A“
GA = Tested terminal zone
M = Minimum distance to DIN VDE 0101
A1 = Terminal for contact arm
A2 = Terminal for connecting bar
A3 = Terminal bar to DIN 46 433
= Earthing conductor terminal, use contact washer
Rated Rated Rated
voltage current short-
circuit
breaking
current
kV A kA p a a
1
cde f g
12/17.5 ... 1250 40 210 610 515 520 570 345 390 409
... 1250 40 210 610 555 560 600 320 405 428
1600 40 210 610 555 560 600 320 405 428
275 750 695 700 750 345 512 428
A3
M12
24
f
M M50
GA
A - A
ø45
22
22
A2: M10/15 deep
+2
A1: M12/18 deep
+2
24
424
80°
670
475
77,5
40°
608
K
T
M
44
530
30
100
50
95
385
M12
237,5
310
588.5
e
g
434
550
a1
a
35
c 25
d
p p
A
A
ABB
!
VD 4ABB
616
385
670
599
40°
80°
f
a1
a
c
d
p p
200
M12
M M
24
M M
200
A3
80
12
A
12
20 20
20 20
35
433
25
M12
95
310237,5
78
M
M12
e
g
424
44
24
30
100
550
475
K
GA
608
A3
T
!
VD 4ABB
A
50
530
1)
1)
1)
A1
M10
Insertion depth
20+2
A2
M12
Insertion depth
25+2
Rated Rated Rated
voltage current short-
circuits
breaking
current
kV A kA p a a
1
cd e f g
12 1600 ... 31.5 210 610 555 560 600 320 405 409
... 2500
1)
275 750 695 700 750 345 512 409
12 1600 40 210 610 555 560 600 320 405 428
... 2500
1)
275 750 695 700 750 345 512 428
17.5 1600 ... 25 210 610 555 560 600 320 405 409
... 2500
1)
275 750 695 700 750 345 512 409
31.5 275 750 695 700 750 345 512 409
17,5 1600 40
... 2500
1)
275 750 695 700 750 345 512 428
15
Figure 2/14: Dimensional drawing of circuit-breaker type VD4:
high-current, 24 kV, ...2500 A, ... 25 kA.
K = Cable entry
T = Handling bores, both sides
Note: Remove the lifting lugs on both sides before commissioning
A = View „A“
GA = Tested terminal zone
M = Minimum distance to DIN VDE 0101
A1 = Terminal for contact arm
A2 = Terminal for connecting bar
A3 = Terminal bar to DIN 46 433,
for 24 kV shrink sleeve fitted
= Earthing conductor terminal, use contact washer
1)
Breakers with rated currents 2500 A are fitted with a cooling element.
Rated Rated Rated
voltage current short-
circuit
breaking
current
kV A kA p a a
1
cdf e
24 ... 2500
1)
... 25 275 750 695 700 750 512 345
661
642
A
385
670
608
M M
A3
K
T
200
M12
f
24
M M
200
80
A1
M10
Insertion depth
20+2
12
A
12
20 20
20 20
a1
a
35
c
433
25
M12
d
p p
95
310282,5
77,5
M
M12
e
409
424
4444
24
530
30
100
550
475
GA
A2
M12
Insertion depth
25+2
40°
80°
50
1)
1)
1)
!
VD 4ABB
16
Special arrangement for: -S5
Type 19 Type 20 Type 22 Type 23 Type 24
ON
OFF
Standard
arrangement
Type 21
1)
Only when -Y1 not fitted
2)
External operation
2.6 Circuit-breaker wiring diagram
– S1 Auxiliary switch on operating mechanism
– S2 Auxiliary switch on blocking magnet
– S3 Auxiliary switch on the breaker shaft
– S4 Auxiliary switch on the breaker shaft
– S5 Auxiliary switch on the breaker shaft
– S7 Auxiliary switch for fault annunciation
(fleeting contact, time
30 ms)
Figure 2/15 : Wiring diagram
Arrangement for DC 24, 48, 60, 110, 125, 220, 240 V; AC 110, 220, 240 V
– Y1 Blocking magnet
– Y2 Shunt release OFF
– Y3 Shunt release ON
– Y4 Undervoltage release
– Y7 Indirect overcurrent release
– Y9 Second shunt release OFF
– V1 Series rectifier for – Y1
– V2 Series rectifier for – Y2
Shown with the spring energy storage mechanism in the
discharged state. The wiring diagram comprises the
basic components and all further equipment options for
the various VD4 types. The scope of equipment possible
within an individual type series is listed in the relevant
switchgear list, and the equipment fitted in each indivi-
dual case can be found in the order documentation.
Note:
Shunt releases and blocking magnets are fundamentally
wired with rectifiers (e.g. magnet holder 40 with integrated
rectifiers -V1, -V2, -V3 and -V9).
Rectifiers function as free-wheeling diodes if d.c.-supply.
– V3 Series rectifier for – Y3 and – K0
– V4 Series rectifier for – Y4
– V9 Series rectifier for – Y9
– M0 Charging motor for spring
energy store
– K0 Anti-pumping relay
– R0 Series resistor
See page 54 for comparison of VDE/IEC designations.
17
3 Technical Data
Circuit-breakers on withdrawable part
3.1 Technical data and weight
1)
Breaker Rated Rated Rated short- Short- Rated short- Rated short- Pole Weight
1)3)
Permissible number
type voltage current circuit- circuit circuit circuit centres
1)
of vacuum interrupter
breaking breaking making duration switching operations
current current current
symm.
2)
asymm.
2)
(peak)
2)
VM1... kV A kA kA kA s mm approx. kg Figure 2/9 Page 11/12
1206-16 12 630 16 17.4 40 3 150/210 105/110 Diagram A
1212-16 1250 150/210 120/125 Diagram B
1206-20 630 20 21.8 50 3 150/210 105/110 Diagram C
1212-20 1250 150/210 120/125 Diagram D
1216-20 1600 210/275 190/195 Diagram D
1220-20 2000 210/275 195/200 Diagram D
1225-20 2500 275 205 Diagram D
1206-25 630 25 27.3 63 3 150/210 105/110 Diagram E
1212-25 1250 150/210 120/125 Diagram E
1216-25 1600 210/275 190/195 Diagram E
1220-25 2000 210/275 195/200 Diagram E
1225-25 2500 275 205 Diagram E
1206-31 630 31.5 34.3 80 3 150/210 105/110 Diagram F
1212-31 1250 150/210 120/125 Diagram F
1216-31 1600 210/275 190/195 Diagram F
1220-31 2000 210/275 195/200 Diagram F
1225-31 2500 275 205 Diagram F
1212-40 1250 40 43.6 100 3 210 185 Diagram G
1216-40 1600 210/275 190/195 Diagram G
1220-40 2000 210/275 195/200 Diagram G
1225-40 2500 275 205 Diagram G
1706-16 17.5 630 16 17.4 40 3 150/210 105/110 Diagram A
1712-16 1250 150/210 120/125 Diagram B
1706-20 630 20 21.8 50 3 150/210 105/110 Diagram D
1712-20 1250 150/210 120/125 Diagram D
1716-20 1600 210/275 190/195 Diagram D
1720-20 2000 210/275 195/200 Diagram D
1725-20 2500 275 205 Diagram D
1706-25 630 25 27.3 63 3 150/210 105/110 Diagram E
1712-25 1250 150/210 120/125 Diagram E
1716-25 1600 210/275 190/195 Diagram E
1720-25 2000 210/275 195/200 Diagram E
1725-25 2500 275 205 Diagram E
1706-31 630 31.5 34.3 80 3 150/210 105/110 Diagram F
1712-31 1250 150/210 120/125 Diagram F
1716-31 1600 210/275 190/195 Diagram F
1720-31 2000 210/275 195/200 Diagram F
1725-31 2500 275 205 Diagram F
1712-40 1250 40 43.6 100 3 210 185 Diagram G
1716-40 1600 210/275 190/195 Diagram G
1720-40 2000 210/275 195/200 Diagram G
1725-40 2500 275 205 Diagram G
1)
For more details to cell-type allocations see section dimensional drawings.
2)
When the operating voltage is lower than the rated voltage, the same values apply as for rated voltage.
Higher values on request.
3)
With manual charging mechanism.
Weight is increased by around 5 kg if charging motor is fitted.
Weight is increased by around 5 kg if the motor-driven withdrawable assembly is used.
18
Breaker Rated Rated Rated short- Short- Rated short- Rated short- Pole Weight
1)3)
Permissible number
type voltage current circuit- circuit circuit circuit centres
1)
of vacuum interrupter
breaking breaking making duration switching opartions
current current current
symm.
2)
asymm.
2)
(peak)
2)
VD4... kV A kA kA kA s mm approx. kg Figure 2/9 Page 11/12
2406-16 24 630 16 17.4 40 3 210/275 110/115 Diagram A
2412-16 1250 210/275 120/125 Diagram B
2416-16 1600 275 205 Diagram B
2420-16 2000 275 205 Diagram B
2425-16 2500
4)
275 205 Diagram B
2406-20 630 20 21.8 50 3 210/275 110/115 Diagram D
2412-20 1250 210/275 120/125 Diagram D
2416-20 1600 275 205 Diagram D
2420-20 2000 275 205 Diagram D
2425-20 2500
4)
275 205 Diagram D
2406-25 630 25 27.3 63 3 150/210 105/110 Diagram E
2412-25 1250 150/210 120/125 Diagram E
2416-25 1600 210/275 190/195 Diagram E
2420-25 2000 210/275 195/200 Diagram E
2425-25 2500
4)
275 205 Diagram E
1)
For more details to cell-type allocations see section dimensional drawings.
2)
When the operating voltage is lower than the rated voltage, the same values apply as for rated voltage.
Higher values on request.
3)
With manual charging mechanism.
Weight is increased by around 5 kg if charging motor is fitted.
Weight is increased by around 2 kg if the motor-driven withdrawable assembly is used.
4)
> 2300 A with fan cooling
19
p p
ø35
Q
ø74
260 205
25
303
306
383
438
370
21.5
4
50
200
0
-3
320
76
154
8
16
16
A
C
D
E
13.5
19
70.5
18
Stroke 8 -
11mm
55
Z
Y
!
VD 4ABB
2
R
O
N
+
-
)
**
)
*
J
G
30
1) 2)
T
1) 2)
S
1
F
1
Figure 3/1: Vacuum circuit-breaker on withdrawable part, type VD4.
Use in ZS1, UniGear Type ZS1, UniSafe and Powerbloc or mounting frame
12 kV, ...1250 A, ...31.5 kA
17.5 kV, ...1250 A, ...31.5 kA
3.2 Dimensional drawings
1)
Exists only for withdrawable parts of SACE (z.B. UniSafe)
2)
Versions up to 630 A with insulating tube
3)
Versions from 1250 A with shrink sleeve
4)
• With manual charging mechanism.
• Weight is increased by around 5 kg if charging motor is fitted.
• Weight is increased by around 2 kg if the motor-driven
withdrawable assembly is used.
Panel type Parameters Parameters Weight
5)
12 kV 17.5 kV p A C D E J Y
3)
Z
4)
ca. kg
ZS1/Powerbloc/
630 A, ...31.5 kA 630 A, ...31.5 kA 150 502 466 490 503 492 x - 105
Mounting
630 A, ...31.5 kA 630 A, ...31.5 kA 210 650 616 640 653 636 x - 110
frame
1250 A, ...31.5 kA 1250 A, ...31.5 kA 150 502 466 490 503 492 - x 120
1250 A, ...31.5 kA 1250 A, ...31.5 kA 210 650 616 640 653 636 - x 125
UniSafe/UniGear
630 A, ...31.5 kA 630 A, ...31.5 kA 150 502 466 490 503 492 x - 105
Type ZS1
1250 A, ...31.5 kA 1250 A, ...31.5 kA 150 502 466 490 503 492 - x 120
Panel type p F
1
G
1
NOQRS T
ZS1/Powerbloc/
150 38 203 624 618 628 618 128 120±1
Mounting frame
210 47 279 624 618 628 618 118 120±1
UniSafe/UniGear
150 38 203±1 624±2 618 628 620±2 128±1 120±1
Type ZS1
Table 1
Table 2
*)
Rail
**)
Front edge of bar
20
Figure 3/2: Vacuum circuit-breaker on withdrawable part, type VD4.
Use in ZS1, UniGear Type ZS1, UniSafe and Powerbloc or mounting frame
12/17.5 kV, ...1600 A, 40 kA
)
*
Stroke
8 - 11 mm
55
8
16
A
pp
16
J
F
30
O
N
D
13,5E13,5
19
R
310
ø
79
280
25
18
286
4
50
200
320
359,5
370
382,5
303
21,5
S
T
71
Q
76
165
±2
ø 120
1) 3)
2)
)
**
1
G
1
0
-3
1)
Only fitted on withdrawable parts for SACE (z.B. UniSafe)
2)
Remove the lifting lugs on both sides before commissioning
3)
Not available for Powerbloc/Mounting frame
• Weight (manual charging mechanism) 185 kg.
• Weight is increased by around 5 kg if charging motor is fitted.
Weight is increased by around 2 kg if the motor-driven with
drawable is used
*)
Rail
**)
Front edge of bar
Table 1:
Table 2:
Panel type
pF
1
G
1
NOQRS T
ZS1/ 210 44 276 694 688 698 688 118 110
Powerbloc/ 275 144 376 694 688 698 688 118 110
Mounting frame
Unisafe / 210 44±1 273±1 691±2 688 698 688±2 119 111±1
UniGear-type ZS1 275 144±1 373±1 691±2 688 698 688±2 119 111±1
Panel type Parameters p A D E J
12/17.5 kV
ZS1, UniSafe/ ...1250/1600 A, 40 kA 210 650 640 653 636
UniGear-Typ ZS1/
Powerbloc/ 1600 A, 40 kA 275 850 836 853 844
Mounting frame
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

ABB VD4 Series User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI