Hitachi RAM-8MQ Inverter-Driven Multi-Split System Air Conditioners User manual

Category
Split-system air conditioners
Type
User manual
1
INVERTER-DRIVEN
MULTI-SPLIT SYSTEM
AIR CONDITIONERS
Outdoor Units
InstallationMaintenance Manual
Models
8HP 10HP 12HP 14HP 16HP 18HP
RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D)
Be sure to hand over this manual to constructor of next step and finally let the customer keep it.
(Transportation and Handling) (Refrigerant Piping) (Electrical Wiring) (Test Run) (Customer)
Important Notice
z This air conditioner has been designed for common air conditioning for people. Do not apply to other purposes such as for food, animals,
plants, high precision machines or work of art.
z Do not install the unit in the following places. It may cause fire, deformation, corrosion or failure.
Places where is filled with mineral oil mist or oil spray (including machinery oil) or vapor is produced.
Places where is filled with sulfurous gas such as hot spring area.
z Do not install the unit in the following places, it may cause corrosion.
Places where strong salty wind blows such as coast regions.
An acid or alkaline environment.
z Pay attention to the following situations when the unit is installed in a hospital or other facilities where electromagnetic wave is radiated from
medical equipment.
Do not install the unit where the electromagnetic wave is directly radiated to the electrical box, remote control cable or remote control
switch.
To avoid the influence of electromagnetic waves via air, wave generating machines such as radio, medical equipment must be kept at
least 3 meters from air conditioner.
z Do not install the unit in the place where wind directly blows on animals or plants. It could adversely affect the animals or plants.
z Using wireless remote controller, the receiver may fail to receive signals due to effect of the lighting equipment. Therefore keep the receiver
away from the lighting equipment more than 1 meter as possible.
Safety Summary
z Before installation, read this section carefully in order to install correctly.
z This manual contains " Danger" symbol. This symbol indicates a hazardous situation which, if installed incorrectly, it may result in death or
serious injury. Therefore, make sure to observe important messages of safety.
z While checking any abnormality during the test run after installation, explain to customer the correct methods of usage and maintenance
according to the instructions of user’s manual. Then hand over the installation manual and user’s manual to customers.
Meaning of symbols
DANGERIndicates a hazardous situation which, If not avoided,
may result in death or serious injury.
Mandatory Symbol: indicate instructing behavior of
general users.
Mandatory Symbol: indicate grounding must be performed fo
r
machine with grounding terminal.
Indicate prohibited item.
About Electrical Works
DANGER
z Assign an authorized dealer to perform the electrical work. Please note that if improperly performed by yourself, it may result in
electric shock.
z Perform electrical work according to relevant national regulations and the installation manual. Make sure to use the exclusive
circuit to avoid electric shock or fire due to insufficient capacity of power or improper work.
z Use only specified wires for wirings between units. Incorrect selection of wires also causes fire or electric shock.
z Properly fasten the terminals of wirings. Improper fastening the joint of terminals may result in fire, electric shock or the
overheated terminals.
z Fix the cables securely. External forces on the terminals could lead to a fire.
z Installation of an earth leakage breaker (ELB) is necessary. If an ELB is not installed, current leakage may occur.
z When opening the service cover due to need of wiring work or inspection, make sure to completely cut off power before work
to avoid electric shock.
z Perform grounding according to the grounding work instructions. Incident of electric shock may occur if indoor and outdoor units
are not grounded. The ground wire must not be connected to gas pipe, water pipe, lighting rod and ground wire of telephone line.
If the ground wire is not properly connected, it may result in electric shock.
About installation
DANGER
z Installation must be done in accordance with this installation manual. Improper installation may result in water leakage, electric
shock or fire.
z Install the air conditioner on a foundation strong enough that it can withstand the weight of the unit. A foundation of insufficient
strength may result in the unit falling and injury.
z Do not perform installation at locations subject to existence or entry of flammable gas.
z Do not climb or put any object on the air conditioner to prevent injury caused by the unit falling.
z In the event of refrigerant leakage, immediately turn off the fire source (e.g. stoves), wipe the refrigerant off the floor, open the
door and windows for ventilation and then contact the service personnel or the dealer.
IMPORTANT:
READ AND UNDERSTAND
THIS MANUAL BEFORE
USING THIS HEAT-PUMP
AIR CONDITIONER.
KEEP THIS MANUAL FOR
FUTURE REFERENCE.
66MP1373
Before installation,
please read this manual
carefully and keep it properly.
2
DANGER
z Use the adequate non-flammable refrigerant (R410A) and refrigerant oil (Idemitsu Kosan Co.,Ltd.)(FVC68D) to the outdoor
unit in refrigerant cycle. Charging other refrigerant or refrigerant oil, oxygen, acetylene into the refrigerant cycle may result
in explosion or fire.
z This air conditioner contains high pressure gas, in any case, the unit or any part of the unit is prohibited to be heated. It may
result in machine malfunction, even explosion or fire.
1. Common Items
(1) Confirmation of unit model
1) Base unit
HP 8 10 12 14 16 18
Model RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D)
2) Combination of Base Units
HP 20 22 24 26 28
Model RAM-12MQ(D) RAM-10MQ(D) RAM-14MQ(D) RAM-14MQ(D) RAM-14MQ(D) RAM-14MQ(D)
RAM-8MQ(D) RAM-10MQ(D) RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D)
HP 30 32 34 36 38 40
Model
RAM-16MQ(D) RAM-16MQ(D) RAM-12MQ(D) RAM-12MQ(D) RAM-16MQ(D) RAM-16MQ(D)
RAM-14MQ(D) RAM-16MQ(D) RAM-12MQ(D) RAM-12MQ(D) RAM-12MQ(D) RAM-12MQ(D)
— — RAM-10MQ(D) RAM-12MQ(D) RAM-10MQ(D) RAM-12MQ(D)
HP 42 44 46 48 50 52
Model
RAM-16MQ(D) RAM-18MQ(D) RAM-18MQ(D) RAM-18MQ(D) RAM-18MQ(D) RAM-18MQ(D)
RAM-14MQ(D) RAM-14MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D) RAM-18MQ(D)
RAM-12MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-14MQ(D) RAM-14MQ(D) RAM-16MQ(D)
HP 54
Model
RAM-18MQ(D)
RAM-18MQ(D)
RAM-18MQ(D)
※:For 20~54HP, please refer to the table above to select the combination of base units.
(2) Combination of Indoor Unit and Outdoor Unit
Please refer to the table, select outdoor unit and indoor unit number and capacity.
(When the indoor unit does not fit " Minimum Individual Operation Capacity " in the table as shown below, It must not be
connect to the outdoor unit. Please pay particular attention!)
HP Indoor Unit
Range of
Combination Capacity
Maximum Connectable
Indoor Unit Number
The Suggestion of
Maximum Connectable
Indoor Unit Number
8
Max. 130%
13 8
10 16
10
12 19
14 23
16
16 26
18
20 33 18
22 36 20
24 40
26
26 43
28 47
32
30 50
32 53
34 56
36 59
38~54 64 38
Please refer to piping connection limit on P.9.
3
(1) Operation temperature range
Item Air Inlet Temperature of Outdoor Unit Air Inlet Temperature of Indoor Unit (Non-room Temperature)
Cooling -5DB 43 DB 21DB/15WB 32 DB/23 WB
DBDry Bulb WBWet Bulb
(2) When transporting the outdoor unit, observe the following items. Please transport the unit to the installation location under
packed condition.
(3) When hanging the outdoor unit, please follow the description of the label attached to the outdoor unit. After removing the
package, in order to avoid body damage, the unit needs protecting by corrugated board or cloth if moving again.
When hanging outdoor unit, please do not tie the ropes on wooden base or the inside of hanging square holes.
ExampleRAM-8MQ(D)
2. Transportation and Handling
木台
吊掛孔
錯誤
吊掛孔
繩索 繩索
正確
繩索位置
錯誤
繩索
CORRECT INCORRECT
INCORRECT
Rope
Wooden Base
Rope Rope
Square
Hole
Square
Hole
Corrugated Paper Frame
Do not remove corrugated
paper and plastic bands.
Do not apply any force to
this place.(Both Sides)
Rope
Wooden Base
Angle of ropes is more
than 60°.
Plywood or splint
thickness should
be more than 15mm.
Apply rope through the
square holes.
Corrugated Paper Frame
Do not apply any force to
this place.(Both Sides)
Do not remove corrugated
paper and plastic bands.
Angle of ropes is more
than 60°.
Rope
Plywood or splint
thickness should
be more than 15mm.
Apply rope through the
square holes.
4
3. Before Installation
(1) The pressure of refrigerant R410A is 1.4 times higher than conventional refrigerant; it is contaminated easily by moisture,
oxide, oil and other impurities. New refrigerant is adopted; therefore refrigerant oil also needs to be changed. When
installing, make sure to prevent moisture, oxide, oil, conventional refrigerant or refrigerant oil, or other impurities from
getting into the refrigerant cycle.
(2) To avoid accidental mixing of different refrigerant or different refrigerant oil, the size of the charging connectors must be
changed. It is necessary to prepare the following special R410A tools before performing the installation work.
Measuring instrument or tool which is directly contact to refrigerant must be used only for refrigerant R410A.
Symbol DescriptionFor new and old type refrigerant Only for R410A(not for R22)
Only for R407C(not for R22) For both R410A and R407C
Measuring Instrument and Tool
Interchangeability
with R22
Reason of Non-Interchangeability and Attention
(only for new refrigerant)
(Strictly Required)
Use
R407C R410A
Refrigerant
Pipe
Pipe Cutter Cutting Pipe
Removing Burrs
Flaring Tool ○□ To ensure the high pressure of R410A, if using flaring
tube, make dimension of tube larger for R410A. If
you continue to use existent products, shall be used
with the flaring tube adjustment gasket (1mm).
(R410A special flaring tool can be used directly in the
R407C)
Flaring for Tubes
Refrigerant
Pipe
Extrusion
Adjustment
Gauge
(not use)
Dimensional Control
for Extruded Portion
if Tube after Flaring
Pipe Bender If using the 1/2H pipe, it can not be processed.
Please use the elbow welding to connect. Bending
Expanding Tool If using the 1/2H pipe, it can not be processed.
Please use the elbow welding to connect. Expanding Tubes
Torque Wrench
R410A forΦ12.7Φ15.88; spanner size is up 2mm;
existent products can not be used. Connection of Flare Nut
For Φ6.35Φ9.53Φ19.05;
spanner size is the same.
Brazing Tool Perform correct brazing work. Brazing for Tubes
Nitrogen Gas Strict control against contamination.
(Blow nitrogen during brazing)
Prevention from Oxidation
during Brazing
Lubrication Oil
(for Flare
Surface)
Use a synthetic oil(FVC68D) which is equivalent
to the oil used in the refrigerant cycle.
Do not use R22 with mineral oil, and products must
be used the same synthetic oil.
Synthetic oil absorbs moisture quickly. Do not place
it in the humid environment.
Applying Oil to the Flared
Surface
Vacuum
Drying
Refrigerant
Change
Refrigerant
Cylinder
(Brown)
(Pink)
Check refrigerant cylinder color.
(R410A:Pink)(R407C:Brown)
Refrigerant must be charged in a state of liquid.
(Charging in a state of gas is strictly prohibited.)
Refrigerant Charging
Vacuum Pump The conventional ones are applicable. However,
it is required to mount a vacuum pump adapter
which can prevent from reverse flow when a
vacuum pump stops.
Vacuum Pumping
Adapter for
Vacuum Pump
(prevent from
reverse)
※●
Manifold Valve No interchangeability is available due to higher
pressure when compared with R22.
R410A connection diameter1/2 UNF
R407C connection diameter7/16 UNF
◎< Do not use conventional ones (R22) to the
different refrigerant ; If used, mineral oil will
flow into the cycle and cause sludge, resulting in
clogging or compressor failure.
Vacuum Pumping;
Vacuum Holding;
Refrigerant Charging
and Check of Pressures
Charging Hose
Charging Cylinder Prohibited Please use the weight scale. Refrigerant Charging
The ai
r
-ti
g
ht test
p
ressure of the
p
roduct is 4.15M
p
a.
5
+0
-0.4
Weight Scale Measuring Instrument for
Refrigerant Charging
Refrigerant Gas
Leakage Detector ※● The current gas leakage detector(R22) is not
applicable due to different detecting method. Gas Leakage Check
(3) The piping and connection parts use the following R410A. Flare nut and the front of pipe flare size also changes as shown
in the table below.
Unitmm
Pipe thickness selected
Unitmm
Diameter R410A
Thickness Material
¯6.35 0.8 O
¯9.53 0.8 O
¯12.7 0.8 O
¯15.88 1.0 O
¯19.05 1.0 1/2H
¯22.2 1.0 1/2H
¯25.4 1.0 1/2H
¯28.6 1.0 1/2H
¯31.75 1.1 1/2H
¯38.1 1.35 1/2H
¯41.3 1.20 1/2H
¯44.45 1.55 1/2H
Selection of joints
With the design pressure changes, the connection pipe (elbow etc.) thickness are also changes. When using 1/2H
material, the bending and flaring can not be processed, so please follow the table below to choose the minimum
thickness that appropriate to the connecting pipe. Please note that there are several changes in flare nut size.
Connection minimum thickness (mm)
Diameter R410A Diameter R410A
¯6.35 0.5 ¯25.4 0.95
¯9.53 0.6 ¯28.6 1.0
¯12.7 0.7 ¯31.75 1.1
¯15.88 0.8 ¯38.1 1.35
¯19.05 0.8 ¯41.3 1.45
¯22.2 0.9 ¯44.45 1.55
Flare Nut dimension B (mm)
Diameter Flare Nut dimension B(mm) Diameter Flare Nut dimension B(mm)
R410A R410A
¯6.35 17 ¯15.88 29
¯9.53 22 ¯19.05 36
¯12.7 26
Diameter ¯d Dimension ¯A
R410A
¯6.35 ¯9.1
¯9.53 ¯13.2
¯12.7 ¯16.6
¯15.88 ¯19.7
¯19.05 Can not be processed
(1/2H material)
Flare Nut
Pipe Flare Size
6
Season
winds
A
ir inlet
If the season
winds blows
directly,
defrost time
will increase.
Season
winds
A
ir inlet
A
ir inlet
A
ir inlet
Windbreak
4. Installation Work
(1) Selection of Installation Location
1) Make sure the space for operation and maintenance service is secured around the outdoor unit.
2) Install the outdoor unit where it is dry and well ventilated.
3) Install the outdoor unit where it is in the shade or it will not be exposed to direct sunshine or direct radiation from high
temperature heat source.
4) Install the outdoor unit where the operating sound does not affect neighbors.
5) The outlet air does not directly blow to plants or neighbor’s windows.
6) The foundation is strong enough to support the weight and withstand vibrations of the outdoor unit.
7) Do not install the outdoor unit where dust or other contamination could block the heat exchanger of the unit.
8) Do not install the outdoor unit where strong wind could blow to the unit from the air outlet side.
9) Do not install the unit inside the house.
10) Do not place flammable objects near the unit, it may result in fire.
11) Do not install the outdoor unit where there is a high concentration of oil spray, salty air or harmful gases such as sulfurous
gas.
12) Do not install the outdoor unit where the electromagnetic wave directly radiates to the electrical box.
13) To avoid the influence of electromagnetic waves, wave generating machines such as radio should be kept 3 meters from
electromagnetic wave radiator.
(2) Installation Space
1) Ensure the maintenance space around the outdoor unit as shown below. The insufficient air inlet and outlet space may
result in insufficient air intake, poor performance, and other problems. Please be sure to follow it for the convenience of
maintenance.
If the wall of front side is higher than 1,500 mm, the required space is 500h2/2mm.
If the wall of rear side is higher than 500 mm, the required space is 300h1/2mm.
If there are no walls at the front and rear side, the required spaces for the front and
rear side are 500 mm and 300 mm.
If the unit is surrounded by walls, make a ventilation hole on the wall.
Leave space between the top side and wall.
2) Leave the service space when outdoor unit is installed
 1.Walls in 2 Directions
 2.Walls in 3 Directions
Single Unit Installation
Windbreak
Fence
Unit:mm
Unit:mm
7
Multiple Unit Installation
3.Walls in 4 Directions
Single Unit Installation
Multiple Unit Installation
Keep the upper side open.
The front side should be less than 1,500mm; air inlet side should be less than 500mm; other sides are no limits.
If the heights are beyond the limits, add h1/2mm and h2/2mm on the front side and air inlet side respectively.
For the multiple installation, one group allows 6 outdoor units(max.).The required space between each set is at least
1m.
The walls should be partially open if the unit is surrounded by walls in four directions.
NoteIf the distance between unit and obstacles/ceilings is less than 1,500mm or the space is closed, set up the
duct on the air outlet side to prevent the return air.
Unitmm
8
(3) Foundation Work
Please perform this work properly. Ensure the unit does not lean, vibrate, make a noise or fall in the event of strong wind or
earthquake.
1) The height of the base should be 150 mm higher than the ground level.
2) Perform adequate drainage around the foundation.
3) All foot of the outdoor unit need installing on the base.
4) Install the outdoor unit horizontally (Use a level gauge). Ensure the horizontal tolerance is within 10mm.
5) Precautions
The concrete base should be set along the foot direction as shown below. Incorrect installation may cause the foot of the
outdoor unit deformation.
(4) Anchor Bolt Installation Dimensions
RAM-8~12MQ(D) RAM-14~18MQ(D)
Unitmm
(5) Confirmation of drainage
1) When Defrosting operate, the condensation water will be discharged. Select the best area for drainage.
The drain hole position is shown below
RAM-8MQ(D)~12MQ(D) RAM-14MQ(D)~18MQ(D)
Refrigerant Gas Piping
Connection Hole (¯60) Refrigerant Liquid Piping
Connection Hole
¯47
)
Circuit Control Connection
Hole (¯26x2)
Drain Hole (¯26)
Drain Connector
Position
Unitmm
Hole of Anchor Bolt Hole of Anchor Bolt
4-38x15 4-38x15
Refrigerant Gas Piping
Connection Hole (¯60) Refrigerant Liquid Piping
Connection Hole
¯
47
)
Circuit Control Connection Hole (¯26x2)
Drain Hole (¯26)
Drain Connector Position
Power Su
pp
l
y
Connection Hole
(
¯
52
)
Power Su
pp
l
y
Connection Hole
(
¯
52
)
9
2) Drain connector installation methods:
 1.Set the washer on the upper part of drain connector.
 2.According to the shape of base drain holes, insert
the drain connector and turn it clockwise about 40°.
 3.Drain connector is equivalent to VP20.
 4.Drain pipe is field supplied.
NoteThe drain connector is installed
for discharging condensation water
5. Refrigerant Piping
(1) Refrigerant Piping
1) Selection of refrigerant pipes
 1.Please prepare field supplied copper pipes.
 2.Select the piping size as the table below.
3.Select clean copper pipes. Be sure that there is no dust and moisture inside of the pipes.
Cut the copper pipes with a pipe cutter. Blow the inside of the pipes with nitrogen or dry air to remove dust or foreign
materials before connecting pipes. (Do not use a saw, a grindstone or other tool which may cause cutting powder.)
Cautions for refrigerant piping
2) Refrigerant piping limitation and multi-kit
 1.The order of piping connection kit is counted from the indoor unit side(as Branch Pipe 1).
 2.When the maximum length of the equivalent refrigerant pipe(L1)from First Multi-kit to the indoor unit is over 100mm, the
size of gas/liquid pipes from the Piping Connection Kit 1 to the First Multi-kit should be increased one size with the
reducer(field-supplied).
 3.The size of multi-kit between the indoor units should be the same as the size of the indoor unit pipes.
 4.When the liquid piping length is longer than 15m, please useφ9.53 pipe(field-supplied).
 5.Keep the straight line distance longer than 500mm or more after the piping connection kit.
 6.The condition of refrigerant piping installation varies depending on the quantity of indoor units.
 7.Due to the maximum charging of refrigerant, the total piping length should be less than 1,000m.
Piping between Outdoor Unit and First Multi-kit
HP
Gas/Liquid Pipe Size (Φmm)
Equivalent Length100m Equivalent Length100m
8 19.05 / 9.53 22.2 / 12.7
10 22.2 / 9.53 25.4 / 12.7
12~14 25.4 / 12.7 28.6 / 15.88
16 28.6 / 12.7 31.75 / 15.88
18~24 28.6 / 15.88 31.75 / 19.05
26~34 31.75 / 19.05 34.9 / 22.2
36~54 38.1 / 19.05 41.3 / 22.2
配管不可直接放到地上
Convex
Drain Connector
Base Drain
Hole
Washer
Drain Pipe
(Field Supplied)
Drain Connector
When installing pipe through the wall,
secure a cap at the end of the pipe.
CORRECT
CORRECT CORRECT
INCORRECT
INCORRECT
INCORRECT
Hole Hole
A
ttach a cap or vinyl tape
Do not place the pipe directly on the
ground.
A
ttach a cap or vinyl tape
A
ttach a cap or vinyl bag with rubber
band.
Rain water can enter
CORRECT
10
Piping Size and Multi-Kit Selection
Example of System :
The figure is an example which shows the combination
of indoor and outdoor units.
The refrigerant pipes which contain gas/ liquid
pipes are shown in single lines for simplification.
Item
Allowable length
The number of indoor unit is
less than the recommended
maximum combined number
of units.
The number of indoor unit
exceeds the recommended
maximum combined number
of units.
Maximum Piping
Length
Actual length L 1165m
Equivalent length L 1190m
Total length L t1000m L
t300m
Maximum Piping
Length
Length between First Multi-kit and the
furthest indoor unit L 290m L
240m
Length between each Multi-kit and Each
indoor unit L 340m L
330m
Length between Piping Connection Kit 1 and
the furthest outdoor unit L 510m
Maximum Height
Difference
between Outdoor
and Indoor Unit
If the outdoor unit is higher than indoor unit. H 150m
If the indoor unit is higher than outdoor unit. H 140m
Height difference between Each indoor unit H 215m
Height difference between Each outdoor unit H 50.1m
Multi-kit and Piping
First Multi-kit
Outdoor Unit
(HP)
Gas/Liquid
Piping
Diameter
(¯mm)
(L 1 100m)
Gas/Liquid
Piping
Diameter
(¯mm)
(L 1 100m)
Multi-Kit Type
8 19.05 / 9.53 22.2 / 12.7 E-NP282S
10 22.2 / 9.53 25.4 / 12.7
12~14 25.4 / 12.7 28.6 / 15.88 E-NP452S
16 28.6 / 12.7 31.75 / 15.88
18~24 28.6 / 15.88 31.75 / 19.05 E-NP692S
26~34 31.75 / 19.05 34.9 / 22.2
E-NP902S
36~54 38.1 / 19.05 41.3 / 22.2
Other Multi-kits
Indoor Unit Total
Capacity (kW)
Gas/Liquid Piping Diameter
(¯mm) Multi-Kit Type
101.0 38.1 / 19.05 E-NP902S
73.0~100.9 31.75 / 19.05
50.0~72.9 28.6 / 15.88 E-NP692S
45.0~49.9 28.6 / 12.7 E-NP452S
33.5~44.9 25.4 / 12.7
25.0~33.4 22.2 / 9.53
E-NP282S
16.0~24.9 19.05 / 9.53
15.9 15.88 / 9.53
Equivalent length= Actual length+ Additional length(Elbow, Bend and Multi-Kit)
One 90°Elbow is 0.5m.
One 180°Bend is 1.5m.
One Multi-Kit is 0.5m.
室內機
分歧管 1 分歧管 2
第一分歧管
室內機 室內機
室內機 室內機 室內機
Master (A) Slave (C)
Slave (B)
First
Multi-Kit
Piping
Connection Kit 1 Piping
Connection Kit 2
Indoor Indoor Indoor
Indoor Indoor Indoor
11
Piping diameter restriction between Multi-Kit and indoor units:
Piping Diameter
Indoor Unit
Capacity (kW)
Gas/Liquid Piping Diameter (¯mm)
2.2~4.5 12.7 / 6.35
5.0~5.6 15.88 / 6.35
6.3~16.0 15.88 / 9.53
※:When piping length exceeds 15m, liquid piping diameter must change to Φ9.53.
Piping diameter restriction on indoor units:
Model RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D)
RAM-18MQ(D)
Piping
Size
a100m Gas Piping 22.2 25.4 28.6 31.75
Liquid Piping 12.7 15.88 19.05
a100m Gas Piping 19.05 22.2 25.4 28.6
Liquid Piping 9.53 12.7 15.88
HP 20 20 22 24 26 28 30 32
Combination
Model
Master (A) 10MQ(D) 12MQ(D) 14MQ(D) 14MQ(D) 14MQ(D) 14MQ(D) 16MQ(D) 16MQ(D)
Slave (B) 10MQ(D) 8MQ(D) 8MQ(D) 10MQ(D) 12MQ(D) 14MQ(D) 14MQ(D) 16MQ(D)
Piping Connection Kit E-NP692S E-NP902S
Piping
Size
a100m
Gas
Piping 31.75 34.9
Liquid
Piping 19.05 22.2
a100m
Gas
Piping 28.6 31.75
Liquid
Piping 15.88 19.05
b
Gas
Piping 22.2 25.4 28.6
Liquid
Piping 9.53 12.7
c
Gas
Piping 22.2 19.05 22.2 25.4 28.6
Liquid
Piping 9.53 12.7
Slave (B) Slave (B) Master (A)
Master (A)
Outdoor Unit
12
HP 34 36 38 40 42 44 46 48 50 52 54
Combination
Model
Master (A) 12MQ(D) 12MQ(D) 16MQ(D) 16MQ(D) 16MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D)
Slave (B) 12MQ(D) 12MQ(D) 12MQ(D) 12MQ(D) 14MQ(D) 14MQ(D) 14MQ(D) 16MQ(D) 18MQ(D) 18MQ(D) 18MQ(D)
Slave (C) 10MQ(D) 12MQ(D) 10MQ(D) 12MQ(D) 12MQ(D) 12MQ(D) 14MQ(D) 14MQ(D) 14MQ(D) 16MQ(D) 18MQ(D)
Piping Connection Kit E-NP902S×2
Piping
Size
a100m
Gas
Piping 34.9 41.3
Liquid
Piping 22.2
a100m
Gas
Piping 31.75 38.1
Liquid
Piping 19.05
b
Gas
Piping 28.6 31.75
Liquid
Piping 15.88 19.05
c
Gas
Piping 25.4 28.6
Liquid
Piping 12.7 15.88
d
Gas
Piping 25.4 28.5
Liquid
Piping 12.7 15.88
e
Gas
Piping 22.2 25.4 22.2 25.4 28.6
Liquid
Piping 9.53 12.7 9.53 12.7 15.88
Please follow the requirement when performing multi-kit piping. Remove the spare parts of pipes can ensure operational
capacity and prevent noise.
Type E-NP282S E-NP452S
Gas
Piping
Q’ty 1 1
Master (A) Master (A)
Slave (B) Slave (C) Slave (B)
Slave (C)
13
底座
前後框
回油彎折高度
200mm以上
回油彎折高度
200mm以上
回油彎折高度
200mm以上
300mm以下
300mm以下
連接至室內機
連接至室內機
300mm以下
Liquid
Piping
Q’ty 1 1
Type E-NP692S E-NP902S
Gas
Piping
Q’ty 1 1
Liquid
Piping
Q’ty 1 1
(2) Caution about Outdoor Unit Installation
 1.Align the outdoor units and locate large capacity Master (A) on the indoor unit side. Piping length between Piping
Connection Kit 1 and each outdoor unit should be less than 10m.
 2.Place the piping connection kit lower than the outdoor unit piping connection.
In case that the piping connection kit is placed higher than the outdoor unit piping connection, keep 300mm (max.)
between the piping connection kit and the bottom of the outdoor unit. Also, provide an oil trap (min.200mm) between the
piping connection kit and the outdoor unit.
分歧管
室外機
各室外機間高度
連接
室內機
LL
Pi
p
in
g
Len
g
thL
A
LB
LC
10m
Master
(A)
Slave
(B)
Slave
(C)
L
HPMaster
(
A
)
Slave
(
B
)
Slave
(
C
)
0.1m
Indoor Unit Side
Piping
Connection
Kit
Keep the pipes straight at least 0.5m
after piping connection kits.
Max. Lift Difference
between Outdoor
Unit = 0.1m
Master
(A)
Slave
(B)
Slave
(C)
Indoor Unit Side
Indoor Unit Side
Oil Trap
Min. 200mm
Max.300mm Max.300mm
Max.300mm
Base
Bottom of
Outdoor Uni
t
Oil Trap
Min. 200mm
Oil Trap
Min. 200mm
14
連接至室內機
冷涷油囤積
連接至室內機
2m以下
回油彎折高度
200mm以上
2m以上
2m以下
連接至室內機
2m以下
連接至室內機
2m以上
2m以下
回油彎折高度
200mm以上
15
以內
(親機) (子機)
室外機 室外機
(子機)
室外機
連接至室內機
500mm以
室外機
1/3
室外機
2/3
室外機
3/3
Gas Piping
(Field Supplied)
Piping Connection
Kit 1
(
Gas
)
Outdoor 1/3
Outdoor 2/3
Outdoor 3/3
Gas Piping
Liquid Piping
Gas Piping
Piping Connection
Kit 2
(
Gas
)
Piping Connection
Kit 1
(
Li
q
uid
)
Piping Connection
Kit 2
(
Li
q
uid
)
Liquid Piping
Liquid Piping
(Field Supplied)
(Field Supplied)
(Field Supplied) (Field Supplied)
Piping Connector
(L-Shape)
Piping Connector
(L-Shape)
Piping Connector
(L-Shape)
Piping Connector
(L-Shape)
(Field Supplied)
Outdoor 1/3
Front or Rear Side Pi
p
in
g
Connection
冷媒液配管連接口
冷媒氣配管連接口(高壓)
 3.Piping length between piping connection kit (at outdoor unit side) and outdoor unit should be less than 2m.
In case that the piping length between outdoor units exceeds 2m, an oil trap (min.200mm) should be provided
for the gas pipe so that accumulation of refrigerant oil may not occur.
 4.Ensure the direction of outdoor unit pipes is horizontal or with downward gradient towards the indoor unit side to
avoid accumulating refrigerant oil in the pipe.
 5.For maintenance, if the pipe is placed in front of the outdoor unit,
secure at least 500mm between the outdoor units and the piping connection kits.
 6.Place the piping connection kits horizontally (within ±15°).
 7.Piping connection of outdoor unit, please refer to the following figure.
Indoor Unit Side Indoor Unit Side
Indoor Unit Side Indoor Unit Side
Indoor Unit Side
Within±15°
500mm
Master
(A)
Slave
(B)
Refrigerant oil
accumulates in the pipe.
Less than 2m Less than 2m
Less than 2m Less than 2m
2m or more 2m or more
Oil Trap
Min. 200mm Oil Trap
Min. 200mm
Outdoor Unit
Gas Line Refrigerant Piping
Connection
Liquid Line Refrigerant
Piping Connection
Master
(A)
Slave
(B)
Slave
(C)
Master
(A)
Slave
(B)
Slave
(C)
Master
(A)
Slave
(B)
Slave
(C)
Master
(A)
Slave
(B)
Slave
(C)
Slave
(
C
)
(F
15
冷媒液配管連接口(高壓)
D 冷媒液配管連接口
C 冷媒氣配管連接口
A 冷媒氣配管連接口
B 冷媒液配管連接口
245
145
100
冷媒液配管連接口
室外機
1/3
室外機
2/3
室外機
3/3
分歧管
2(
液配管
)
2( )
Outdoor 1/3
Outdoor 2/3
Outdoor 3/3
Gas Piping
Liquid Piping
Gas Piping
Liquid Piping
Piping Connector
(Z-Shape)
Piping Connector
(Z-Shape)
Piping Connector
(L-Shape)
Piping Connector
(L-Shape)
(Field Supplied)
(Field Supplied)
(Field Supplied) (Field Supplied)
Piping Connection
Kit 1
(
Gas
)
Piping Connection
Kit 2
(
Gas
)
Piping Connection
Kit 1
(
Li
q
uid
)
Piping Connection
Kit 2
(
Li
q
uid
)
Gas Line Refrigerant Piping
Connection
Liquid Line Refrigerant
Piping Connection
Downward Piping Connection
(3) Pipe Connection Position
Model
A B C D
Gas Line Refrigerant
Piping Connection
Liquid Line Refrigerant
Piping Connection
Gas Line Refrigerant
Piping Connection
Liquid Line Refrigerant
Piping Connection
RAM-8MQ(D)
150 155
320
335
RAM-10MQ(D)
315
RAM-12MQ(D)
RAM-14MQ(D)
170 175
RAM-16MQ(D)
RAM-18MQ(D)
Unit:mm
D
C
100
A
B
16
室外機
1
分歧
2
分歧
3
分歧
最佳安裝狀況
容許安裝狀況
1
分歧
2
分歧
3
分歧
室外機
錯誤
室外機
1
分歧
2
分歧
3
分歧
4
分歧
錯誤
第 1 主分歧
2主
分歧
第 1 主分歧
1
分歧
2
分歧
3
分歧
室外機
2
主分歧
室外機
第 1 主分歧
2
主分歧
2
主分歧
第 1 主分歧
(4) Setting of the multi-kit pipe
It is necessary to use optional multi-kit to prevent unit’s insufficient capacity due to the uneven distribution of
the refrigerant. Do not use connectors to connect.
1) The installation of the main branch as shown below
Main Pipe (The pipe between each multi-kit or the pipe between the outdoor units and the first multi-kit)
Main BranchOne multi-kit is connected with other multi-kits connected with more than one indoor unit.
Setting ConditionThe branches extending to third are allowed, but main branches can only extend to second.
 Piping length within 40 m between the first branch and the indoor units :
 Piping length in excess of 40 m between the first branch and the indoor units
Only one main branch is allowed, and total indoor unit capacity should be in the range of 40% to 60% for each
route after the first main branch.
Indoor
Unit Total
Capacity
50%
Indoor
Unit Total
Capacity
50% 71Type
71Type
71Type
71Type
y
71Type
71Type
Indoor
Unit Total
Capacity
33%
Indoor
Unit Total
Capacity
67%
140Type
71Type
71Type
71Type
140Type
140Type
3
分歧
2
主分歧
Best installation situation
A
llowing installation situation
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor Outdoor Outdoor
A
llowing installation situation
A
llowing installation situation
A
llowing installation situation
First Main Branch
First Main Branch
First Main Branch First Main Branch
First Main Branch First Main Branch First Main Branch
Second Main Branch
Second Main Branch
Second Main Branch
First Branch
First Branch
First Branch
First Branch
Second Branch
Second Branch
Second Branch Second Branch
Second Main Branch
Second Main Branch
First Branch
Third Branch Third Branch
Third Branch
Third Branch
Third Branch
Fourth Branch
Pi
p
e Len
g
th 40m~90m Pi
p
e Len
g
th 40m~90m
Incorrect
Incorrect
17
[支撐方法]
直管部
0.5m 以上
直管部
0.5m 以上
2) Fixed the multi-kit piping
1.Horizontal
The branch pipe must be set in the same plane.
Keep the outdoor unit pipes straight at least 0.5m after piping connection kits.
 2.Vertical
Upward BranchKeep the outdoor unit pipes straight at least 0.5m after piping connection kits.
Downward BranchKeep the outdoor unit pipes straight at least 0.5m after piping connection kits.
(5) Refrigerant piping fixation methods:
Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Fix the refrigerant piping at certain points
and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc.( If touched,
abnormal sound may occur due to the vibration of the piping, especially in the case of short length piping.)
(6) Piping Direction
1) The pipes are available to connect in five directions (front, rear, left, right or bottom side) from bottom base.
2) Please weld the flange combination and connection pipe in advance, and then lock with the gas stop valve.
3) In order to prevent rainwater and insects from entering into the unit, please fill the gap between piping hole and pipes with
insulator.
Pipe Size Φ22.2 Φ25.4
Max. Interval 1.0m 1.5m
傾斜角度
15
以內
15
傾斜角度
底座 (底面側)
下配管 後配管
(背面側)
(正面側)
前配管
左配管
(左面側)
右配管
(右面側)
Flange Combination
Bolt 2 Piece
Spring Washer 2 Piece
Flat Washer 2 Piece
A
ttached Washer
Original
Washer
Gas Stop
Val ve Set
Closed Flange
Discard
Flare Nut
Spring Washer 2 Piece
Flat Washer 2 Piece
Right Piping
(Right Side)
Front Piping
(Front Side)
Left Piping
(Left Side)
Base Bottom Piping
(Bottom Side)
Rear Piping
(Rear Side)
Up Up
Up Up
Down Down
Down Down
Straight Pipe
Straight Pipe
Straight Pipe
0.5m Above
0.5m Above
0.5m Above
Up
In the same
Horizon Plane
Upward Branch
Downward Branch Tilt Angle
Within 15°
Tilt Angle
(A Direction)
Outdoor Unit
Indoor Unit
(Fixation Methods Example)
Piping Fixation Interval
18
Use special tools and measuring instruments only for the new refrigerant R410A.
If vacuum degree -0.1MPa is not available, it is considered that leakage and moisture exist.
(7) Refrigerant Piping Work
1) Confirm that the stop valves of outdoor unit are closed.
2) Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Fix the refrigerant piping at certain points
and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc.( If touched,
abnormal sound may occur due to the vibration of the piping, especially short length piping.)
3) Please connect the piping between indoor and outdoor unit. When tightening the joints of piping, coat inside and outside of
flare piping with a layer of refrigerant oil [Field-supplied (Idemitsu Kosan Co., Ltd. Synthetic oil”FVC68D”)], and use double
spanner to tighten with specific tightening torque. After tightened, please confirm the gas leakage once more. During
brazing, please blow nitrogen into the piping.
4) Before air-tight test, please re-tighten the gas line stop valve spindle.
(a) After flange connection, open the gas line stop valve cap and tighten the spindle with 20 ~ 25 N • m of torque.
(b) Removing the valve cap will cause voice due to slight gas leakage, but the condition is normal.
5) Please perform the air-tight test.
Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the
liquid line and the gas line stop valves. Perform the air-tight test. Apply gas pressure of 4.15MPa.
6) Insulate the unions and flare-nuts at the piping connections completely. Insulate the liquid piping and gas piping completely
to avoid decreasing performance and dewing on the surface of the pipe.
Required Torque
(8) Vacuum Work
About the details of stop valve operation, please refer to the nameplate inside service cover.
1) Connect a manifold gauge to the check joints at the both sides. Continue vacuum pumping work until the pressure
reaches-0.1MPa or lower for one to two hours. After vacuum pumping work, shut the manifold valve, stop the vacuum
pump and leave it for one hour. Check to ensure that the pressure in the manifold gauge does not increase.
2) Because check joints and flare nut cannot be connected, please use the charging hoses. After the work, please tighten the
flare nut with 15~16N • m torque.
3) Vacuum drying determination example
Piping Size (mm) Tightening Torque
¯6.35(1/4”) 20N˙m
¯9.53(3/8”) 40N˙m
¯12.7(1/2”) 60N˙m
¯15.88(5/8”) 80N˙m
¯19.05(3/4”) 100N˙m
Flange With Bolt 53~75 N˙m
Please implement vacuum drying determination, to confirm whether moisture exists within the system. If moisture is
present, please extend the vacuum time or install the drying filter until no moisture is present within the system. Be sure
to do this work, otherwise the unit may be damage easily and difficult to handle.
Vacuum Degree
Vacuum Time (min)
Figure1Vacuum Time and Vacuum Degree
Outside air temperature 23°C
Vacuum pump stop
After the vacuum pump
stop, the vacuum degree
rebound phenomenon
Vacuum Degree
Figure2 Vacuum time and degree with moisture in system
Outside air temperature 20°C
System with
moisture
System without
moisture
Vacuum Degree
Vacuum Time (min)
Figure3Outside air temperature vacuum time and degree
System with
moisture, outside air
temperature 20°C
System with
moisture, outside air
temperature 10°C
The system without moisture is not
affected by outside air temperature.
(
Double spanner work Stop valve tightening work
Do not apply the double spanner work here.
(Refrigerant leakage will occur)
Vacuum Time (min)
19
(9) The Additional Refrigerant
Outdoor unit has been filled with refrigerant, but still need to add an appropriate amount of refrigerant based on the length
of the pipe.
Please follow the steps below to calculate the additional amount of refrigerant, and fill the outdoor unit with it.
Note:
W0 is outdoor unit ref. charge before shipment.
In case of the combination of the base unit, calculate
the total ref. charge before shipment of the outdoor
units to be combined.
<Max. Additional Refrigerant Charge Quantity>
Outdoor Unit RAM-8,10MQ(D) RAM-12MQ(D) RAM-14,16MQ(D) RAM-18MQ(D),
20~24HP 26~54HP
Max. Additional Ref.
Charge Quantity 28.0 36.0 40.0 51.0 63.0
Model W0 Outdoor Unit Ref. Charge(Kg)
RAM-8~10MQ(D) 6.5
RAM-12MQ(D) 7.5
RAM-14MQ(D)
9.0
RAM-16MQ(D)
RAM-18MQ(D) 10.5
W Wo = 100 kg
1. Calculation of Additional Refrigerant W (kg)
No.
kg
22.2
x1.0kg/unit =
1 W1
19.05
15.88
12.7
9.53
6.35
m
m
m
m
m
m
x0.39=
x0.28=
x0.19=
x0.12=
x0.06=
x0.03=
/
/
kg
W
kg
Refrigerant Content Additional Refrigerant (kg)
A
dditional Amount of Refrigerant for Liquid Pipe W1(kg)
Pipe Size Pipe Length (m) The Amount of
Refri
g
erant Pe
r
Mete
r
Additional Amount
of Refrigerant W1(kg)
Total Amount of Additional Refrigerant for Liquid Pipe
A
dditional Amount of Refrigerant for Indoor Unit W2(kg)
8HP, 10HP each indoor unit needs addition 1 kg of refrigerant.
There is no addition of refrigerant for the unit less than 8HP.
The Total Number of 8HP, 10HP Indoor Unit
A
dditional Amount of Refrigerant W2(kg)
Calculation of Indoor Unit Connection Capacity Ratio
Indoor Unit
T
otal Ca
p
acit
y
/ Outdoor Unit Ca
p
acit
y
Condition Additional Amount of Refrigerant W3(kg)
Connection Capacity Ratio 100% 0.0kg
Connection Capacity Ratio 100 ~ 115% 0.5kg
Connection Capacity Ratio 116 ~ 130% 1.0kg
A
dditional Amount of Refri
g
erant W
(
k
g)
(
W1W2W3
)
Ref. Charge Amount of O.U Before Shipment (W0) kg
2. Additional Refrigerant Filling Amount Records
Please refer to the following formula to calculate the
total charges of system
Total charges of system
W
W
0
Note:
W0 : Factory refrigerant charging weight.
A
dditional Refrigerant:
System Refrigerant:
A
dditional Refrigerant Date:
W2
W3
W
2
3
4
kg
kg
kg
20
(1)無論是大中室、小室極小室對於洩漏冷媒量皆以 20kg 來計算。
Maximum
p
ermissible concentration
(
k
g
/ m3
)
R410
A
( (0.3k / )
1) Fully open the gas line stop valve.
2) After cooling operation starts, connect the gauge manifold
using charging hoses with a refrigerant charging cylinder
to the check joints of the liquid line stop valve to charge
refrigerant. (Refrigerant charging quantity error tolerance:
±0.5kg around.) In the meantime, the liquid line stop valve
is slightly open.
3) Fully open the liquid line stop valve after completing
refrigerant charge.
4) Please be sure to perform the air-tight test.
5) The check joints on the accumulator is used to fill
refrigeration oil, do not use for other purposes.
(10) Caution of The Refrigerant Leakage
When an air conditioner is installed in a room, in case of refrigerant leakage, refrigerant concentration must not exceed the
maximum permissible concentration.
The products use non-flammable, non-toxic safe refrigerant R410A. If leakage occurs and gas fills a room, it may cause
suffocation. Especially for multiple indoor units and outdoor units with long-distance piping connection, the amount of
refrigerant is more than individual air-conditioner. So make sure the indoor unit installed in the room, even in case of
refrigerant leakage, the refrigerant concentration should never exceed the maximum permissible concentration.
Please calculate the refrigerant concentration by the following formula
The total amount of charged refrigerant (kg)
Room space for each indoor unit (m3)
If a room’s refrigerant concentration is more than the maximum permissible concentration and the air conditioner still need
to be installed, please choose a treatment method according to the following
1.Set refrigerant leakage detector alarm and link it to mechanical ventilation devices. (See below) (Cooling capacity per ton
should be more than 0.4 m3/min ventilation capacity. Cooling capacity is shown in following table according to the outdoor
unit capacity.)
2.Set the effective ventilation outlet between adjacent rooms (The outlet area need to be more than 0.15% floor area on the
upper and lower of the door), so that the leakage of refrigerant concentration can drop less than the maximum permissible
concentration.
New refrigerant R410A product notes:
Since R410A is a non-azeotropic refrigerant, when leakage occurs, the proportion of
mixture will change. Do not charge new refrigerant directly; the whole system must
be re-processed.
Outdoor
Unit
Cooling
Capacity
R410A
冷媒配管作業要領圖
Outdoor Unit
Gas Piping
Liquid Piping
Branch Pipe
Refrigerant Piping Work Diagram
Indoor Unit Indoor Unit
Pipe connection part
union and flare nut, be
sure to do insulation
process.
Nitrogen Bottle (Use
for Brazing and
A
i
r
-Tight Test)
(Note1) Whether it is a large room, medium room, small room or tiny small room,
the amount of refrigerant leakage is all 30kg.
(Note2) The concentration must not exceed the maximum permissible concentration
0.3k
g
/ m3.
The total amount of refrigerant within the system: 30kg
Example
Indoor
Outdoor
Large Room
Medium Room
Small Room
Ventilation
Outlet
Refrigerant Pipe
mechanical ventilation devicesrefrigerant
leakage detector alarms devices
Excess or insufficient additional refrigerant will result in
compressor failure or other abnormal conditions, be sure
to charge refrigerant according to the calculated values.
Liquid piping must be insulated. (To prevent poor
performance and low pressure pipe surfaces condensation.)
Be sure to check the refrigerant leakage. If a large amount of
refrigerant leaks, it will cause the following phenomena
1. Lack of oxygen.
2. Harmful gases would occur if a fire was being used in the
room
.
Liquid Line Stop Valve
Gas Line Stop Valve
Manifold Gauge
Vacuum Pump
Refrigerant
Cylinder (R410A)
Weight Scale
Thermal Insulation
Material Wrapping
Outdoor Unit
Capacity (HP)
Cooling Capacity
(ton)
R410A
8~12 4.11
14~16 6.48
18 6.54
20 8.22
22~26 10.59
28~32 12.96
24 13.02
26 13.08
28~40 14.70
42 14.76
44~46 17.13
48 17.19
50~52 19.56
54 19.62
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32